Introduction

When searching for efficient techniques increasing the energy potential related to the conversion of pure energy originating from the Sun (Kabir et al. 2018)—a spectral type G star, attempts are made to utilise it both by means of direct—helioelectric, as well as indirect methods, related to heat transfer (Orzechowski and Stokowiec 2016), meaning heliothermal. Thus, the commissioning of installations with photovoltaic cells with increasingly larger areas and higher powers seems to be a reasonable trend (Renewable Energy Institute 2020). Such an action also follows one of the main objectives of the amended EU directive related to the energy characteristics of buildings (Directive (EU) 2018), meaning the reduction of the emission of greenhouse gases until 2050 by 80-95% compared to 1990. In the long term, it will enable conversion of existing buildings into buildings with an almost zero energy consumption—for which the ratio of demand for non-renewable primary energy PE is close to 0 kWh/(m2 year). A solution to this involves an increase in the scale of complex and deep thermal upgrading, as well as the construction of new facilities with a low emission of CO2 and particulate matter (PM).

The term—deep thermal upgrading is to be understood as reaching such an energy standard of a building after thermal upgrading, which would fulfil requirements related to energy efficiency (Rasmussen 2017) like those for new buildings, and, e.g. this standard for residential single-family and multi-family buildings expressed by the ratio of demand for non-renewable primary energy for the needs of heating, ventilation and the preparation of warm utility water amounts to PEmax, H+w = 70 and 65 kWh/(m2 year), respectively; educational buildings: PEmax, H+w = 190 kWh/(m2 year) (status for Poland—the geometric centre of Europe—as of 1 January 2021). The remaining member states with a longer membership in the European Union are under an obligation to make the energy standards of buildings erected starting from 2021 similar to those of zero-energy buildings.

Poland should have implemented the provisions of Directive (Directive (EU) 2018) by 10 March 2020. Meanwhile, only 1% of single-family buildings in Poland are energy efficient, meaning that the ratio of demand for non-renewable primary energy PEmax = 95 kWh/m2 year (starting from 2021, PEmax = 70 kWh/m2 year), and almost 70% are heated using black coal and require modernisation.

European law (Renewable Energy Institute 2020; Directive (EU) 2018; Directive 2006, 2009) encourages the use of renewable energy sources. However, sure solutions seem to be unprofitable. Efficiency of some renewable energy sources usage, e.g. PV systems strongly depends on i.e. climate conditions but, on a way of electrical network connection (on-grid, off-grid, tracking) and on economic situation of specific country. Due to this, there is an observed increase in the number of submitted applications for the funding of actions related to thermal upgrading, the assembly of RES installations and the auditing of energy and energy efficiency.

Belgium is among the countries that saw a considerable increase in powers resulting from the installed PV cells (Huijben et al. 2016) during the last 5 years.

A review of government measures which influenced both the exponential increase in new PV systems, as well as their stagnation between 2006 and 2013, is discussed in (Directive 2009).

The report (Renewable Energy Institute 2020) also indicates that the combined power installed in photovoltaic sources in Poland amounted to approx. 1500 MW as by the end of 2019 (three times more than in 2018), while in May of 2020 it exceeded 1950 MW (an increase by almost 30% was recorded compared to 2019). In 2019, Poland was rated fifth among EU countries, due to a yearly power increase of 0.9 GW (i.e. almost 40% of annual growth). It is predicted that in mid-2020 Poland will be rated 4th among EU countries in terms of new installed power. (Renewable Energy Institute 2020) predicts that even 1 GW of new PV installations will be added in the whole year of 2020, and the total power of photovoltaic installations in Poland at the end of 2020 will amount to 2.5 GW.

Among European countries, the highest increase in new PV power in 2018 was recorded in Germany (over 3 GW), the Netherlands (1.5 GW), France (1.3 GW) and Hungary (over 0.5 GW); these are followed by Italy, Spain, Greece and Czechia (Jäger-Waldau et al. 2019). Although RES directive (Directive 2009) was introduced already in 2009, small incremental PV increases were present during first 6 years and only in 2018 significant increase in dynamic installation and power originating from PV in Europe was observed (more than 50% increase from 2017 (Jäger-Waldau et al. 2019)).

An analysis of the operation of over 31,000 PV systems installed in Europe between 2006 and 2014 indicates that it is difficult to determine their capacity unambiguously (Leloux et al. 2015) due to the significant difference in the efficiency of the inverters and modules, as well as the technology of their production. There are estimates of an even 30% difference in the efficiency of any system, resulting from the quality of production of the modules themselves.

In order to assess the capacity of a PV system, the so-called PR ratio is determined, which measures the difference between the real and theoretical production of energy by a photovoltaic system, expressed as percentage of energy generated by a system relative to potential energy calculated by measuring the intensity of solar irradiation and temperature (Gaglia et al. 2017). Over seven years, the recorded improvement in the annual increase in the PR ratio amounted to approximately 0.5%. The desired unit performance ratio PR for new installations is 0.84. When reached, such a value would influence an improvement in the capacity of PV systems by approximately 10% and the same level of reduction in the cost of consumption of electricity (Leloux et al. 2015).

For a quick assessment of the ability to use the energy of solar irradiation for a given region in the world, country or town, it is possible to implement physical and mathematical models used to perform simulations of the efficiency of solar cells into the computer environment. In here, attention should be paid to the fact that solar irradiation which reaches the surface of an absorber located on the ground is weakened by Earth’s atmosphere and other phenomena, such as scattering, reflection or attenuation (typical anisotropic solar radiation model is widely discussed and accessed in literature (Seidel et al. 2010)).

Relatively fast, simple and most popular radiative transfer models (RTMs), taking into account, e.g. atmospheric transmission vs wavelength, Rayleigh scattering, aerosol scattering, water vapour absorption, ozone absorption, unmixed gas absorption, turbidity, precipitable water vapour, Earth–Sun factor, include: the Simple Model of the Atmospheric Radiative Transfer of Sunshine (SMART) with an uncertainty range of up to 5÷10% (Seidel et al. 2010) and the Model of American Society for Testing and Materials (ASTM). Moreover, the following models are also known: Second Simulation of a Satellite Signal in the Solar Spectrum (6S) (Vermote et al. 1997), SCIATRAN (Rozanov et al. 2005), SHARM (Muldashev et al. 1999), RT3 (Evans and Stephens 1991), RTMOM (Govaerts 2006), RAY (Zege and Chaikovskaya 1996), STAR (Ruggaber et al. 1994), Pstar2 (Ota et al. 2010), DISORT (Stamnes et al. 1988), along with computer programs use them -: MODTRAN (Berk et al. 1987), STREAMER (Key and Schweiger 1998) and SBDART (Ricchiazzi et al. 1998), PV Lighthouse, SMART (Mehta 2014), SOLAR GIS, Solar CalQ 1.0 and others.

