Introduction

In gas condensate reservoirs, reservoir fluids exist initially in gaseous phase but as the reservoir pressure declines below the dew point pressure, liquids condense out of the gaseous phase. As observed in the temperature–pressure phase envelope shown in Fig. 1, gas condensate reservoirs have a temperature range greater than the critical temperature but less than the Cricondentherm (maximum temperature for which two phases can exist). Gas condensate reservoirs produce both gaseous and liquid condensates on the surface separators (Louli et al. 2012; Majidi et al. 2014; Skylogianni et al. 2015). As the initial pressure of the reservoir (indicated by point A on the phase envelope), declines isothermally to a condition below the dew-point curve (indicated by point B on the envelope), heavier fraction of the reservoir fluids condenses out of the gas phase. More liquid condenses out as the reservoir pressure decreases beyond the dew point (Almehaideb et al. 2003; Mohammadi et al. 2013; Mokhtari et al. 2013; Novak et al. 2018).

Fig. 1
figure 1

Gas condensate phase envelope

The liquid condensate forms a “ring” or “bank” around the production wells as shown in Fig. 2. This phenomenon is commonly referred to as condensate banking (Barker 2005; Hassan et al. 2019; Rahimzadeh et al. 2016). Within the reservoir pore space, the condensate bank remains immobile until its saturation exceeds critical saturation (Scc). The formation of the condensate bank around the producing well decreases the cross-sectional area available for gas flow, consequently reducing the gas production rate. From the literature reviewed, there are two main approaches to managing gas condensate banks; (i) modeling reservoir performance to predict/delay the onset of the banking, and (ii) mitigating gas condensate blockage already formed using chemical/mechanical methods. This study focuses on the second approach.

Fig. 2
figure 2

Schematics of gas condensate banking (Ikpeka et al. 2020)

Several techniques have been applied to mitigate gas condensate banking effect. One of such techniques involves the injection of solvents and alcohols such as Methanol to reduce the interfacial tension between the heavier liquid fractions and the lighter gaseous fractions (Azari et al. 2018; Cameselle and Gouveia 2018; Hassan et al. 2019). When interfacial tension is reduced between the gaseous and liquid phases, the displacement efficiency of the injected brine or gas is remarkably improved. However, this technique only provides temporary relief to the production wells. As production continues overtime, the effect of the solvent wears out and more solvents/ alcohols is required to be injected. Besides the cost of injecting the solvents into the well, the periodic shutting of the production well comes at a cost to the production company. The cost-benefit ratio of this method depends primarily on the volume and cost of Solvents/Methanol injected compared to the equivalent amount of gas produced within the time frame. An important limitation of this technique is that some reservoir clay fines and formation water is sensitive to Methanol (Al-Anazl et al. 2005). Another technique employed to mitigate condensate banking is wettability alteration of reservoir rock from water wet to preferentially gas wet using surfactant flooding, polymer flooding and nanoparticles (Fahimpour and Jamiolahmady 2014; Hassan et al. 2019; Williams and Dawe 1989). This technique results in a permanent alteration of the reservoir pore structure; permeability, and porosity. The consequence of this alteration could be severe pore throat blockage and irreversible well damage (Babadagli 2007; Dang et al. 2018; Gregersen et al. 2013). The permeability of condensate-banked region can be improved by dissolving carbonaceous materials in sandstone reservoirs through acidizing (Ansari et al. 2015a, 2017; Rossen et al. 1995; Tang & Morrow 1999). High temperature affects the effectiveness of acids and surfactants in both carbonate and sandstone reservoirs. At higher reservoir temperatures, acids react quickly with the sandstone and this limits its ability to penetrate the formation. A further technique used to mitigate condensate banking is gas injection and water-alternating-gas injection to maintain reservoir pressure above dew point pressure (Geiger et al. 2009; Hassan et al. 2019; Rossen et al. 1995; van Dijke and Sorbie 2003). While authors have investigated the use of different types of gas for re-injection purposes (Ayub and Ramadan 2019; Odi et al. 2012), for the gas re-injection to be effective, it has to be above the minimum miscibility pressure and the injected gas should be easily separated from the reservoir fluids at the surface (Ayub and Ramadan 2019; Dang et al. 2018; Garmeh et al. 2009; Hoteit 2013). However, for this method to be effective, the amount of gas injected into the reservoir must equal or be greater than the hydrocarbon produced from the reservoir (Sayed and Al-Muntasheri 2016). This presents an important limitation for this technique in the long term. An alternative technique for mitigating the effect of condensate banking involves drilling horizontal wells and hydraulic fracturing. However, this technique delays the onset of condensate banking and does not stop its occurrence (Behmanesh et al. 2018; Ghahri et al. 2018; Ghahri 2010; Hassan et al. 2019; Hekmatzadeh and Gerami 2018; Wei Zhang et al. 2019a, b). Hydraulic fracturing if not properly cleaned up can accumulate liquid within the fractures which affects the efficiency of the technique. In addition to these, the operational cost is sometimes very high and could be as much as several million dollars in the case of drilling horizontal wells (Hassan et al. 2019).

