1 Introduction

Engineers and architects are often faced with the problem to increase the shear strength of historic unreinforced masonry (URM) walls. The poor quality of historic masonry is a factor of serious vulnerability that often makes difficult or impossible to design upgrading interventions in response to static and dynamic forces caused by earthquakes. The need to meet anti-seismic standards leads to the use of new reinforcement materials that are able to ensure an improvement of the mechanical properties of the walls. However this may cause the demolition of portions of buildings or the application of intrusive and non-reversible retrofitting techniques.

Following the destructive 1976 earthquake in northern Italy and Slovenia, technicians started studying the problem of conservation and upgrading of ordinary historic constructions. In the following years a series of new techniques were proposed and applied. Most of these are now regarded as “traditional” because they used standard materials like steel profiles and concrete. Surface treatments [1], grout injections [25], external reinforcements [6, 7] are examples of such conventional techniques.

Some of these strengthening techniques, such as steel jacketing and injections of cement- or lime-based grout, which were widely used in the reconstruction work following the earthquakes in the 80s presented several negative issues over time in terms of effectiveness and durability [8, 9]. The use of steel meshes embedded into cement-based mortars often leads to corrosion problems with loss of capacity and variation in volume and causes overstated increases of wall shear stiffness. The application of grout injection for stonewalls with no voids or cracks within the core makes this retrofitting intervention ineffective due to the impossibility for the grout to penetrate into the wall.

The most recent research studies have thus been directed towards different techniques, such as those which provide for bonding with composites materials (FRP: fiber reinforced polymers) [1018]. Guidelines for the application of FRP materials to masonry were issued by the Italian founding research council (CNR) in 2003 [19]. Many advantages are associated with the use of FRPs, but their application is not entirely problem-free. Some drawbacks are attributed to the epoxy resins used to impregnate the reinforcing fibres: poor behavior at temperatures above the glass transition temperature and negative long-run effects, high cost of epoxy resins, potential hazards for the manual worker, difficulty in removal or irreversibility of the retrofitting intervention. The use of epoxy resins also prevents water–vapor permeability and its fire resistance is very low. In many cases heritage conservation authorities do not permit an extensive use of epoxy resins on listed buildings.

A promising solution to the above issues would be the replacement of epoxy resins with inorganic lime or cement mortars [2022] to embed FRP bars or grids. The compatibility of inorganic matrices with historic masonry is extremely high: inorganic matrices, especially when lime-based, are similar in composition and mechanical properties to historic mortars.

However the need to insulate masonry walls, frequently the case in work done on historic-monumental buildings, greatly limits the choice of retrofitting methods. This is often needed for both relatively thin solid brick and thick stone walls. In a thick triple-leaf stone wall there are inner and outer leafs with a loose rubble fill between, almost a cavity wall and the inner surface is usually plastered with lime. Any increase in temperature in a stonework construction is lost very quickly because these walls work by allowing air to pass from inside to out.

The application of thermal insulating mortars is aimed to face the problem of energy consumption and represents an interesting solution to reduce heat loss in historic buildings. Thermal insulating mortars are usually cheap, easy to apply and compatible with historic mortars and bricks/stones. The replacement of steel meshes with composite materials embedded into thermal insulating mortars offers a solution to the problems typically faced in traditional steel meshes in concrete while the flexibility of this strengthening technique allows both indoor and outdoor applications, with different substrates (brick or stone work).

This paper presents the results of a series of tests on square wall panels reinforced with GFRP meshes embedded into lime-based mortars: both mechanical testing and thermal conductivity analyses have been performed to address the problem of the effectiveness of the proposed reinforcing technique.

2 The strengthening technique

The strengthening technique is very similar to the traditional steel jacketing for masonry wall panels: in place of a metal mesh, a GFRP grid is inserted into a thermal insulating mortar. Four different thermal insulating mortars have been used in this investigation. GFRP and thermal insulating mortars underwent a mechanical and thermal characterization.

GFRP grid used in the experimental campaign is produced by Fibre Net (Udine, Italy) and is made of a 66 mm square mesh fabricated with an AR (Alkali Resistant) glass fiber with a zirconium content greater than 16 % impregnated with an epoxy-vinylester resin.

Before carrying out the present experimental investigation, the GFRP grid’s mechanical properties were tested. The ultimate tensile strength of the impregnated roving constituting the grid are 530 and 680 MPa in weft and warp directions, respectively. GFRP material exhibits a linear elastic response up to failure with a modulus of elasticity of 36.1 (weft dir.) and 39.8 GPa (warp dir.). Strain at fracture is between 1.7 and 1.9 % (Table 1).