Currently, one of the basic requirements faced by buildings undergoing modernisation involves limitation in the emission of carbon dioxide even by over 90% compared to original values. In order to fulfil these criteria, it is necessary to use alternative solutions based on renewable energy sources. In here, photovoltaics constitutes a reasonable option and provides the possibility to achieve a high level of reduction in the emission of primary contaminants, such as CO2, SOx, NOx or solid particles.

To achieve European climate goals and in order to motivate to increase the share of RES (in this case energy from PV) in the total energy balance in countries with low energy prices it is proposed in (Radl et al. 2020) to design and set grid charges in accordance with the ‘polluter pays’ principle. Moreover, financial support as well as the obligation of photovoltaic installations would seem to be the most reasonable solution.

In (Radl et al. 2020) it is also discussed the impact of grid fees, irradiance and local consumption on the profitability of PV electricity on the basis of eight European Countries with different specific conditions. As it turns out, in countries with high number of sun hours (e.g. Spain, Portugal, Italy), high-power PV systems are profitable without any subsidies or government programs. It is also worth emphasizing that among the analysed countries, the investments into Battery Energy Storage Systems - BESS are only beneficial in Spain and Portugal. On the way, on the basis of (Jäger-Waldau 2019), it is stated that tracking off-grid and consumer product markets is extremely complicated.

In some cases, an analysis of the profitability of PV systems utilisation indicates the lack of feasibility. These may include, i.e.: resource potential (location and landform), technical potential (i.e. way of electrical grid connection) and economic potential (actual economical politics, technology costs and so on). As it turns out, there is no universal indicator for assessing the economic situation of a given country in the context of obtaining solar energy from photovoltaic cells (Bódis et al. 2019). In this case, the most common expression is Levelized Cost of Electricity (or Energy), LCOE (Vartiainen et al. 2015). This indicator can be calculated using the Eq. (1) and it is the quotient of the net present value of all costs incurred in the total lifetime of a given installation to the total amount of electricity generated by it. This seems to be the way to discuss the installed capacity and economic potential of PV cells (but also other renewable energy sources) in different European countries.

$$ \mathrm{LCOE}=\frac{\mathrm{all}\ \mathrm{costs}\ \mathrm{in}\mathrm{curred}\ \mathrm{in}\ \mathrm{the}\ \mathrm{total}\ \mathrm{lifetime}\ \mathrm{of}\ \mathrm{a}\ \mathrm{given}\ \mathrm{in}\mathrm{stallation}}{\mathrm{t}\mathrm{he}\ \mathrm{total}\ \mathrm{amount}\ \mathrm{of}\ \mathrm{electricity}\ \mathrm{generated}} = \frac{\sum_{\mathrm{t}=1}^{\mathrm{n}}\frac{{\mathrm{I}}_{\mathrm{t}}+{\mathrm{M}}_{\mathrm{t}}+{\mathrm{F}}_{\mathrm{t}}}{{\left(1+\mathrm{R}\right)}^{\mathrm{t}}}}{\sum_{\mathrm{t}=1}^{\mathrm{n}}\frac{{\mathrm{E}}_{\mathrm{t}}}{{\left(1+\mathrm{R}\right)}^{\mathrm{t}}}} $$
(1)

where: It—investment expenditures in the year t, Mtoperations and maintenance expenditures in the year t, Ft—fuel expenditures in the year t, which is zero for PV electricity, Et—electrical energy generated in the year t, R—discount rate, n—expected lifetime of system or power station.

Due to technological progress, research activities and European market development, a drastic decrease in the prices of assembly, cells and PV installations has been observed. However, the profitability of an investment is usually determined at the design stage. Assuming in this case no fuel costs (Ft = 0), the Weighted Average Cost of Capital, WACC (see Eq. 2) adversely affects the LCOE value.

$$ \mathrm{WACC}=\frac{\mathrm{E}}{\mathrm{E}+\mathrm{D}}\cdotp {\mathrm{R}}_{\mathrm{e}}+\frac{\mathrm{D}}{\mathrm{E}+\mathrm{D}}\cdotp {\mathrm{R}}_{\mathrm{d}}\ \left(1-{\mathrm{T}}_{\mathrm{c}}\right), $$
(2)

where E—market value of the company’s equity, D—market value of the company’s debt, Re—equity cost, Rd—debt cost, Tc—corporate tax rate, E/(E+D)—equity (percentage of financing), D/(E+D)—debt (percentage of financing).

The combination of high debt and low cost of debt in some countries outside the EU allowed the signing of beneficial PPAs (Power Purchase Agreements) (Jäger-Waldau 2019).

When analysing the impact of financing on LOCE, it was found that with WACC = 12%, the financing costs would have amount to 50% of the total LOCE value. Hence, the cost of producing PV energy is increasingly dependent on an environment with low financial risk and costs, rather than on high levels of solar irradiation (Jäger-Waldau 2019).

Most of the considerations related to LCOE determination assume a certain level of the capital cost of financing the investment (Lazard 2016). In fact, the cost of capital is a variable value that depends on several market factors. Changing certain factors of the capital cost can lead to major changes in the LCOE of a given energy project (Dzieża 2017).

In (Bódis et al. 2019), a method of assessing the technical potential of electricity production from PV cells mounted on the roofs in the EU countries was developed. For this purpose, up-to-date spatial information (with a resolution of 100 m) on the building stock in the EU and the Photovoltaic Geographical Information System (PVGIS) methodology were used. It turned out that roofs across the EU could cover around 24% of the annual electricity demand (i.e. 680 TWh). The inference was made on the basis of the average cost of electricity (LCOE) and country-specific parameters (taking into account, e.g. energy prices). An interesting point of the paper is the presentation of the influence of the WACC value on spatial distribution of the LCOE for rooftop solar PV installations. It follows that the most favourable LOCE values ​​are assigned to countries with the highest solar energy potential (e.g. Cyprus EUR 6.19 EURcent/kWh, Malta 7 EURcent/kWh), and the lowest correspond to less sunny locations (e.g. northern Finland areas). As the Weighted Average Cost of Capital turns out, WACC does not always correlate with LOCE values. The countries with good insolation conditions, but high capital costs (e.g. Bulgaria, Croatia) have a lower technical and economic solar electricity potential than countries with lower production costs, such as Germany, Belgium. It was also noted that at present it is not possible to achieve grid parity for the countries of Eastern Europe, which include, e.g. Poland, Romania, Hungary, Czech Republic, Slovakia, Croatia, Lithuania, Latvia, Estonia.