The use of electric current in facilitating the flow of condensate in a reservoir presents an interesting solution to treating condensate banking (Rehman & Meribout 2012). Previous laboratory studies done on conventional reservoirs have shown significant improvement in oil recovery when direct current is passed through the core samples (Ansari et al. 2015b; Ghosh et al. 2012; Hill 2014; Yim et al. 2017; Wentong Zhang et al. 2019a, b). Numerical investigation conducted by Peraki et al. (2018) reported an increase in oil recovery when electric current is combined with waterflooding. The improved recoveries observed in these studies were attributed to electrical double layer expansion of oil-brine-rock interface, movement of charged ions from the anode to the cathode, drag-force transfer of water molecules associated with charged ion movement, disintegration of water molecules into constituent gaseous and ionic phases, movement of colloid particles, viscosity reduction and thermal mobility of reservoir fluid (Ghazanfari et al. 2012; Haroun et al. 2009; Peraki et al. 2018; Wittle et al. 2011). Some factors affecting the efficiency of EEOR in oil reservoirs include brine salinity, hydrocarbon composition (presence of polar components as found in asphaltenes), rock mineral composition and the amount of direct current passed through the reservoir. Within the pore space of gas condensate reservoirs, formation brine containing dissolved minerals and condensate molecules (in gaseous or liquid state depending on the pressure condition) interacts with the minerals of pore walls. Direct current introduced into this pore space interacts with the brine, condensate, and surface of the pore walls. These interactions support the hydrodynamic condition of the reservoir to yield more condensate. Previous studies conducted macro-experiments using direct current on core samples saturated with brine. These experiments do not capture the interactions within the pore space. To adequately quantify the effect of electric current on gas condensate reservoirs, these interactions need to be characterized. This study attempts to capture the behavior of condensate droplet in the presence of electric current in real-time. The effect of electric current of condensate droplets is captured vis-à-vis interfacial tension changes and movement of droplets due to electric field.

Interfacial tension calculation (Pendant drop method)

In hydrocarbon recovery, a lower IFT improves the sweep efficiency of the water flood and favors recovery of more oil (Asar & Handy 1989; Thomas et al. 2009; Wagner and Leach 1966). There are many techniques available to measure interfacial tension in a fluid–fluid system and their features are described by Drelich et al. 2002. In this study, Pendant drop tensiometry (PDT) was used because of its simplicity and robustness. In PDT, the shape of the droplet is used to estimate the interfacial tension of the fluid (Berry et al. 2015; Ferri and Fernandes 2011; Loglio et al. 2011). By extracting the dimensions of the condensate droplet, the interfacial tension can be estimated using the dimensionless shape factor as captured in Fig. 3 (Drelich 2002; Stauffer 1965). The equatorial diameter of the droplet D, and the diameter d, at a distance D from the tip of the droplet are all measured. The dimensions are taken just before droplet breaks-off to ensure a maximum D.

Fig. 3
figure 3

Estimating interfacial tension using Pendant drop method

The interfacial tension is then calculated from the following equation:

$$\begin{gathered} \gamma = \frac{{\Delta \rho gD^{2} }}{H} \hfill \\ \frac{1}{H} = \frac{{B_{4} }}{{S^{a} }} + B_{3} S^{3} - B_{2} S^{2} + B_{1} S - B_{0} \hfill \\ S = \frac{d}{D} \hfill \\ \end{gathered}$$
(1)

where

Bi-constants.

H-Shape dependent parameter.