Table 1 GFRP grid mechanical properties

The strengthening technique consists in the removal of all existing plaster back to the masonry (it is also possible to use a small cold chisel to remove any plaster left on the face of the masonry and to remove the loose pulverulent mortar from between the brick or stone blocks to a depth of 10–15 mm to increase the bonding between existing masonry and new coating). Before the application of the fist layer of thermal insulating mortar it is necessary to dampen the masonry by using a spray of clean water or flicking a brush. GFRP grid should be applied when the mortar is still wet. For multi-leaf walls (mainly stonemasonry).

GFRP transversal connectors can be used to bond masonry leaves. Each connector is made up of two fiberglass L shaped bars joined together by injecting them with epoxy paste into a transversal hole drilled in the masonry wall. Lastly a second layer of the thermal insulating mortar can be applied by sprayer or hand in a thickness of about 50 mm (for a single-layer reinforcement the total thickness of the GFRP-reinforced coating is 100 mm). Despite the presence of the GFRP grid, the application of thermal insulating mortar is not difficult, thanks to the large size of the meshes (Fig. 1).

Fig. 1
figure 1

GFRP grid

The first thermal insulating mortar (Type RO, Röfix Calce Clima) is characterized by a compression strength of 0.7 MPa according to the producer’s data sheet. It is a ready-to-use hydraulic lime-based mortar with a small volume percentage of aerial lime, limestone sands and light mineral aggregates: it is light and completely natural.

The second mortar (Type D) is a hydraulic-based lime with the addition of granules of cork (diameter smaller than 0.3 mm). It is on the market with the commercial name Diathonite Evolution and it is characterized by a compression strength of 2.7 MPa according to the producer’s data sheet. The producer of the second mortar is Diasen.

The third (Type R2) and fourth (Type C) mortars were specifically studied and supplied respectively by Röfix and CVR in order to achieve both high mechanical characteristics and good insulating properties. Also the mortar Type C is composed by lime, aggregates and other additives with high mechanical strength. The lightness of all the tested mortars contributes to obtain good thermal insulating properties.

All mortars are non-cement based and have been subjected to mechanical characterization [23, 24] and results expressed in terms of compressive strength [25], tensile splitting strength [26], Young’s modulus [27] are reported in Table 2. The choice of mortars with no-cement content was dictated by the need to meet the requirement of heritage bodies and to have good insulating properties. The mortars’ mechanical properties were determined by compression and tensile splitting tests on cylindrical samples approximately 94 mm in diameter and approximately 180 mm in height. Compressive strength of mortar at 30 days after casting has been measured. Sixteen cylindrical samples (four for each type) were tested and the lowest and highest mean mortar strength was 0.72 and 2.70 MPa, respectively for mortars Type RO and C.

Table 2 Properties of thermal insulating mortars

The mechanical properties of the bricks and mortar used for the construction of the wall panels were also measured. The compressive and tensile splitting strength of mortar was obtained in laboratory and results are results are given as the mean strength value and coefficient of variation (Table 3).

Table 3 Properties of bricks and mortar used for panel construction

3 Thermal performance of retrofitted masonry walls

The thermal performance of the GFRP-reinforced mortars were experimentally evaluated by means of an experimental apparatus designed and built at the Laboratory of Thermal Science, University of Perugia (Small Hot-Box). It is composed by a hot and a cold side (with a difference of temperatures of about 20 °C) [28].

The thermal resistance of the mortars was evaluated by means of the thermal flux meter methodology consisting in the measurement of the heat flux through the sample and the surface temperatures in the cold and hot sides of the specimen. A typical trend of the surface air temperatures and of the heat flux during a test is represented in Fig. 2.

Fig. 2
figure 2

Typical trends of surface temperatures and heat flux through a specimens during a test (duration approximately 4 h)

All the samples were assembled with external dimensions 300 × 300 mm, for a total area of 0.09 m2, due to the dimensions of the experimental apparatus. At first a specimen composed by only plasterboard without coating was tested (specimen PL) as support panel for the mortars. The coatings were analysed with different chemical compositions, with and without a glass fiber reinforced polymers grid, characterized by square mesh with dimensions of 60 × 60 mm, inserted into the matrix [29]. The description of the coatings, the total thicknesses of the specimens and the measured thermal resistances and conductivities of the composed samples (plasterboard + final coating) are reported in Table 4.