However, the LOCE parameter exposes some limitations (Radl et al. 2020); including profile cost (flexibility and utilization effects), balancing costs and grid costs; and should be contained in all LCOE costs of the electricity generation technology. Moreover, (Dzieża 2017) describes in great details other critical measures of LCOE as an indicator of making investment decisions in the energy sector. These include:

  • failure to take into account the flexibility of energy projects and project risks,

  • no distinction between marginal costs and capital expenditure.

In (Campisi et al. 2018) an interesting and more and more popular model of Multi Criteria Decision Making, MCDM, was presented. Due to the fact that MSDM takes into account the complexity of socio-economic and biophysical systems, it was used in a multi-criteria analysis of activities in the field of energy efficiency and reduction of fossil fuel consumption when implementing integrated renewable energy sources during the modernization of a single-family residential buildings.

The case study presented in (Campisi et al. 2018) concerns the evaluation of the alternatives for heating systems in a residential building localized in Italy. MCDM analysis (with fourteen assessment criteria) considers the following alternatives: 1) Liquid Petroleum Gas, LPG heating, 2) oil boiler heating, 3) heating with pellets, 4) heating with the heat pump, HP 5) heating with the HP cooperates with typical the solar thermal energy system, or 6) with photovoltaic system. The most significant criteria turned out to be investment costs (importance factor is '5'), then support for domestic hot water production (importance factor is '4'), operating costs and cleaning (importance factor is '3'). The 'working life' criterion, for which the importance factor was '0', turned out to be insignificant. In the end, the most economical installation turned out to be the HP with the solar thermal energy system (total MCDM index was 24.57), followed by the HP without any supporting (22.03) and then the HP with photovoltaic cells (20.09). If the investor decides on the most advantageous alternative from szyk- from the point of view of the MCDM alalysis of the MCDM analysis view, the reduction of CO2 emission to the Earth's atmosphere will be approx. 73%, and the payback time for investment expenditure will be approx. 4 years.

In addition to the LOCE typical for the energy sector, the Net Present Value NPV, the internal rate of return IRR and the Simple Pay-Back Time SPBT may be other relatively simple and willingly chosen statistical methods of making investment decisions.

The profitability of an on-grid PV installation for three buildings located in southern Finland has been discussed in (Simola et al. 2018). The energy demand for analysed cases, i.e. a grocery store, a dairy farm and a family house, is 89 kWp, 28 kWp and 5.2 kWp, respectively. The NPV and IRR indicators are used to assess the profitability of the investment. On their basis, it is found that:

  • PV installation for a single-family house is not profitable; the solution could be an annual increase in electricity of 0.6% and higher tax credits for this purpose;

  • PV installation for a store can be profitable with the annual decrease in energy prices by 3.6% and with subsidies at the level of 25%;

  • PV installation for a dairy farm can be profitable with a 3.3% annual decrease in energy prices while maintaining subsidies.

The price of PV installations for less than 10 kWp and the low price of electricity in Finland make small installations unprofitable. In addition, the high variability of insolation conditions in Finland is a significant problem, as the greatest demand occurs in winter, when the number of hours of sunshine and the intensity of solar radiation are lowest.

Generally, PV installations with a higher self-consumption of electricity, such as a shop or a dairy, are considered profitable; they also receive higher subsidies from government programs for PV installations than those with a capacity below 10 kWp.

The installed capacity of grid-connected PV solar cells in Finland is steadily increasing, but still appears to be low compared to the potential of residential rooftops. Moreover, the low profitability of PV systems in Finland is largely due to sociotechnical, management, economic and policy barriers (Sami and Ahvenniemi 2019).

This work is mainly to show how diverse the level of insolation in European countries is and how it affects the possibilities of effective use of renewable energy from the sun (see the “Solar irradiation density in Europe” and “Global power density and photon current simulation for into module solar irradiation” sections) on the specific case. Nevertheless, the other technical and economic factors were also mentioned for future detailed analysis (see section 2.3).

This paper discusses an example of an already completed investment of the thermomodernization of an educational building, located in the geometric centre of Europe, near Bialystok, Poland, where the intensity of solar irradiation is not high compared to other European countries (Šúri et al. 2007; No Author 2020a). The mean values of the total intensity of the solar radiation on the horizontal surface (ITH) obtained for this region were compared to the maximum and minimum ITH values for Malta and Finland and presented in the “Methods” section. The next part of this paper discusses detailed data of the energy audit of the building. The building was subjected to extensive thermomodernization improvements such as the installation of photovoltaic cells cooperating with a heat pump as an alternative energy source (basic parameters of the building and thermal up-grading range—see the “A boiler room supported by PV system—case study” section). The optimization of the PV installation size was carried out based on the following:

  • reduction of CO2 emissions to 90% compared to the state before the modernization

  • off-grid system operation.

Environmental analysis and results of the calculations of CO2 emissions for the current status and with alternative energy sources are delivered in the “Environmental analysis of the assumed thermal up-grading option” section.

The next subsection deals with economic evaluation and delivers simple and discounted economic efficiency indicators calculated for a sample investment, such as SPBT, NPV and IRR (see the “Economic evaluation” section). The last “Detailed conclusions” section compares, discusses and concludes obtained values. Moreover, future research direction and limitations of the case study were also considered.

Methods

Solar irradiation density in Europe

It turns out that, according to the calculations of Szymon Antonii Sobiekrajski of 1775, the geometric centre of Europe is located in north-eastern Poland, in Suchowola near Biaystok. According to statistical data originating from a weather station in this area, developed based on full 30-year measurement cycles used for energy balances of buildings, the sum of total intensity of solar irradiation incident on a horizontal plane amounts to ITHav,year = 897.14 kWh/m2 (the monthly average is ITHav,month= 74.76 kWh/m2) (No Author 2020a), while this value for Poland and Europe is estimated (based on interpolation and modelling of 580 meteorological measurements constituting a database for a period of 1981-1990) at 1012 kWh/m2 (ITHav,month = 84.33 kWh/m2) and 1205 kWh/m2 (ITHav,month = 100.42 kWh/m2), respectively (Hernandez-Moro and Martinez-Duart 2013; No Author 2020b). The highest and lowest values of total intensity ITHav,year are recorded in Malta and Finland and they amount to 1766 kWh/m2 and 841 kWh/m2, respectively. The distribution of direct average annual solar irradiation in Poland and European countries is mapped and updated in the Solar GIS base in an ongoing manner (The World Bank 2019). The Solar GIS database has been validated at 200+ locations globally. A long historical archive of solar irradiation data is available for any location between latitudes of 60N and 45S.