The range of S is shown in Table 1

Table 1 Empirical constants for Eq. (1) (Drelich 2002)

Condensate droplet rise trajectory

The condensate droplet rises vertically through the brine solution in the absence of electric current. Figure 4 traces the droplet rise trajectory path through the brine solution. The velocity of the vertical rise is dependent on the temperature, salinity of the surrounding brine and composition of the condensate droplet. However, in the presence of electric field, the droplet exhibits a preferential movement toward the cathode. At position A, after droplet break-up, the droplet rises vertically because the dominant force acting immediately is buoyancy and pump pressure force. As the travel distance increases, the effect of electric field becomes increasingly dominant and causes a deviation in the otherwise straight path of the droplet. The point of deviation is marked by point D while the distance traveled from point A to D is represented by d. At position C, the rising droplet reaches the surface of brine solution at a horizontal distance c from the vertical point. Higher electric current applied in the system causes an equivalent higher deviation in c (Fig. 5).

Fig. 4
figure 4

Schematics of forces acting on Condensate droplet

Fig. 5
figure 5

Schematics of droplet interface and volume

To define the effect of electric current on the condensate droplet, analyzing the dynamic forces acting on the droplet between both phases becomes necessary. Six main forces were identified to act on the condensate droplet as it rises through the continuous brine solution. These forces have been categorized below:

Upward acting forces

  1. 1.

    Buoyancy force, FB—For a system with constant brine salinity and pump flowrate, the buoyancy of the droplet can be estimated using Eq. (2). The volume of displaced brine is equivalent to the volume of condensate droplet. Assuming a fixed volume of droplet, the buoyancy force would be only a function of the salinity of the brine solution.

    $$F_{B} = V_{d} \rho_{b} g$$
    (2)

    where Vd–droplet volume (m3), ρb–brine density (kg/m3), g–gravity (9.81 m/s2).

  2. 2.

    Pump pressure force, FPPump pressure force is given by the volumetric flowrate of the pump and is a function of time and is given by Eq. (3).

    $$F_{P} = Q_{p} \rho_{c} g$$
    (3)

    where Qp–volumetric flowrate (m3/s), ρc–condensate density (kg/m3).

Downward acting forces

  1. 3.

    Gravity of the droplet, FGThe effect of gravity on the droplet is a function of the mass of condensate trapped within the droplet and is given by Eq. (4).

    $$F_{P} = V_{d} \rho_{c} g$$
    (4)
  2. 4.

    Hydrostatic Pressure Force, FHP—Hydrostatic Pressure force of the brine column above the droplet is a function of droplet rise velocity and the weight of brine column above the droplet. It is a function of time and given by Eq. (5);

    $$F_{{{\text{HP}}}} = V_{t} \rho_{b} g$$
    (5)

    where Vt–Droplet rise velocity.

  3. 5.

    Drag force, FDThe empirical correlation given by (Kelbaliyev and Ceylan 2007) is used to estimate the drag coefficient. This correlation applies for 0.1 ≤ Re < 0.5 and it is presented in Eq. (6).

$$F_{D} = C_{d} A\frac{{\rho V_{t}^{2} }}{2},C_{d} = \frac{8}{{\text{Re}}}\left[ {1 + \frac{1}{{1 - 0.5\left( {1 + 250 {\text{Re}}^{2} } \right)^{ - 2} }}} \right]$$
(6)

Cd–Drag coefficient.

A–surface area of droplet.

Re–Reynolds Number.

Assuming a constant surface area of droplet the Drag force is calculated as a function of droplet rise velocity.

Lateral forces

  1. 1.

    Electric force, FECoulomb’s force of attraction between two charges is used to estimate the force attraction between the droplet and the anode. The magnitude of the force of attraction is shown in Eq. (7);

$$F_{E} = \frac{1}{{4\pi \varepsilon_{o} }}\frac{{Q_{1} Q_{2} }}{{r^{2} }}$$
(7)

where Q1–charge on the anode, Q2–droplet charge, r–distance between droplet and anode, εo–permittivity of the medium.

The resultant force acting on the droplet is calculated from

$$R = \sqrt {\left( {F_{B} + F_{P} - F_{G} - F_{{{\text{HP}}}} - F_{D} } \right)^{2} + \left( {F_{E} - F_{{{\text{DE}}}} } \right)^{2} } ,\theta = \tan^{ - 1} \left( {\frac{{F_{B} + F_{P} - F_{G} - F_{{{\text{HP}}}} - F_{D} }}{{F_{E} - F_{{{\text{DE}}}} }}} \right)$$
(8)

Analytical models are used to obtain FB, FP, FG, FHP, FD and FDE, while R is obtained from experimental data. Force due to electric field FE is then obtained by substitution of Eq. (8).

Assumptions for analytical models.

The following underlying assumptions were made during the development of the analytical models.

