1 Introduction

As we know that nowadays the power generation and transmission systems are in operation under more and more emphasize state and are experiencing to rise the power loss due to increasing demand, environmental and economic or financial restriction, along with a competitor energy industry [1], so there are some needs to make better power demand, the standard of power, and preferably the growing of DG and the problems of global warming to the environment. Dispersed generation can the little or intermediate power plant installation was neighboring to the statistical distribution supply to the high voltage of electrical power transmitting and distribution to the proper of the supply to the consumer endmost [2]. The demand for energy is anticipated for the increase is 39% by 2040 [3]. To determine the optimum DG allocation optimum bus location and more size of DG units and reduced the total power loss in the distribution systems [4]. Consequently, the significant figure of the literature has dedicated to the region, along with the different method purpose the minimization of the real power system [5,6,7,8,9,10,11], and active power loss minimization [12,13,14,15]. Moreover, decreasing the loss of energy and better voltage profile to the distributions system has prepared the multi-objective function (MOF) [16, 17]. In the difference imaginary power losses, the consciousness. More advantages connected as well as improved the reactive power. As long as the decrease imaginary power consumption and the upgrade system, voltage drop, increase network load capacity and the assistance to the transmission line.

The author has been considered condition minimizations of reactive power losses in the single objective functions [18,19,20]. The use of meta-heuristic procedures is solving to the DG allocation difficulty termination the analytical and classical approach. Different methods are artificial bee colony algorithm (ABC) [21], gravitational search algorithm (GSA) [22], bat optimization algorithm (BAT) [23], particle swarm optimization (PSO) as well as constriction factor approach [24], flower pollution algorithm (FPA) [25], modified teaching learning-based optimization (MTLBO) [26], backtracking search algorithm (BSA) [27], krill heard algorithm (KHA) [28], moth flame optimization (MFO) [29], sine cosine algorithm (SCA) [30], crow search algorithm (CSA) [31]. The procedure of optimization based on the unique hunting, searching for prey, encircling prey, and attacking prey of grey wolf optimization’s is applied to find the optimum location and size of DG in a power distribution network. The motive of developing as the meta-heuristic algorithms is to reduction find the place.

The main contributions of this paper are summarized

  • The proposed methods that have been applied on standard IEEE-16, 30, 57 and 118 radial bus test distribution systems along considering multiplier DG power losses minimization and get a better voltage profile improvement.

  • Comparison results along with type 3 DG at 0.9 pf and with type DG at unity pf obtained by the proposed algorithm along with the optimum location and size of DG as obtained by the GWO is more effective and voltage profile.

  • The proposed algorithm is compared as well as from the VSI, CPLS and NM method given the superior solution.

The rest of the paper as per the following: Sect. 2 arrangement the problem formulation, Sect. 3 described the GWO method, Sect. 4. The detail explanation analysis and parameters of IEEE-16, 30, 57 and 118 bus distribution system percentage loss reductions and then also convergence characteristics curves respectively and finally Sect. 5 has been present in conclusion.

2 Result and Discussions

The proposed algorithm has been executing by MATLAB 2015a and the IEEE-16, 30, 57, and 118 buses of the radial distribution system. The main aim of loss minimization has been executing using GWO, which has been valuing as well as the population is 50, and the maximum iteration is 200. The objective function is to decide the optimum location and size of DG in the radial distribution networks and the power loss minimization. The detail algorithm methods of working by flow chart gradually. The proposed algorithm is compared as well as from the VSI, CPLS and NM methods [35], given the superior solution.