Figure 1 presents a general map of the distribution of total annual average solar irradiation for Poland and for European countries.

Fig. 1
figure 1

Map of total solar irradiation in (a) Poland (The World Bank 2019) and in (b) Europe with additional data of photovoltaic solar electricity potential (Jäger-Waldau et al. 2019; No Author 2020c)

Figure 2 presents the monthly distribution of total solar irradiation intensity for the geometric centre of Europe—a spot near Bialystok, which indicates that the monthly average solar irradiation intensity for the geometric centre of Europe is lower by approx. 26 kWh/m2 (26%) than the European average (100 kWh/m2). It results in muchreduction in photovoltaic solar electricity potential for the purpose of its conversion and utilization, shown in Fig. 1b. The yearly sum of solar electricity generated by optimally-inclined 1kWpeak system with a performance ratio of 0.75 for Poland, Malta and Finland are 675, 1,325 and 631 kWh/kWpeak respectively.

Fig. 2
figure 2

A climograph for selected European countries

Additionally, Fig. 2 shows also a climograph representing European countries with extreme values of the dry-bulb temperature, MDBT (Mean Dry Bulb Temperature), which is compared to the ITH value for the geometric centre of Europe.

Figure 3 in turns presents average ITH values recorded by the Photovoltaic Geographical Information System (PVGIS) for European Communities between 2001–2019, which indicate that Poland is rated twentieth in terms of the conditions of insolation, and the ITH in here is lower by 16% and 43% than the European average and the maximum average for Malta, respectively, and higher by 17% than the minimum average recorded for Finland.

Fig. 3
figure 3

Total average intensity of solar irradiation on the horizontal plane for European countries (Global yearly irradiation); 1-AT- Austria, 2-BE- Belgium, 3-BG- Bulgaria, 4-CY- Cyprus, 5-CZ- Czech Republic, 6-DE- Germany, 7-DK- Denmark, 8-EE- Estonia, 9-ES- Spain, 10-FI- Finland, 11-FR- France, 12-GR- Greece, 13-HR- Croatia, 14-HU- Hungary, 15-IE- Ireland, 16-IT- Italy, 17-LT- Lithuania, 18-LU- Luxembourg, 19-LV- Latvia, 20- MK- Republic of North Macedonia, 21-MT- Malta, 22-NL- Netherlands, 23-PL- Poland, 24-PT- Portugal, 25-RO- Romania, 26-SE- Sweden, 27-SI- Slovenia, 28-SK- Slovakia, 29-TR- Turkey, 30- UK- United Kingdom

For the highest possible utilisation of the energy potential of PV panels, it is suggested to optimise their tilt angle, or additionally to commission a tracking system (Ngo et al. 2020; Whang et al. 2019); the 18-year average optimal angle of the position of photovoltaic panels for Poland amounts to approx. 36o, with 32o for Malta and even 45o for Finland (see Fig. 4).

Fig. 4
figure 4

The optimal tilt angle of photovoltaic panels (an average of 18 years) aimed at the utilisation of their maximum capacity

Global power density and photon current simulation for into module solar irradiation

Making appropriate simulations are necessary to highlight the large differences in solar conditions in European countries with respect to each season. It is directly related to potential use of renewable solar energy resources (especially in the heating season).

The assessment of average solar conditions existing in Europe was performed using version 1.1.1 of the PV Lighthouse calculator (No Author 2020d).

Simulations were performed for the central part of Europe—an area near Bialystok (Poland), the capitals of Malta–Valletta and Finland–Helsinki, for which the respective values of total average intensity of solar irradiation on the horizontal plane were the highest and the lowest. Special attention should be paid to Finland, for which, due to locational aspects, the conditions of insolation were also estimated in the city of Rovaniemi, situated in the Arctic Circle. The input data and sample results of the performed simulations of global vs wavelength incident on the module are listed in Table 1 and in Figs. 5 and 6. The tilt angle varying among countries results from the optimisation of the positioning of solar panels aimed at the utilisation of their maximum capacity (see Fig. 4).

Table 1 General and atmospheric input and output data for simulations using the PV Lighthouse calculator
Fig. 5
figure 5

Global power density in the central point of Europe (Poland) in comparison to Maltese and Finnish results for into module solar irradiation (integrated over a wavelength range of 280–4000 nm)

Fig. 6
figure 6

Global photon current in the central point of Europe in comparison to Maltese results for into module solar irradiation (integrated over a wavelength range of 280–4000 nm)

Figures 5 and 6 present global power density and photon current in the central point of Europe in comparison to the results from Malta (Valletta) and Finland (Helsinki) for into module solar irradiation; the values are related to simulations of insolation as of 1 Jan and 15 Jul 2019.

As can be seen from Figs. 5 and 6, the middle of summer, which is considered to occur on the 15th of July, does not exhibit high variances in insolation in each one of the analysed cases. The difference between the values of power density and photon current for Poland, Malta and Finland does not exceed 3.5% for solar rays with an average optimal angle for a given country, amounting to 36, 32 and 45o, respectively.

However, considering the data on insolation for January, in which the average respective numbers of sunshine hours recorded for Poland and Malta amount to 31 (No Author 2020e) and 169 (No Author 2020f) (meaning 5.5 times more solar energy in Malta in January and 33% more annually; see Fig. 7), the modelled values of power density and photon current exhibit considerable variability. Therefore, between the central point of Europe—Bialystok (Poland), the capitals of Malta—Valletta and Finland—Helsinki, the respective differences in power density amount to 54 and 33% (see Fig. 5); the photon current differences amount to 46 and 27% (see Fig. 6).

Fig. 7
figure 7

The average number of sun hours for Poland, Malta and Finland

However, when the above values are related to the city of Rovaniemi (Finland), located in the Arctic Circle, the respective estimated differences in power density and the energy of photons will each time amount to approx. ~98 and 97% respectively.