  1. (i)

    Brine density is homogenous, and the brine volume is constant within the tank

  2. (ii)

    There is negligible movement of particles within the brine

  3. (iii)

    Droplet volume is constant during droplet rise

  4. (iv)

    The temperature of the brine is constant throughout the experiment

  5. (v)

    The graphite electrodes have constant surface charge

Estimating droplet volume using Young–Laplace model

Volume of droplet was calculated using Young–Laplace solution:

$$\gamma \left( {\frac{1}{{R_{1} }} + \frac{1}{{R_{2} }}} \right) = \Delta P \equiv \Delta P_{0} - \Delta \rho gz$$
(9)

R1 and R2 are the principal radii of curvature, while \(\Delta P\) represents the pressure difference between the fluid within the droplet and the bulk continuous fluid outside the droplet. \(\Delta \rho\) is the difference in densities of condensate fluid and brine solution. For an axisymmetric system, Eq. (9) can be written using cylindrical coordinate’s r, ϕ and z as presented by Karbaschi et al. 2015;

$$\begin{gathered} \frac{{{\text{d}}\varphi }}{{{\text{d}}s}} = 2 - \frac{{\Delta \rho gzR_{0}^{2} }}{\gamma } - \frac{\sin \varphi }{r} \hfill \\ \frac{{{\text{d}}r}}{{{\text{d}}s}} = \cos \varphi \hfill \\ \frac{{{\text{d}}z}}{{{\text{d}}s}} = \sin \varphi \hfill \\ \end{gathered}$$
(10)

The droplet profile of the experimental image is first extracted using canny edge detector (Canny 1986). Then the Laplace-young model is iteratively optimized to fit the extracted profile as described by (Berry et al. 2015). After fitting the droplet profile into the Young–Laplace equation as shown in Fig. 6, the volume and surface area of the droplet is estimated using Eq. (11).

$$\begin{gathered} V_{d} = \pi \smallint r^{2} \sin \varphi {\text{d}}s \hfill \\ A_{d} = 2\pi \smallint r {\text{d}}s \hfill \\ \end{gathered}$$
(11)
Fig. 6
figure 6

Processing experimental image to obtain droplet volume by fitting Young–Laplace equation

Experimental investigation

The experimental set-up shown in Fig. 7 is used to analyze the effect of direct current on droplets of the synthetic condensate rising through brine solution. The brine-condensate system is contained within a rectangular tank of dimensions: 36 × 23 × 26cm. The rectangular tank is made from 5 mm thick clear glass to allow for optical access into the system. The entire experiment was run under ambient temperature conditions. A variable rate syringe pump fitted with a partially filled 100 ml Luer-locked graduated syringe is attached to 80 cm long clear flexible plastic tubing. The tubing is connected to a nozzle attached to the base of the tank. The position of the nozzle-tip is perpendicular to the base of the tank to ensure vertical release of droplets. A constant pump pressure is applied to the syringe pump.

Fig. 7
figure 7

Experimental Set-up

Droplet movement is captured by a high-speed high-resolution camera (DSC-RX10M3) with a total bit rate of 51195kbps and 50 frames per second. The camera is positioned perpendicular to tank so that the entire droplet path can be captured. A focused light source is attached at the opposite end of the tank to illuminate the droplet. A video processing tool (Adobe Photoshop 2020) is used to render the video into images at 40fps. From the processed image, the effect of electric current on the droplet velocity was obtained.

Synthetic condensate and brine preparation

To prepare the synthetic condensate, n-pentane, n-hexane, n-heptane, n-octane, n-decane, and toluene all of 99% purity were obtained from VWR Chemicals UK. Using n-pentane as the base fluid, other components were added under standard conditions of temperature and pressure according to the composition given in Table 2. To achieve homogenity, the resulting synthetic condensate was stirred continuously for 4 h using a table-mounted electric stirrer.

Table 2 Brine and Condenstate composition

The brine composition was modeled after Kester et al., (1967). To prepare the brine solution, each salt component was first measured-out according to the composition given in Table 2. An empty beaker filled with 1400 mL of deionized water (density 0.9982 g/cm3 @ 20 oC) was placed on a table-mounted magnetic stirrer. The measured-out salts were then added in the order shown in Table 2. To ensure homogeneity in the brine solution, each salt was added while stirring continuously for 10 min before the next was added. The mixing process is carried out with Steinberg Electric Stirrer with maximum rotation speed of 3400 rpm. The surface of the brine exposed to ambient temperature (~ 21OC ± 0.5) and atmospheric pressure (14.696 psi). The total volume of brine solution recorded was 1530 mL, while the density of the brine was measured to be 1.0658 g/cm3 and the Molarity was calculated to be 0.052 M. The actual experiment set-up is shown in Fig. 8. To prevent redox reactions at the electrodes during experiment, the graphite electrodes (with 99% percent purity) were used for both the cathode and anode. The graphite electrodes were connected to the power supply unit Powerflex CPX400A Dual 60 V 20A.