2.1 Problem Formulation

The problem formulation is to define the size of DG, optimal location in the reduction of distribution network, to the active power loss in the distribution system, and the active power is produced and to the operate the DG is evaluated.

$$minimize {f}_{i}\left(x,u\right), i=\mathrm{1,2},\mathrm{3,4}\dots {N}_{obj},$$
(1)
$$Subject to \mathrm{g}\left(x,u\right)=0,$$
(2)
$$h\left(x,u\right)\le 0,$$
(3)

2.2 Objective Function

The objective function is (I2R), or system power loss minimization in the section power flow of b/w buses k and i at bus k is given, Fig. 1, in this system the reactive power is neglected,

Fig. 1
figure 1

Single line diagram of radial distribution system

$${S}_{{DG}_{i}}={P}_{{DG}_{i}}^{Loss}+j{Q}_{{DG}_{k}}^{Loss}$$
(4)
$${S}_{\overrightarrow{D}{G}_{i}}={P}_{\overrightarrow{D}{G}_{i}}^{Loss}+j{Q}_{\overrightarrow{D}{G}_{k}}^{Loss}$$
(5)
$${S}_{ik}={P}_{ik}^{Loss}+j{Q}_{ik}^{Loss}$$
(6)
$${S}_{ik}={V}_{i}{I}_{ik}^{*}$$
(7)
$${S}_{ik}={V}_{i}{(V}_{i}^{*}-{V}_{k}^{*}){Y}_{ik}+{V}_{i}{V}_{i}^{*}{Y}_{ik0}$$
(8)
$${S}_{ki}={V}_{i}{(V}_{k}^{*}-{V}_{i}^{*}){Y}_{ki}+{V}_{k}{V}_{k}^{*}{Y}_{ki0}$$
(9)

Consequently, the addition of the power flow in Eqs. (5) and (6), and the power loss system in between buses i and k,

$${S}_{DG}^{Total Power loss}={S}_{ik}+{S}_{ki}$$
(10)

The overall in a power loss system to get along with the branches of power flow and the total power loss inside the slack bus be able to get the power flow along with sum at the finished bus,

$${F}_{loss}^{Power}=real\left[{\Sigma }_{i=1}^{n}{S}_{DG}^{Total Power loss}\right]$$
(11)

2.3 Constraints

They consist of voltage magnitude and true power, including DG. The variation is according to them, and they are restricted to be inside the constraints through the optimization performance. These systems are changing in the identified the following,

$${V}_{i}^{min}\le {V}_{i}\le {V}_{i}^{max} \forall i\varepsilon NG$$
(12)
$${P}_{DG}^{min}\le {P}_{\overrightarrow{D}{G}_{i}}^{Total}\le {P}_{DG}^{max} \forall i\varepsilon NG$$
(13)
$${Q}_{i}^{min}\le {Q}_{i}\le {Q}_{i}^{max} \forall i\varepsilon NG$$
(14)
$${ \emptyset}_{ik}^{min}\le { \emptyset}_{ik}\le { \emptyset}_{ik}^{max} \forall i\varepsilon NG$$
(15)
$${I}_{ik}^{min}\le {I}_{ik}^{max} \forall i\varepsilon NG$$
(16)

2.4 Equality Constraints

The equality constraints are the stability power generations, load flow power, load demand, and power losses [33, 34],

$${S}_{i}={P}_{ik}+j{Q}_{i}^{*}={V}_{i}{I}_{i}^{*}$$
(17)
$${S}_{i}={V}_{i}{\sum\limits_{k=1}^{n}{V}_{k}^{*}}{Y}_{ik}^{*}={\sum\limits_{k=1}^{n}}|{ V}_{i}\left|{V}_{k}\right|\left|{Y}_{ik}\right|<\left({\delta }_{i}-{\delta }_{k}+{ \emptyset}_{ik}\right)$$
(18)

Solve the real and imaginary parts, after then the power load flow mathematical problem without DG are given,

$${P}_{i}={\sum\limits_{k=1}^{n}}|{ V}_{i}\left|{V}_{k}\right|\left|{Y}_{ik}\right|cos\left({\delta }_{i}-{\delta }_{k}+{ \emptyset}_{ik}\right)={P}_{G,i}-{P}_{D,i}=0 \quad \forall i\varepsilon nb$$
(19)
$${Q}_{i}={\sum\limits_{k=1}^{n}}|{ V}_{i}\left|{V}_{k}\right|\left|{Y}_{ik}\right|sin\left({\delta }_{i}-{\delta }_{k}+{ \emptyset}_{ik}\right)={Q}_{G,i}-{Q}_{\overrightarrow{D,}i}=0 \quad \forall i\varepsilon nb$$
(20)