The PV Lighthouse environment also enables determining an average number of sunlight hours in a day or year for any location. Figure 9 clearly shows the high diversity in the number of sunlight hours in the analysed countries of Europe.

Results

Above delivered analyses of the irradiation conditions in European countries of the medium, highest and lowest potential seems to be important from the design process of thermal up-grading.

A boiler room supported by PV system—case study

This chapter focuses on optimizing the size of PV installation for the sample educational building (area of Af = 1,324.29 m2) located in Bialystok, near the geometrical center of Europe. The building was comprehensively thermally upgraded. It resulted in heat demand decrease from 300 to 210 kW (see Table 2). Therefore, the scope of thermomodernization work was extensive. This study focused on one of the proposed improvements: the replacement of the gas heat source with an electric heat pump equipped with vertical heat exchangers and supported by a PV system. The technical aspect of selecting this type of applied heat source is not the subject of the analysis presented in this study. Moreover, the investor-imposed guidelines, mainly relating to project financing, are operating a PV system in an off-grid system and reducing CO2 emissions to 90% of that before the modernization. Results of the calculations of CO2 emissions for the current status and with alternative energy sources are outlined and simple and discounted economic efficiency indicators calculated for a sample investment (such as the Simple Pay-Back Time SPBT, the net present value NPV and the internal rate of return IRR) are discussed.

Table 2 A list of input data for determining the size of a PV installation

Environmental analysis of the assumed thermal up-grading option

Table 2 presents basic and necessary input data for environmental analysis. Before thermal up-grading, in the current ‘0’ status, the building is heated by means of a boiler fired with type E methane-rich natural gas; an electric brine-water heat pump (with vertical geothermal heat exchanger) supported by an off-grid PV system (battery capacity: 378 720 Wh) has been proposed for use after thermal upgrading. Upon thermal upgrading, also encompassing the enhancement of heat insulation, the design heat load and usable energy decreased by 30%; these figures are provided as supplementary data to show the general scale of modernisation works and are not significant from the point of view of the calculations below. Estimated length of the heating period for the region of Bialystok is 200 days so the PV system is designed for this period of time.

In Table 2, ‘Annual consumption of electricity by the boiler assembly, PAK, kWh/annum’ is so-called auxiliary energy used only for equipment such as circulation pumps and control units; ‘yearly fuel consumption’ refers to the fuel that the heating source uses; in ‘0’ option it is natural gas, type E and in ‘1’ option it is electric power.

Calculations of the annual amounts of carbon dioxide emitted into the atmosphere and its ecological effect are based on emission indicators listed in Table 3 (Institute of Environmental Protection - National Research Institute 2020).

Table 3 Calorific values (WO) and CO2 emission indicators (WE) in 2017 for reporting under the emissions trading system for 2020

The total system efficiency is equal to ηtot = 3.6 and derives from the following ratio: ηtot = ηg · ηe ·ηd ·ηs; The individual components given here relate to the efficiency of: heat source (here a heat pump with ηg = COP = 3.8), regulation and use of heat in the heated space (ηe = 0.97), transmission (ηd = 0.98) and heat accumulation (ηs = 1). Coefficient of Performance COP for a heat pump adopted above is typical for the production technology and market for these devices, not only in Poland (Campisi et al. 2018). The method of determining the total efficiency of the system, ηtot is also common (Campisi et al. 2018).

Estimated yearly fuel consumption value, \( {\mathrm{P}}_{\mathrm{e}{\mathrm{l}}_{\mathrm{P}\mathrm{C}}} \)given in the Table 2 is calculated basis on the following dependence:

$$ {\mathrm{P}}_{\mathrm{e}{\mathrm{l}}_{\mathrm{P}\mathrm{C}}}=\mathrm{FE}\cdotp \mathrm{HP}\%=297.71\frac{\mathrm{GJ}}{\mathrm{annum}}\cdotp 277.8\mathrm{kWh}\cdotp 100\%=\mathrm{82,704}\frac{\mathrm{kWh}}{\mathrm{annum}}, $$

where, HP% is the heat pump share in the energy balance.

What is more, calculated operating costs cu of the fuels are based on actual market prices and caloric values of the fuel supplier, cu= fuel unit cost/calorific values. Exemplary estimations are as follows:

  • for natural gas, type E, \( {\mathrm{c}}_{\mathrm{u}}=\frac{0.543\frac{\mathrm{EUR}}{{\mathrm{m}}^3}}{0.03654\frac{\mathrm{GJ}}{{\mathrm{m}}^3}}=14.86\frac{\mathrm{EUR}}{\mathrm{GJ}} \),

  • for heat pump, \( {\mathrm{c}}_{\mathrm{u}}=\frac{9.20\frac{\mathrm{EUR}}{\mathrm{GJ}}\cdotp 32\%}{0.0036\cdotp 277.8\frac{\mathrm{GJ}}{\mathrm{GJ}}}=2.94\frac{\mathrm{EUR}}{\mathrm{GJ}} \);

it is assumed that the operating cost of the heat pump is 32% of total electrical energy demand and that the rest originates from the PV installation.

The price of natural gas 0.543 EUR/m3 derives from (No Author 2021a) and may be a little bit differ from an average value for the country. It also depends on calorific value, an actual EURO exchange rate and on individual agreement between the supplier and the recipient.

An actual prices of electricity may be taken from (No Author 2021b) with the same limitations as above. The value of 9.20 EUR/GJ is calculated on the basis of the following assumptions and calculations: \( \left({\mathrm{P}}_{\mathrm{e}{\mathrm{l}}_{\mathrm{P}\mathrm{C}}}\cdotp 0.119\frac{\mathrm{EUR}}{\mathrm{kWh}}\right)/\left(\mathrm{EU}\cdotp 277.8\frac{\mathrm{kWh}}{\mathrm{annum}}\right)\approx 9.20\frac{\mathrm{EUR}}{\mathrm{GJ}}. \)

In order to establish the direct ecological effect of the investment (Wciślik 2017; Moreno-Mondéjar and Cuerva 2020), the first step involves determining the emission of CO2 from a natural gas boiler station, for option ‘0’ (formulas 35), the next one focusing on a boiler station based on a system of heat pumps (formulas 67); the combined results and the achieved reduction in CO2 are presented in Tables 4 and 5.