Table 4 Description of the samples for thermal measurements

The total thermal resistance R of the sample is composed by two contributes: the coating and the plasterboard one (Eq. 1). By using this equation it is possible to evaluate only the thermal conductivity of the coatings λ c.

$$R = \frac{{s_{\text{c}} }}{{\lambda_{\text{c}} }} + \frac{{s_{\text{p}} }}{{\lambda_{\text{p}} }}$$
(1)

where s c and s p are the thicknesses of the coating and the plasterboard, respectively.

The measured thermal conductivity of the mortars (Types RO and D) is 0.105 W/(mK) (without fiber reinforced grid), while considering the glass fiber reinforced grid (RO-FRP and D-FRP), 0.089 and 0.092 W/(mK) were respectively found, with a reduction of about 15 and 12 %. Also mortar R2 and C were examined but the thermal insulating properties of these types are not so meaningful above all for mortar Type C (0.096 W/(mK) was measured for R2-FRP and 0.210 W/(mK) for C-FRP): for the sake of brevity only the mortar types D-FRP and RO-FRP were considered in the following final application analysis.

For an in-deep analysis, the thermal transmittance U of typical masonry walls can be calculated [30, 31] before and after the refurbishment action, in order to evaluate the effectiveness of the application of the mortars. Two walls were considered: the first one is a brick wall internally and externally lime plastered (total wall thickness s total = 0.33 m, U = 1.61 W/(m2K)), the second one is a cavity masonry wall with a total thickness of 0.28 m and a U-value of 1.10 W/(m2K).

As shown in Table 5, by applying 45 mm of the mortars types RO-FRP and D-FRP, the U reductions of the walls vary within 34 and 45 %. Generally the U decreasing is more evident when the original thermal transmittance of the wall is higher (wall type n.1).

Table 5 Thermal transmittance values of different walls before and after the insulating plasters application

4 Mechanical testing

4.1 Test set-up

In order to study the shear behavior of the wall panels reinforced with thermal insulating coatings, 10 wall panels were assembled in laboratory and then tested in diagonal tension. Diagonal tension test is being widely used by the research community to develop knowledge on in-plane behavior of masonry walls. Figure 3 illustrates the test setup. A compression load was applied diagonally through a 500 kN capacity hydraulic jack mounted at the top edge and activated by a hand pump. Loading steel shoes were positioned on the panel’s diagonally-opposite corners. Two steel ties connected the loading shoes and a digital pressure transducer was applied on the hydraulic jack to measure the magnitude of the diagonal compression load. Four inductive linear transducers (LVDT) were installed along the panel four diagonals on each face to measure its shortening and elongation. The diagonal compression load was applied in stepped cycles of loading and unloading using the manual pump, where the last cycle was continued till failure. All data were recorded by using a Spider8 data acquisition system operating Catman software at a frequency of 2 Hz. Figure 4 shows the location of the instruments (LVDT, hydraulic jack, loading shoes) that was common to all specimens.

Fig. 3
figure 3

Schematic arrangement of the test lay-out

Fig. 4
figure 4

Test apparatus arrangement

Diagonal tension test is standardized in accordance to ASTM [32] and RILEM [33] standards. In the test setup according to ASTM, weight of the masonry wall is assumed to be disregarded compared to applied loads.

The RILEM interpretation of the test is based on a model of the masonry panel as if it is an isotropic and homogeneous material and a linear elastic analysis: the stress state in terms of normal (σ x and σ y ) and shear stresses (σ xy ) at the centre point of the panel:

$$\sigma_{x} = \sigma_{y} = - 0.56\frac{P}{{A_{n} }}\quad \sigma_{xy} = 1.05\frac{P}{{A_{n} }}$$
(2)

in which P the diagonal compression load and A n is the cross- section of the wall panel, calculated as the average of the width and height of the specimen multiplied by its thickness. According to RILEM interpretation, the masonry tensile strength f t is:

$$f_{\text{t}} = 0.5\frac{P}{{A_{n} }}$$
(3)

According to the Turnšek and Čačovič [34] formulation, the shear strength τ is:

$$\tau = \frac{{f_{\text{t}} }}{1.5}$$
(4)

Furthermore it is possible to calculate the shear modulus G (secant value of the modulus at 40 % of the peak load) defined as:

$$G = \frac{{\sigma_{xy,0.4} - \sigma_{xy,i} }}{{\gamma_{0.4} - \gamma_{i} }}$$
(5)

where σ xy,0.4 and γ 0.4 are the shear stress at 40 % maximum load and the angular strain at the corresponding strain value, respectively. The initial stress and strain (σ xy,i and γ i ) were taken at a load level of 10 % of the maximum diagonal load.