The basic power balance equation,

$${P}_{G,i}={P}_{D,i}+{P}_{L}$$
(21)
$${Q}_{G,i}={Q}_{\overrightarrow{D,}i}+{Q}_{L}$$
(22)

The power flow losses as well as the DG the true power generation units operate in unity pf, then the mathematical problem of power flow is given.

The DG is an active power source only at unity pf, so the \({Q}_{DG,i}=0\),

$${P}_{i}+{P}_{DG,i}={P}_{D,i}+{P}_{L}$$
(23)
$${Q}_{i}={Q}_{\overrightarrow{D},i}+{Q}_{L}$$
(24)

The last power flow mathematical problem for the distribution system,

$${\sum\limits_{k=1}^{n}}|{ V}_{i}\left|{V}_{k}\right|\left|{Y}_{ik}\right|cos\left({\delta }_{i}-{\delta }_{k}+{ \emptyset}_{ik}\right)+{P}_{DG,i}={P}_{D,i}+{P}_{L}$$
(25)
$${\sum\limits_{k=1}^{n}}|{ V}_{i}\left|{V}_{k}\right|\left|{Y}_{ik}\right|sin\left({\delta }_{i}-{\delta }_{k}+{ \emptyset}_{ik}\right)={Q}_{\overrightarrow{D,}i}+{Q}_{L}$$
(26)
$${\sum\limits_{k=1}^{n}}|{ V}_{i}\left|{V}_{k}\right|\left|{Y}_{ik}\right|cos\left({\delta }_{i}-{\delta }_{k}+{\emptyset}_{ik}\right)+{P}_{DG,i}-{P}_{D,i}-{P}_{L}=0$$
(27)
$${\sum\limits_{k=1}^{n}}|{ V}_{i}\left|{V}_{k}\right|\left|{Y}_{ik}\right|sin\left({\delta }_{i}-{\delta }_{k}+{ \emptyset}_{ik}\right)-{Q}_{\overrightarrow{D,}i}-{Q}_{L}=0$$
(28)

3 Methods

3.1 Grey Wolf Optimizations Methods

Grey wolf belongs to the Candidate family they are mainly considered as apex predators, and it means that they are at the topmost of the food series. Grey wolves generally like to live in a collection. These classifications usually are 5–12. It is an incredibly harsh, community superiority hierarchy.

3.2 The Aim, Design, and Setting of the Study

Figure 2a shows the steps of the hierarchy are small from alpha (α) to omega (ω) search agents. All take the decisions regarding sleeping place, hunt, and waking time. The alpha (α) choice is dictated to the pack. Beta (β) are supporting wolves that assist the (α) indecisiveness making and reinforces the (α) commands throughout.

Fig. 2
figure 2

a The level of the hierarchy from the top down. b The flow chart of proposed grey wolf optimization.

Moreover, (β) working such that response source for alpha (α), as well as the delta (δ) wolf’s reportage to alpha and Beta. Moreover, omega (ω) is an assistant and to the lowest degree level of hierarchy [32].

The general assumption for mathematical modeling:

  • The GWO in the algorithm for the social hierarchy, alpha (α), is said to be the best fit solution according to the Beta (β) and delta (δ) the follow such as the second and third best-fit solutions for them respectively. Grey wolf optimization algorithm is guided by the three wolves, omega (ω) wolves follow (α), (β), and (δ) and the hunting (optimization).