Table 4 Results of the calculations of CO2 emissions for the current status and with alternative energy sources
Table 5 Direct ecological effect of the investment1

Annual emission of CO2 from a natural gas boiler:

$$ {\mathrm{E}}_{\mathrm{E}}^{{\mathrm{CO}}_2}={\mathrm{V}}_{\mathrm{E}}\cdotp {\mathrm{WO}}_{\mathrm{E}}\cdotp {\mathrm{WE}}_{\mathrm{E}} $$
(3)

Annual emission of CO2 from electrical energy for powering the boiler assembly:

$$ {\mathrm{E}}_{\mathrm{e}{\mathrm{l}}_{\mathrm{BA}}}^{{\mathrm{CO}}_2}={\mathrm{P}}_{\mathrm{e}{\mathrm{l}}_{\mathrm{BA}}}\cdotp {\mathrm{WO}}_{\mathrm{e}\mathrm{l}}\cdotp {\mathrm{WE}}_{\mathrm{e}\mathrm{l}} $$
(4)

Total annual emission of CO2 for the boiler station:

$$ {\mathrm{E}}_{{\mathrm{E}}_{\mathrm{tot}}}^{{\mathrm{CO}}_2}={\mathrm{E}}_{\mathrm{E}}^{{\mathrm{CO}}_2}+{\mathrm{E}}_{\mathrm{e}{\mathrm{l}}_{\mathrm{BA}}}^{{\mathrm{CO}}_2} $$
(5)

Annual emission of CO2 from electrical energy for powering the heat pumps:

$$ {\mathrm{E}}_{\mathrm{e}{\mathrm{l}}_{\mathrm{P}\mathrm{C}}}^{{\mathrm{CO}}_2}={\mathrm{E}}_{\mathrm{e}{\mathrm{l}}_{\mathrm{P}\mathrm{C}}}={\mathrm{P}}_{\mathrm{e}{\mathrm{l}}_{\mathrm{P}\mathrm{C}}}\cdotp {\mathrm{WO}}_{\mathrm{e}\mathrm{l}}\cdotp {\mathrm{WE}}_{\mathrm{e}\mathrm{l}} $$
(6)

Combined annual emission of CO2 for a system based on heat pumps:

$$ {\mathrm{E}}_{\mathrm{e}{\mathrm{l}}_{\mathrm{tot}}}^{{\mathrm{CO}}_2}={\mathrm{E}}_{\mathrm{e}{\mathrm{l}}_{\mathrm{PC}}}^{{\mathrm{CO}}_2}+{\mathrm{E}}_{\mathrm{e}{\mathrm{l}}_{\mathrm{BA}}}^{{\mathrm{CO}}_2} $$
(7)
$$ {\displaystyle \begin{array}{c}{\mathrm{E}}_{\mathrm{e}{\mathrm{l}}_{\mathrm{PC}}}^{{\mathrm{CO}}_2}=\mathrm{82,704}\ \mathrm{kWh}\cdotp 3.6\frac{\mathrm{MJ}}{\mathrm{kWh}}\cdotp 93.63\frac{\mathrm{kg}}{\mathrm{GJ}}=\mathrm{27,876.87}\frac{\mathrm{kg}}{\mathrm{annum}}\\ {}{\mathrm{E}}_{\mathrm{e}{\mathrm{l}}_{\mathrm{BA}}}^{{\mathrm{CO}}_2}=3,025\ \mathrm{kWh}\cdotp 3.6\frac{\mathrm{MJ}}{\mathrm{kWh}}\cdotp 93.63\frac{\mathrm{kg}}{\mathrm{GJ}}=\mathrm{1,019.63}\frac{\mathrm{kg}}{\mathrm{annum}}\\ {}{\mathrm{E}}_{\mathrm{e}{\mathrm{l}}_{\mathrm{tot}}}^{{\mathrm{CO}}_2}=\mathrm{27,876.87}+\mathrm{1,019.63}=\mathrm{28,896.5}\frac{\mathrm{kg}}{\mathrm{annum}}\end{array}} $$

Resulting reduction in CO2 for a system based on heat pumps:

$$ {\mathrm{E}}_{\mathrm{red}.}=1-\frac{{\mathrm{E}}_{\mathrm{e}{\mathrm{l}}_{\mathrm{tot}}}^{{\mathrm{CO}}_2}}{{\mathrm{E}}_{{\mathrm{E}}_{\mathrm{tot}}}^{{\mathrm{CO}}_2}}\cdotp 100,\% $$
(8)

The next step involves determining the required minimum power of PV cells amounting to Pmin= 36.43 kW (Eq. (9)) and their number nPV = 182, in order to achieve a minimum reduction in CO2 emission of 90% relative to the current status.

$$ {\mathrm{P}}_{\mathrm{min}}=\frac{E_{\mathrm{e}{\mathrm{l}}_{\mathrm{tot}}}^{{\mathrm{CO}}_2}-\left({\mathrm{E}}_{{\mathrm{E}}_{\mathrm{tot}}}^{{\mathrm{CO}}_2}\cdotp 10\%\right)\cdotp 1000}{{\mathrm{WO}}_{\mathrm{e}\mathrm{l}}\cdotp {\mathrm{WE}}_{\mathrm{e}\mathrm{l}}},\frac{\mathrm{kWh}}{\mathrm{annum}} $$
(9)
$$ {\mathrm{P}}_{\mathrm{min}}=\frac{\mathrm{28,896.5}-\left(\mathrm{104,789.79}\cdotp 10\%\right)\cdotp 1000}{3.6\cdotp 93.63}=\mathrm{54,640.37}\frac{\mathrm{kWh}}{\mathrm{annum}}=\frac{\mathrm{54,640.37}}{200\ \mathrm{d}}=273.20\frac{\mathrm{kWh}}{\mathrm{d}}=\frac{273.20}{7.5\mathrm{h}}=36.43\ \mathrm{kW} $$

The required number of PV panels:

$$ NPV=\frac{36.43}{0.2}\cong 182\mathrm{pcs} $$

In order to select the minimum number of PV cells, it was assumed that the estimated average daily time of harvesting energy by photovoltaic cells for the winter period is 7.5 h (see Fig. 9) (what is calculated in typical manner for such purposes and identically as in (Campisi et al. 2018)), the surface area of a single photovoltaic panel – 1.6 m2, and the recovery of electrical power from a single panel is 0.2 kW.

However, the power demand of the boiler room is 82.704 kWh/annum. Assuming that the solar cells will cover 68% of this demand, we get the value of 56,238.72 kWh/annum. In this case, the number of photovoltaic cells will increase to 187.