The angular strain γ is expressed as:

$$\gamma = \varepsilon_{\text{c}} + \left| {\varepsilon_{\text{t}} } \right|$$
(6)

where ε c and ε t are the strains associated with the panel diagonals in compression and tension, respectively.

For both unreinforced and reinforced wall panels brickwork pattern was made from all headers (header bond pattern) on each course. Panels were assembled in laboratory using for construction a lime-based mortar. This bond pattern was chosen because it is frequently encountered in Italy for eighteen–nineteenth century constructions.

5 Test results

Although the resistance to in-plane forces is the key parameter to address the effectiveness of the proposed retrofitting technique, other factors such as the shear modulus, ductility and deformability, failure modes, stiffness and strength degradation from multi-cycle loading have been considered in this study. The different tests will hereafter be referred to by their number and letter designation. While the numerical designation will be different for each test, the letter designations indicate unreinforced panels (UR) and the type of mortar used for reinforcement (RO, D, R2 and C).

5.1 Un-reinforced panels

With regard to un-reinforced panels the shear stress-angular strain curves show an initial quasi-elastic behavior followed by a nonlinear decrease in shear stress in the plastic region. The non-linear plastic behaviour of masonry response was produced by progressive diagonal cracking. In fact, all un-reinforced panels exhibited a failure along the compressed panel diagonal. Failure initiated in the central part of the wall panel when the diagonal compression force exceeded the in-plane strength capacity of the panel: diagonal cracking opened slowly in the mortar joints and expanded toward the panel extremities (corners) (Fig. 5). The failure produced and an abrupt loss of lateral stiffness (shear modulus). Two unreinforced brickwork panels have been tested and the average lateral capacity and shear strength τ were respectively 201.1 kN and 0.230 MPa while the shear modulus G was 4078 MPa. Results are summarized in Table 6 and Fig. 6.

Fig. 5
figure 5

Detail of failure (unreinforced panel)

Table 6 Test results
Fig. 6
figure 6

Shear stress versu angular strain curves for unreinforced panels: a 35-UR, b 36-UR

Another point which needs to be mentioned is the low scattering of results in terms of shear strength (0.234 and 0.226 MPa for test No. 35-UR and 36-UR, respectively) and to some extent also for shear modulus (4466 and 3691 MPa).

5.2 Reinforced panels

Eight reinforced masonry panels were subjected to the diagonal tension test. For all reinforced panels, the masonry is initially uncracked and has a linear elastic response. A single test was performed on each wall panel. Table 6 gives peak lateral compression loads, shear strengths and moduli for each test.

For panels reinforced with mortar Type RO, the results obtained did not show significant increases both in terms of shear strength and stiffness. The lateral load-capacity and stiffness (shear modulus) values became, respectively 215.6 kN and 4829 MPa with a limited increment of 7 and 18.4 % compared to the values measured for the control panels. This result substantially showed that the proposed technique is essentially ineffective when inappropriate thermal insulating mortars are used.

The stress–strain curve shows a quasi-elastic behaviour with a post-cracking pseudo-ductile response. Peak diagonal load was 247.5 kN for panels reinforced using mortar Type D (33-D and 34-D). The results obtained for the diagonal tension tests carried out on the panel reinforced with this mortar showed a limited increase in terms of lateral capacity (+23 %) while the shear modulus G (−0.6 %) did not change.

Increases in strength (ultimate) from 57 to 62 % and 109 to 115 % compared with control panels were achieved for wall panels strengthened with GFRP reinforced mortars Type R2 and C, respectively. Ultimate diagonal compression loads for these strengthened panels ranged from about 315 to 431 kN. Again the stiffness and deformation capacity of the wall panels was not highly changed by the application of the strengthening.

In-plane resistance of reinforced masonry wall panels is mainly based on tensile strength and stiffness of the thermal insulating mortars: mortar coatings have the function to transfer the tensile load from the substrate (masonry) to the GFRP grid reinforcement and to resist to compression loads. Low tensile strength mortars are unable to act on this issue leaving the reinforcement essentially unloaded and ineffective.

Figures 7 and 8 record the crack pattern in the masonry face for panels strengthened with GFRP-reinforced mortars Type D and RO, respectively. For all reinforced panels, the failure modes are characterized by a similar cracking pattern as those of the un-reinforced. The failure mechanism consisted in the formation of diagonal cracks along the compressed diagonal observed on mortar surface. Panels failed by rapid propagation of diagonal cracks, which followed the mortar joints and by separation of the GFRP coating from the masonry substrate. Tensile or shear failure of the strengthening never occurred in the GFRP grid, but failure by debonding initiating at the concentration of interfacial shear stress in the center of the panel and by the formation of diagonal cracks on the thermal insulating mortars.