  • GWO first encircle prey after than the circling prey during hunting and follow to determine the encircling behavior is presented [32].

    $$\overrightarrow{K}=|\overrightarrow{B}.{\overrightarrow{Z}}_{p}\left(t\right)-\overrightarrow{Z}\left(it\right)|$$
    (29)
    $$\overrightarrow{Z}(it+1)={\overrightarrow{Z}}_{p}\left(t\right)-\overrightarrow{D}. \overrightarrow{K}$$
    (30)

where the current iteration, \(\overrightarrow{Z}\) and \({\overrightarrow{Z}}_{p}\) the position vector of a grey wolf, and the prey respectively, the vector \(\overrightarrow{B}\) and \(\overrightarrow{D}\) indicate the coefficient vectors are calculated as follow,

$$\overrightarrow{D}=2\overrightarrow{d}.{\overrightarrow{r}}_{1}-\overrightarrow{d}$$
(31)
$$\overrightarrow{B}=2.{\overrightarrow{r}}_{2}$$
(32)

where \({\overrightarrow{r}}_{1},{\overrightarrow{r}}_{2}\) are the random numbers between 0 and 1. Component \(\overrightarrow{d}\) is the linearly decreased from 2 to 0 over the course iterations.

$${\overrightarrow{K}}_{\alpha }=|{\overrightarrow{B}}_{1}.{\overrightarrow{Z}}_{\alpha }\left(t\right)-\overrightarrow{Z}\left(it\right)|$$
(33)
$${\overrightarrow{K}}_{\beta }=|{\overrightarrow{B}}_{2}.{\overrightarrow{Z}}_{\beta }\left(t\right)-\overrightarrow{Z}\left(it\right)|$$
(34)
$${\overrightarrow{K}}_{\delta }={|\overrightarrow{B}}_{3}.{\overrightarrow{Z}}_{\delta }\left(t\right)-\overrightarrow{Z}\left(it\right)|$$
(35)
$${\overrightarrow{Z}}_{1}={\overrightarrow{Z}}_{\alpha }\left(t\right)-{\overrightarrow{D}}_{1}.\left({\overrightarrow{K}}_{\alpha }\right)$$
(36)
$${\overrightarrow{Z}}_{2}={\overrightarrow{Z}}_{\beta }\left(t\right)-{\overrightarrow{D}}_{2}.\left({\overrightarrow{K}}_{\beta }\right)$$
(37)
$${\overrightarrow{Z}}_{3}={\overrightarrow{Z}}_{\delta }\left(t\right)-{\overrightarrow{D}}_{3}.\left({\overrightarrow{K}}_{\delta }\right)$$
(38)
$$\overrightarrow{Z}\left(it+1\right)=\frac{{\overrightarrow{Z}}_{1}+{\overrightarrow{Z}}_{2}+{\overrightarrow{Z}}_{3}}{3}$$
(39)

The GWO exploration and exploitation capability are appeared for by the prey for grey wolves find out and aggressively, [32].

3.3 Execution of the GWO for Optimum DG Allotment

Some steps execute GWO to get the optimum allocation (i.e., site and size). The method is explained by the flowchart Fig. 2b. The already to determine the maximal number of iterations, the dimension of the problem and the number of search agents are implemented [39].

3.3.1 Step 1—Starting

The system study line data, load data calculate power flow and use the Newton–Raphson power flow method.

3.3.2 Step 2—Positions of Grey Wolf Generation

Search agent population is randomly generated by a GWO, and the initialized positions are (α), (β) and (δ) wolves, the setting for the parameter (size of DG, number, location, max. iteration ands population), after then every population for the objective function is to the calculation by the procedure of load flow.

3.3.3 Step 3—Standard Explanations

Every search agent constraint is investigated, and if the constraints are confirmed, after then the calculation of Multiobjective function (MOF) only just in case the infringement constraints the outcome is abandoned.

3.3.4 Step 4—Select the Finest Location yet

Compute the power loss and store the size of DG and decided the losses for the show that efficiency load flow and the update positions wolves, for (α), (β) and (δ), except the (ω) wolf after then the updating including (ω) wolf through the used to determine now the better solved.