Fig. 8
figure 8

Final experimental set-up

Results

PDT uses the shape of the curved interface to extract the interfacial tension of the droplet and does not require advanced instrumentation. The precision of the analysis is improved with the use of image analysis software to match the shape of the curve to Young–Laplace equation. The effect of electric field on the movement of the condensate droplet along the rise path is captured using the force analysis equation given in Eq. (8). The effect of electric field on the interfacial tension between the condensate droplet and the brine solution is captured using pendant drop tensiometry. As shown in Table 8 (see Appendix), the salinity and electric current were varied from 0–19.23ppt and 0–46.5 V, respectively. The measurements for each parameter were obtained at least 12 times to satisfy statistical significance. Properties of the droplet and brine solution extracted from the experiment are presented in Table 3.

Table 3 Droplet data extracted from experiment

Based on the conditions of this experiment, a significant deviation of droplet trajectory is expected under the following conditions:

  1. (i)

    Changes in the permittivity of the brine due to alterations in the salinity of the brine. Brine salinity would be altered if new ions are introduced at the electrodes during REDOX reactions. The probability of REDOX reaction occurring at the electrodes was minimized with the use graphite electrodes

  2. (ii)

    Increase in polar components (acids and bases which are surface active) of the condensate droplets. This would occur if the composition of the condensate changes with time. An increase in polar component would increase the charge density around the droplet surface.

  3. (iii)

    Temperature change caused by increase in electric voltage. Electrolysis is initiated when the voltage increases beyond a threshold value. Heat given off at the electrodes during electrolysis may cause a temperature rise within the brine. The resulting temperature rise affects the buoyancy force acting on the droplet and causes a deviation. The maximum voltage applied across the electrodes was limited to 46.5 V to checkmate this occurrence

By minimizing or eliminated other potential sources of trajectory deviation, the experiment was designed to capture only deviations caused by varying electric voltage.

The droplet trajectory was extracted using the guidelines highlighted in Sect. 2.1. Deviations in the droplet trajectory as a function of electric voltage across the electrodes were recorded using the high-speed camera. For each droplet trajectory shown in Fig. 9, the droplet rise velocity, horizontal deviation, nominal distance (a and b) was measured, and the results presented in Tables 4, 5, 6, 7. Each droplet trajectory was measured 3 times. Details of the results obtained are captured in Appendix section.

Fig. 9
figure 9

Extracted images of actual droplet paths (a) No Voltage (b) 5.25 V (c) 26.5 V (d) 46.5 V

Table 4 Case a: Deionized water with no salt content and no DC current
Table 5 Case b: Salinity Constant, Low Voltage (5.26 V)
Table 6 Case c: Salinity Constant, Low Voltage (26.24 V)
Table 7 Case d: Salinity Constant, Low Voltage (46.57 V)

During the experiment run-time, an average of 4 droplet rise is recorded; this brings total measurement for the behavior droplet at various voltages to 12. A plot of the droplet trajectory properties is presented in Fig. 10. The droplet rising velocity was estimated by measuring the droplet travel distance against the time it takes for the droplet to rise from position A to position D. Results from the analysis shows that as the voltage increase, the droplet rise velocity decreases from the initial 140 mm/s to a near constant value of 120 mm/s at 26.5 V. The change in trajectory of the droplet increases the travel time as voltage applied increases. True vertical distance to deviation indicates the kick-off point for the change in droplet trajectory. An increase in voltage causes a corresponding decrease in the true vertical distance to deviation to reflect the increasing radius of impact.

Fig. 10
figure 10

Effect of voltage on droplet trajectory

The horizontal deviation C is the strongest measure of the effect of the electric field on the droplet path as it alters the otherwise vertical motion of the droplet due to buoyancy effect. From the result obtained, a temporary decrease was observed. This could be attributed to the random motion of brine immediately after mixing. Thereafter, a progressive increase in deviation is observed as the voltage is increased. Typically, during oil production, brine (low salinity) is used to drive the oil from the reservoirs into the production well. The ability to do this effectively depends on the interfacial tension acting between the brine and the oil molecules. A lower interfacial tension increases the oil displacement efficiency of the brine (Nicolini et al. 2017; Wagner and Leach 1966). Results from the interfacial tension (IFT) measurement obtained from the experiment reveal a progressive increase in IFT as the voltage is increased (see Fig. 11). This can be attributed to the distribution of electric charge across the droplet interface in the presence of the electric field. When the electric voltage is increased up to 26 V, a significant increase in interfacial tension is observed. This increase is captured by a change in trendline.