Fig. 7
figure 7

Reinforced panel after failure (panel reinforced with mortar Type D)

Fig. 8
figure 8

Detail of the failure mode (panel reinforced with mortar Type RO)

Behavior of each reinforced specimen is illustrated in the shear stress versus angular strain plots shown in Fig. 9 (with the exception of test 38-R2 where angular strain was not recorded). From these results, a clear tendency is shown: the reinforcing technique can increase the lateral load-capacity of the masonry only if a thermal insulating mortar with good mechanical properties is used (compressive strength higher than 0.9–1.4 MPa, Young’s Modulus higher than 1.1–1.3 GPa). It is clear that these values depend on the mechanical properties of the substrate (masonry) and on the panel and coating thicknesses, but the emerging line seems to be correct and acceptable for standard one-brick-thick (25 cm) walls bonded with lime-based mortars hence allowing the considerations reported above.

Fig. 9
figure 9

Load-deflection response for all wall panels tested

For reinforced panels the diagrams underline two stages of the global behaviour: a first linear elastic and a second plastic produced by the progressive cracking of both the bed joint and coating reinforcing mortars. The post-cracking phase of the curves of the reinforced panels are characterized by reduced stiffness and a similar almost horizontal slope as those un-reinforced. Thus, an important consequence of the reinforcement is the increase of the shear strength of the wall while leaving unaffected the in-plane stiffness.

The GFRP grid reinforcement is initially fully bonded and acts compositely with brickwork masonry. Since the shear stiffness is not significantly greater than for the unreinforced wall panels, the composite reinforcement does not at first increase the lateral diagonal compression load carried by the wall. For an angular strain of approximately 0.4 ‰, diagonal cracks form in the bed joints of the brickwork masonry and the GFRP grid start to work. This continues until the thermal insulating mortar starts cracking or to separate and debond from the masonry.

6 Conclusions

Historic buildings with load bearing brick walls are very common in many European and American cities. While these thick brick walls are often plastered on one or both sides, they are usually not insulated and may present serious problems to resist to horizontal in-plane loading produced by seismic actions.

This paper presents an experimental investigation on the behavior of in-plane loaded masonry panels retrofitted with an innovative method made of a GFRP grid inserted into a thermal insulating jacketing mortar. Four different thermal insulting mortars have been experimented and results have highlighted limitations and advantages of the proposed technique but in conclusion demonstrating the feasibility of using GFRP grids inserted into thermo-insulating mortars for both insulating and reinforcing masonry wall panels. The GFRP grid upgrade with thermal insulating mortar is promising, but less effective compared to the reinforcement with epoxy resins or steel reinforced concrete coatings [4, 6, 9].

The following remarks may be drawn from this investigation:

  1. 1.

    The externally applied GFRP mesh to masonry panels resulted in a stronger system, as compared to the un-reinforced configuration. The addition of the GFRP grid embedded in thermal insulating mortars resulted in an increase in lateral load capacity between 7 and 117 %;

  2. 2.

    The reinforcing technique can increase the lateral load-capacity of the masonry only if a thermal insulating mortar with high mechanical properties is used (Types R2 and C);

  3. 3.

    The shear in-plane stiffness of reinforced panels remains essentially unaffected by the application of the reinforcement;

  4. 4.

    When low-strength lime-based thermal insulating coatings (Types RO and D) are used, the tests have highlighted the fact that the adhesion between the panels and the lime-based mortars used as a base for reinforcements (GFRP mesh) was the weakest element in the strengthening system. As the shear stiffnesses of the panel and reinforcement start to differ significantly due to diagonal cracking in the brickwork, the failure resulted from the separation of the layer of thermal insulating mortar from the masonry panels. This continues until the thermal insulating mortar also starts cracking.

  5. 5.

    The thermal performance of the innovative fiber-reinforced insulating coatings were also studied. The thermal conductivities of samples RO and D were measured by thermal flux meter method by using an experimental Small Hot-Box apparatus. A similar behavior was found considering the thermal performance of only the coating without reinforced mesh (λ = 0.105 W/(mK)). The GFRP grid allows an improvement for both the samples (a reduction of the thermal conductivity of about 12–15 %), probably due to air included in the mixture. Both the insulating coatings are efficient in building refurbishment also thanks to their thermal properties (U-reduction of about 35–45 % obtained by applying 45 mm of the coating).

Existing analytical formulations cannot fully explain tests results, based only on the variation of the type of thermal insulating mortar. Future work will concentrate on evaluating the accuracy for detecting the lateral capacity using innovative analytical and numerical assessments.