3.3.5 Step 5—Calculate the New Location of Search Agents

To determine the newly search agents’ positions and these operations are complete continuously.

3.3.6 Step 6—Ending

In this study, the standard has stopped the fixed maximal iterations, and the criteria are confirmed, after finishing the simulation and the optimal size of multiplier DG units and the confirmation on the whole particular distribution system of the constraints it will get it.

4 IEEE-16 Bus System

Figure 3 shows the IEEE 16-bus system of single line diagram for distribution system [36], and these system voltages is 12.66 kV, total system dynamic, reactive power loads is 1240.568 kW and 1265.478 kVAr. Including one slack bus 16 buses and 15 branches and load buses for these distribution systems respectively. The installation of real DG, reactive power losses with and without are 60.4031 kW and 55.3574 kVAr respectively in the 16-bus distribution system.

Fig. 3
figure 3

Single line diagram of the IEEE-16 radial bus test system

Table 1 shows the optimum location for the 16-bus system is 8, the size of DG is 671.645 and the minimum before voltage installed of DG units is 0.9682. The real, reactive power losses, minimized voltage later the position of dissimilar types of DG and further in case of without DG, with DG, with type 1 DG, with type 2 DG, with type 3 DG, with type DG at 0.9 pf and with type DG at unity pf. The minimized is more in case of with type 3 DG 0.9 pf when compared to other types of DG. The result shows that size of DG is maximum at lagging pf and as well as the compared size of DG to get at unity pf although the DG losses are reduction at lagging pf rather than at unity pf with DG, with due to reactive power attainable local to the loads minimizing the reactive power obtainable from the substation.

Table 1 Results of IEEE-16 bus system

Figure 4 shows the voltage profile of this system and size of DG is better at lagging pf and also voltage is a reduction to get the lagging pf compared as well as the DG at unity pf, so the necessary evaluate obtainable reactive power from the size of DG calculations and better voltage profile effects on the loss minimization. The result to acquire the observed of the reactive power is superior to the obtained as well as DG at unity pf.

Fig. 4
figure 4

Voltage profile IEEE-16 bus system

Figure 5 shows the convergence characteristics of the GWO IEEE-16 radial bus test system consequently GWO algorithm are the total minimization power losses in (kW) and 200 iterations.

Fig. 5
figure 5

Convergence characteristics of GWO IEEE-16 radial bus test system

5 IEEE-30 Bus System

Figure 6 shows the IEEE 30-bus system of single line diagram for distribution system [36], and these system voltages is 12.66 kV, total system dynamic, reactive power loads are 3620.546 kW and 2200.784 kVAr. Including one slack bus 30 buses and 29 branches and load buses for these distribution systems respectively. The installation with and without real DG and reactive power losses are 208.4592 kW and 139.6552 kVAr in the 30-bus distribution system.

Fig. 6
figure 6

Single Line Diagram of the IEEE-30 Radial Bus Test System

Table 2 shows the optimum location for the 30-bus system is 27, the size of DG is 1530.08 and the minimum before voltage installed of DG units is 0.9111. The real, reactive power losses, minimized voltage later the position of dissimilar types of DG and further in case of without DG, with DG, with type 1 DG, with type 2 DG, with type 3 DG, with type DG at 0.9 pf and with type DG at unity pf. The minimized is more in case of with type 3 DG 0.9 pf when compared to other types of DG. The result shows that size of DG is maximum at lagging pf and as well as the compared size of DG to get at unity pf although the DG losses are reduction at lagging pf rather than at unity pf with DG, with due to reactive power attainable local to the loads minimizing the reactive power obtainable from the substation.

Table 2 Results of IEEE-30 bus system

Figure 7 shows the voltage profile of this system and size of DG is better at lagging pf and also voltage is a reduction to get the lagging pf compared as well as the DG at unity pf, so the necessary evaluate obtainable reactive power from the size of DG calculations and better voltage profile effects on the loss minimized, Fig. 8 shows the convergence characteristics of GWO IEEE-30 radial bus test system consequently GWO algorithm is the total minimization power losses in (kW) and 200 iteration the result to acquire observer of the reactive power is superior to the obtained as well as DG at unity pf.