Economic evaluation

For the proposed option of thermal upgrading analyses in the paper (exchange heat source for electric heat pump with vertical geometrical heat exchanger and supported by a PV system) the following simple and discounted indicators of economic efficiency are calculated:

SPBT—static method,

NPV—dynamic method,

IRR—dynamic method.

In the analysed case, the Simple Pay-Back Time SPBT of expenses paid for an investment related to deep thermal upgrading, including primarily an exchange of the heat source with the necessary equipment (N1 = 201,909 EUR), the purchase and assembly of photovoltaic panels (N2 = 121,859 EUR) and gel batteries (N3 = 154,525 EUR) amounts to almost 25 years, which in the practice of investment economics is considered as an infeasible undertaking. Assumptions presented in Table 6 were made in order to estimate the static indicator of profitability, which is the SPBT.

Table 6 Assessment of the feasibility of modernisation of a heating installation

What must be added, total costs of boiler room modernization (N1) include the following:

  • 42 wells; the total length of the geothermal probes is 4.222 m, and the unit drilling cost is 26.49 EUR/m (~ EUR 111.841),

  • Vitocal 300-G Pro BW2250 brine-water heat pump with 210 kW: EUR 72.407,

  • the hydraulic equipment of the boiler room: EUR 17.661;

the given prices include VAT and result from the investor's cost estimate; given costs are typical for Polish market.

Moreover, assuming a discount rate of R = 4%, the indicator determined based on relationship (10) is NPV < 0 and it amounts to €-260,372.93 which also negates the feasibility of the investment. The building service life was assumed as 15 years (a typical value for an investment of this type).

$$ NPV={\sum}_{i=1}^n\frac{CF_i}{{\left(1+R\right)}^i}-N $$
(10)

The investment turns out to be unquestionably profitable when the co-financing is 70%. This level of co-financing is possible to acquire via contests organized periodically with the participation of the European Union’s capital, e.g. Norwegian Funds 2020. Therefore, when taking advantage of the funding, in this case SPBT = 7.32 years, which is a value about the maximum threshold value for which the investment is considered profitable, meaning 7 years. Interestingly, already with 60% of funding, the dynamic indicator of economic efficiency, which is the NPV, deemed more credible than the SPBT, takes on values higher than ‘0’. To be clear, the relationship between the NPV indicator and the discount rate was determined as well, as shown in Fig. 8.

Fig. 8
figure 8

NPV for an investment as a function of the discount rate, R

Figure 8 indicates how the internal rate of return IRR changes depending on the level of funding. It has been shown that the IRR is higher than the discount rate R = 4% applicable in the calculation period with the co-financing at the level of 60% and is equal to IRR = 5.9%. Moreover, for 30% and lower co-founding, the investment seems to be completely unprofitable. IRR is calculated using Equation (11) and is the quantity at which NPV = 0.

$$ NPV=0\kern1.25em {\sum}_{i=1}^n\frac{CF_i}{{\left(1+ IRR\right)}^i}=N $$
(11)

Table 7 lists the basic indicators of economic efficiency of an investment implemented in an education center, near the geometrical center of Europe, involving the modernization of a gas boiler station and the assembly of a renewable heat source—a ground heat pump with a vertical heat exchanger (the technical aspect of the type of lower heat source is designers decision and is not the subject of the analysis presented in this study. The ground conditions as well as spatial and location possibilities of the investment were also part of the design of this project) supported by photovoltaic cells (the total costs include the purchase of a heat source, the drilling of boreholes, the assembly of PV cells along with gel batteries).

Table 7 Basic indicators of economic effectiveness for a sample investment

On-hand, and for good reason, performed calculations are involving the pay-back time for expenses paid for investments related to the system and use of renewable energy sources. These include e.g. photovoltaic cells, often pointing at very significant savings in operating costs, and reduced harmful substances emitted into Earth’s atmosphere—especially carbon dioxide and particulate matter PM—compared to the conventional manner of producing this energy. However, these values should be related to the life cycle of a given installation, taking into account the energy, the costs and emissions associated with its components (Piasecka et al. 2020; de Almeida et al. 2020).

Moreover, in accordance with Eq. (1), Levelized Cost of Electricity, LCOE for exemplary installation is calculated for the following data set: investment expenditures, It = N2 + N3 = 276,384 EUR, electrical energy generated, Et = 56,238.72 kWh/annum, discount rate R = 4% ÷ 10%, the building service life (expected lifetime of the system), n = 15 ÷ 25 years. Total investment costs taken for consideration for LCOE calculations are only that involved with PV off-grid system and contains photovoltaic panels (N2 = 121,859 EUR) and gel batteries (N3 = 154,525 EUR).

Based on the results of calculations of the costs of energy production from an off-grid photovoltaic installation presented in Fig. 9, it can be concluded that the greatest profitability of the investment is obtained when the LCOE cost is balanced with the average rates for electricity from the grid (in Poland it is ~0.11 EUR/kWh (No Author 2021c)), i.e. only with a 70% subsidy, a discount rate of 4.6% and 20 years of the building's life.

Fig. 9
figure 9

Levelized Cost of Electricity, LCOE as a function of the discount rate, R for thermal up-grading based on the ground heat pump with vertical heat exchangers and PV off-grid system; a) 0% co-financing, b) 40% co-financing, c) 70% co-financing

Generally, currently residential PV systems with storage (off-grid or hybrid) are still more than twice as expensive as PV on-grid systems (Jäger-Waldau 2019). As far as bigger installations (as in here P > 35 kWp ) are concerned, in the literature there is no comprehensive studies to discuss with. But according to (Jäger-Waldau et al. 2019) and very meaningful and interesting study on the spatial distribution of the LCOE of rooftop grid-connected solar PV systems it is clearly shown that LCOE for Malta, Poland and Finland – countries of the better, average and the worse solar irradiation in Europe—is ~6, 26 and 20÷32 EURcent/kWh respectively. It confirms calculations delivered in Fig. 9a), where LCOE for off-grid PV installation without co-financing is presented. The costs of energy production is about two times higher than for grid-connected systems and are from 0.43 EUR/kWh to 0.59 EUR/kWh depending on the discount rate.