Fig. 11
figure 11

A graphical plot of the effect of Electric voltage on Interfacial tension

Experimental Error Reporting

Two types of error are captured in this analysis: reading error and standard deviation error. The reading error accounts for the uncertainty in measurement observed from the high-speed camera. Three parameters were measured directly; true vertical distance to deviation (d), horizontal deviation (c), and droplet rise time. The droplet diameter, horizontal and vertical deviations were all subjected to a reading error of ± 0.05 mm, while the droplet rise time (t) was subjected to a reading error of ± 0.005 s. To account for the disparity in measured values, the standard deviation of each reading was estimated from the mean value. The standard deviation gives the error spread in the mean value of the readings obtained from the experiment. Using data given in Table 4, 5, 6, 7, the mean, standard deviation, and coefficient of variance were computed from Eqs. (12)–(14).

$${\text{Mean}}, \mu = \frac{{\sum \left( {x_{i} + x_{i + 1} + \ldots x_{N} } \right)}}{N}$$
(12)
$${\text{Standard}} \;{\text{Deviation}}, \sigma = \sqrt {\left[ {\frac{{\sum \left( {x_{i} - \mu } \right)^{2} }}{N}} \right]}$$
(13)
$${\text{Coefficient}}\;{\text{of}}\;{\text{ Variance}} = \frac{\sigma }{ \mu }$$
(14)

where N–Number of input data, xi–measured data.

Error propagation

The droplet rise velocity was analytically obtained from these parameters using Eq. (15). We observed that the reading error was relatively small compared to the standard deviations. For the error propagation, we made use of standard deviation.

$${\text{Droplet Rise Velocity }}\left( {{\text{mm}}/{\text{s}}} \right) = \frac{{d + \sqrt {\left( {a^{2} + c^{2} } \right)} }}{t}$$
(15)
$${\text{Error}}\;{\text{Propagation}} = \sqrt {\left( {\sigma_{d}^{2} + \sigma_{a}^{2} + \sigma_{c}^{2} + \sigma_{t}^{2} } \right)}$$
(16)

where a, d, c and t are droplet trajectory parameters as shown in Fig. 4 and given in Tables 4, 5, 6, 7

σd–standard deviation for true vertical distance to deviation.

The results of the analysis for each voltage reading are presented in Figs. 12, 13, 14.

Fig. 12
figure 12

Error analysis for 5.26 V

Fig. 13
figure 13

Error analysis for 26.24 V readings

Fig. 14
figure 14

Error analysis for 46.57 V readings

From the error analysis, it was observed that the coefficient of variation for all considered parameters did not exceed 10%. This connotes that repeated measurements produced similar results with a 90% confidence interval. A progressive increase in error propagation of the droplet rise velocity was observed as the voltage is increased. This is expected because of the increase in lateral movement of the droplet observed when the volage is increase.

Conclusion

In this work, laboratory experiments to capture the effect of direct current on condensate droplets were performed. This provides insights into the behavior of condensate droplets in the pore space when DC current is introduced. Results obtained from previous laboratory experiments reveal that an increase in the current introduced into the hydrocarbon saturated cores, leads to a corresponding increase in condensate displacement efficiency until a certain threshold of current is reached (Wentong Zhang et al. 2019a, b). The explanation for this was tied to the interaction between the direct current and rock surface via electromigration and electrophoresis (Ghosh et al. 2012; Paillat et al. 2000; Rahbar et al. 2018). The release of hydrogen ions and hydroxide ions during electrolysis at high voltage is thought to weaken the acidic environment of the pore space by combining to form water. However, insights from this experiment reveal that in the absence of rock surface, an increase in voltage leads to a preferential movement of the condensate droplet toward the anode and a corresponding increase in interfacial tension between the condensate droplet and brine solution. This shows that as DC current is increased, the interfacial tension increases progressively until its effect counteracts the benefit obtained from the preferential movement of condensate droplet. Temperature variation was not considered in this study because at reservoir conditions the temperature is fairly constant. However, for future investigations, the experiments should be conducted at elevated temperatures to capture the reservoir temperature conditions.