Fig. 7
figure 7

Voltage profile IEEE-30 bus system

Fig. 8
figure 8

Convergence characteristics of GWO IEEE-30 radial bus test system

Table 3 shows the comparison results of the IEEE-16 and 30 bus system with DG at 0.9 pf. When comparing as well as VSI, CPLS and NM methods, it gives better results [35].

Table 3 Comparison results of IEEE-16 and 30 bus system with DG at 0.9 pf

Table 4 shows the comparison results of the IEEE-16 and 30 bus system with DG at 0.9 pf. When comparing as well as VSI, CPLS and NM methods, it gives better results [35].

Table 4 Comparison results of IEEE-16 and 30 bus system with DG at unity pf

6 IEEE-57 Bus System

Figure 9 shows the IEEE 57-bus system of single line diagram for distribution system [36], and these system voltages is 12.66 kV, total system active, reactive power loads is 3802.190 kW and 2694.600 kVAr. Including one slack bus 57 buses and 56 branches and load buses for these distribution systems respectively. The installation with and without real DG and reactive power losses are 158.643 kW and 99.861 kVAr in the 57-bus distribution system.

Fig. 9
figure 9

Single line diagram of the IEEE-57 radial bus system

Table 5 shows the optimum location for the 57-bus system is 46, the size of DG is 1278.66 and the minimum before voltage installed of DG units is 0.9510. The real, reactive power losses, minimized voltage later the position of dissimilar types of DG and further in case of without DG, with DG, with type 1 DG, with type 2 DG, with type 3 DG, with type DG at 0.9 pf and with type DG at unity pf. The minimized is more in case of with type 3 DG 0.9 pf when compared to other types of DG. The result shows that size of DG is maximum at lagging pf and as well as the compared size of DG to get at unity pf although the DG losses are reduction at lagging pf rather than at unity pf with DG, with due to reactive power attainable local to the loads minimizing the reactive power obtainable from the substation.

Table 5 Results of IEEE-57 bus system

Figure 10 shows the voltage profile of these systems and size of DG is better at lagging pf and also voltage is a reduction to get the lagging pf compared as well as the DG at unity pf, so the necessary evaluate available reactive power from the size of DG calculations and better voltage profile effects on the loss minimization. The result to acquire the observed of the reactive power is superior to the obtained as well as DG at unity pf.

Fig. 10
figure 10

Voltage profile IEEE-57 bus system

Figure 11 shows the convergence characteristics of the GWO IEEE-57 radial bus test system consequently GWO algorithm are the total minimization power losses in (kW) and 200 iterations.

Fig. 11
figure 11

Convergence characteristics of GWO IEEE-57 radial bus test system

Table 6 shows the comparison results of the IEEE-16, 30 and 57 bus systems with DG at 0.9 pf. When comparing as well as VSI, CPLS and NM methods, it gives better results [35].

Table 6 Comparison results of IEEE-16, 30 and 57 bus system with DG at 0.9 pf

Table 7 shows the comparison results of the IEEE-16, 30 and 57 bus systems with DG at unity pf. When comparing as well as VSI, CPLS and NM methods, it gives better results [35].

Table 7 Comparison results of IEEE-16, 30 and 57 bus system with DG at unity pf

7 IEEE-118 Bus System

Figure 12 shows the IEEE 118-bus system of single line diagram for distribution system [37], and these system voltages is 12.66 kV, total system active, reactive power loads is 199,785.683 kW and 115,431.015 kVAr. Including one slack bus 118 buses and 117 branches and load buses for these distribution systems respectively. The installation with and without real DG and reactive power losses are 1298.09 kW and 976.215 kVAr in the 118-bus distribution system.