Power production estimation for grid-connected, tracking and off-grid systems

The simulation performed using the Photovoltaic Geographical Information System (PVGIS) application (No Author 2020c) allowed comparing the production of energy in a photovoltaic system for three cases:

  1. 1

    on-grid,

  2. 2

    in a tracking system,

  3. 3

    off-grid

The calculations were performed for the same locations which are analyzed above: Bialystok—the geometrical centre of Europe, the capital of Malta–Valletta (with the best solar radiation conditions in EU, see Fig. 3), and the city of Helsinki (southern part of Finland) and Rovaniemi situated in the Arctic Circle, in Finland—country with the worst solar irradiation in EU. Due to diversity in solar radiation in Finland these two geographical localizations are analyzed. The results of the simulation are presented in Fig. 10 and exemplary simulation inputs are: PV installed: 36.43 kWp, system loss: 14%, slope and azimuth: optimized for localization, the installation is integrated to the building, solar radiation database for Europe: PVGIS-ERA5, battery capacity: 32,787 Wh, Discharge cutoff limit is 40%. Moreover, total yearly energy production from PV installation is performed in Fig. 11.

Fig. 10
figure 10

The amount of electrical energy generated by a photovoltaic system for: a) the Bialystok location—the geometrical centre of Europe, b) Malta–Valletta, c) Finland—Helsinki and Rovaniemi locations

Fig. 11
figure 11

The yearly energy production from the PV exemplary installation

Detailed conclusions

The present study discusses the environmental and economic efficiency of a PV fitting supporting a modernised central heating system based on heat pumps with a vertical ground heat exchanger. Moreover, photovoltaic solar electricity potential for the purpose of its conversion and utilization among European countries was presented. The major conclusions of this study are as follows:

  • the policy related to the requirements for obtaining energy from the Sun should at least be adjusted to conditions for each country;

    this study compares the values of the total solar radiation density for a city of Bialystok, Poland in the central part of Europe (897.14 kWh/m2/yr) to the maximum and minimum values recorded for Malta (1766 kWh/m2/yr) and Finland (841 kWh/m2/yr), respectively;

    additionally, the monthly average solar irradiation intensity for the geometric centre of Europe is lower by approx. 26 kWh/m2/mo than the European average which is 100.42 kWh/m2/mo (see Fig. 2);

    the potential of the utilisation of solar energy for the purpose of its conversion may reach even up to 49% what derives from Fig. 1; the yearly sum of solar electricity generated by optimally inclined 1kWpeak system (for Poland, Malta and Finland it amounts to 36o, 32o and 45o respectively) for Poland, Malta and Finland is 675, 1,325 and 631 kWh/kWpeak respectively; therefore, properly configurated system in Poland generates 51% of Malta system and 107% of the system in Finland;

    a detailed estimation of the effective solar energy usage for the above cases were obtained with PV Lighthouse calculator; the simulations confirmed a wide variety of global power density and photon current for into module solar irradiation, especially in the winter period;

    between the central point of Europe–Bialystok (Poland), the capitals of Malta–Valletta and Finland–Helsinki, the respective differences in power density amount to 54 and 33%; the photon current differences amount to 46 and 27%; (see Figs. 5 and 6);

  • the work deals also with environmental and simple economic analysis for specific case of the building localized near the geometrical Europe centre;

    the building was thermally upgraded and the boiler room was modernized; the assumed works costs derive from the energy audit and concern a heat source replacement from gas boiler to an electric brine-water heat pump with vertical geothermal heat exchanger supported by an off-grid PV system;

    in order to achieve a minimum reduction in CO2 emission of 90% (a level required to be granted funding) relative to the existing status it is necessary to install PV cells in a number of 182, which generates high investment costs;

    the Simple Pay-Back Time of expenses paid for the investment SPBT = 25 years, which in the practice of investment economics is considered infeasible;

    it is not until reaching 60% of funding that the dynamic indicator of economic efficiency NPV would take on values higher than ‘0’;

    an investment is entirely profitable with 70% of funding at which SPBT ~ 7 years although NPV > 0; IRR = 10.6% and is higher than the effective and adopted rate of return amounting to 4%.

  • the literature review shows that the cost of capital is the decisive factor for the profitability of the PV investments; the countries with good insolation conditions, but high capital costs (e.g. Bulgaria, Croatia) have a lower technical and economic solar electricity potential than countries with lower production costs, such as Germany or Belgium;

  • the Levelized Cost of Electricity, LCOE of rooftop grid-connected PV systems for Malta, Poland and Finland is ~6, 26 and 20÷32 EURcent/kWh respectively. But, the costs of energy production are about two times higher for off-grid systems and in Poland are from 0.43 EUR/kWh to 0.59 EUR/kWh depending on the discount rate;

  • simulations performed using the Photovoltaic Geographical Information System (PVGIS) shows diversity in energy production from the PV exemplary installations of 36.43 kWp localized in Poland, Malta and Finland. PV grid connected system in Poland is 40% less efficient than in Malta and 12% more than Finish average. In turn, off-grid installation in Poland is 32% less efficient than in Malta and 22% than Finish average. Tracking system is the best option and for each case is more of 32% effective in comparison with on-grid variant, but nowadays is seem to completely unprofitable.

Future investigations

Due to the variation in the number of sunny hours and the intensity of solar radiation during the month, day and hour, it was decided for the Bialystok location to install an off-grid PV system with batteries with a capacity of 32,787 Wh. This allowed for the use of the obtained energy in transition periods, when the current production of electricity from PV cells is insufficient or even zero. The reports available in the literature most often refer to the annual power yield. In the case of locations with seasonally changing insolation conditions, an hourly and monthly simulations of the power efficiency should be presented, which is planned to be performed in further investigation. In periods off the heating season, the surplus energy is sold to the power grid with losses of 30%; the accounting period falls at the end of the calendar year and any unused capacity is missed. Currently, the prices of the gel (and others) batteries used here are at a high level, but there is a downward trend. It is evident that installations of this type are becoming more and more popular. Their price is falling and the service life of the batteries available on the market is getting longer (now it is even about 12 years during buffer working). From the economic point of view, presented off-grid system is not profitable, however, it seemed to be the only one that met the criterion of co-financing investments from foreign funds at that time. The only criterion for receiving 88% funding was the reduction of CO2 emissions at the level of min. 90%. Among the solutions analysed in the project and the energy audit, the installation of HP supported by PV operation seemed the most reasonable.

In next term, it is planned to perform more detailed economic and environmental analysis and to compare the profitability of installations in the off-grid, on-grid and tracking system, taking into account the benefits, legal possibilities of connecting to the network and the economic situation of the European countries.