Fig. 12
figure 12

Single line diagram of the IEEE-118 radial bus test system

Table 8 shows the optimum location for the 118-bus system is 113, the size of DG is 2580.12 and the minimum before voltage installed of DG units is 0.9271. The real, reactive power losses, minimized voltage later the position of dissimilar types of DG and further in case of without DG, with DG, with type 1 DG, with type 2 DG, with type 3 DG, with type DG at 0.9 pf and with type DG at unity pf. The minimized is more in case of with type 3 DG 0.9 pf when compared to other types of DG. The result shows that size of DG is maximum at lagging pf and as well as the compared size of DG to get at unity pf although the DG losses are reduction at lagging pf rather than at unity pf with DG, with due to reactive power attainable local to the loads minimizing the reactive power obtainable from the substation.

Table 8 Results of IEEE-118 bus system

Figure 13 shows the voltage profile of these systems and size of DG is better at lagging pf and also voltage is a reduction to get the lagging pf compared as well as the DG at unity pf, so the necessary evaluate obtainable reactive power from the size of DG calculations and better voltage profile effects on the loss minimization. The result to acquire the observed of the reactive power is superior to the obtained as well as DG at unity pf.

Fig. 13
figure 13

Voltage profile IEEE-118 bus system

Figure 14 shows the convergence characteristics of the GWO IEEE-118 radial bus test system; consequently, the GWO algorithm is the total minimization power losses in (kW) and 200 iterations.

Fig. 14
figure 14

Convergence characteristics of GWO IEEE-118 radial bus test system

Table 9 shows the comparison results of the IEEE-16, 30, 57 and 118 bus systems with DG at 0.9 pf. When comparing as well as VSI, CPLS and NM methods, it gives better results [35].

Table 9 Comparison results of IEEE-16, 30, 57 and 118 bus system with DG at 0.9 pf

Table 10 shows the comparison results of the IEEE-16, 30, 57 and 118 bus systems with DG at 0.9 pf. When comparing as well as VSI, CPLS and NM methods, it gives better results [35].

Table 10 Comparison results of IEEE-16, 30, 57 and 118 bus system with DG at unity pf

8 Percentage Loss Reductions

Figure 15 shows the percentage loss reductions along with all types of DG units for IEEE-16, 30, 57, and 118 bus test systems respectively. From pie chart without DG, with DG, with type 1 DG, with type 2 DG, with type 3 DG, with type DG at 0.9 pf and with type DG at unity pf lagging gives more loss reductions.

Fig. 15
figure 15

a The percentage loss reductions IEEE-16 bus test system. b The percentage loss reductions IEEE-30 bus test system. c The percentage loss reductions IEEE-57 bus test system. d The percentage loss reductions IEEE-118 bus test system

9 Convergence Characteristics Curves

Figure 16 is the convergence characteristics curves of IEEE-16, 30, 57, and 118 bus test systems respectively. All these convergence characteristics curves GWO algorithm is converged rapidly and the objective function and 200 iterations. Consequently, the GWO algorithm is practical, reliable and able to treatment mixed-integer nonlinear optimization problems [38].

Fig. 16
figure 16

a The convergence characteristics curves of IEEE-16 bus test system. b The convergence characteristics curves of IEEE-30 bus test system. c The convergence characteristics curves of IEEE-57 bus test system. d The convergence characteristics curves of IEEE-118 bus test system

10 Conclusions

A novel nature encourages in GWO algorithm modeled based on the objective function is used to analyzing the optimum location, size of DG, it’s the minimization of system power loss and gets a better voltage profile. The procedure is standard on IEEE-16, 30, 57 and 118 radial bus test distribution systems as well as the considering multiplier DG superior consequence and gets to the GWO. When compared as well as another method and the simulation outcome show that the all-inclusive effect the DG unit voltage profile is affirmative and proportionate minimization of power losses in the distribution system is attained. Since it generates both the real and reactive power and able to interjected the better results had been attained without DG, with DG, with type 1 DG, with type 2 DG, with type 3 DG, with type DG at 0.9 pf and with type DG at unity pf.