1 Introduction

Increasing demand for higher performance of the electronic devices and the level reliability of the heat rejection largely requires for these devices. The development of the miniaturized technology, mini and micro-component has rapidly increased especially in the electronic engineering and other fields. Gao and Rowe [1] developed a theoretical model for calculating the cooling performance of an integrated thermoelectric micro cooler. Zhao and Lu [2] presented an analytical and numerical study effect of porosity on the thermal performance a micro channel heat sink. Xuan [3] investigated the effect of the thermal and contact resistances of ceramic plate in thermoelectric micro coolers. Chein and Chuang [4, 5] studied the micro channel heat sink performance with and without thermo-electric using nanofluids as coolants. Bhowmil [6] studied on the steady-state convective heat transfer of water from an in-line four electronic chips in a vertical rectangular channel.

Zhang et al. [7] study of a single-phase heat transfer of micro channel heat sink for electronic packages. Sauciuc [8] presented an electronics cooling advancement challenges and innovation needs. Kminaga Matsumura and Kurakane [9] studied on advanced water cooled heat sink using thermosyphon for electronic device. Naphon and Khonsue [10] studied on the convective heat transfer and pressure drop in the micro channel heat sink. Naphon and Wiriyasart [11] experimentally stuied the liquid cooling in the mini rectangular fin heat sink with and without thermoelectric for CPU.

To the best of author’ knowledge, the papers presented the experimental investigation on the heat transfer in the micro-channel have been reported. The objective of this paper is to study on the heat transfer characteristics of the micro fin heat sink with and without thermoelectric of CPU of PC. Effects of relevant parameter on the cooling CPU are considered.

2 Experimental apparatus

A schematic diagram of the experimental apparatus is shown in Fig. 1. The test loop consists of a set of PC, cooling de-ionized water loop and data acquisition system. The test section and the connections of the piping system are designed such that parts can be changed or repaired easily. The close-loop of de-ionized water consists of storage tank, water pump, flow meter, and radiator. The cooling de-ionized water is chilled by the atmospheric air. After the temperatures of the water are cooled to achieve the desired level, the cooling water is pumped out of the storage tank, and is passed through a flow meter, CPU and returned to the storage tank. The flow rates of the cooling water are controlled by adjusting the valve and measured by the flow meter. The test sections fabricated from the blocks of aluminum with the details are listed in Table 1. The measured temperatures of cooling water at various positions are shown in Fig. 1.

Fig. 1
figure 1

Schematic diagram of experimental apparatus

Table 1 Dimensions of the micro fin heat sinks

The micro fin heat sink unit was shown in Fig. 2. Experiments were conducted with various cooling water flow rates, channel height of heat sink, and run condition of PC. The supplied load into the CPU was adjusted to achieve the desired level by setting run condition of PC. Adjusted to achieve the desired level by setting run condition of PC.

Fig. 2
figure 2

Photograph of the micro fin heat sink components

3 Results and discussion

Each condition of the experiment was performed at the room temperature of 30–31 °C in the period time of 60 min for the steady state condition. The cooling water in the radiator was cooled by the atmospheric air at this temperature. Therefore, the inlet temperature of coolant water before entering the cooling section. In the present study, the cold side of thermoelectric is attached on the CPU of computer while the hot side of thermoelectric is attached with heat sink. The heat is removed from the cold side to the hot side when the electric current passes through the module and then removed to the heat sink. Effects of cooling flow rate on the CPU temperatures for different load conditions of the aluminum heat sink with the channel height of 1.5 mm are shown in Fig. 3. For the three different coolant flow rates, a larger CPU temperature drop is found for a larger coolant flow rate. A larger coolant flow rate results in lower capacity resistance and consequently lower heat sink thermal resistance (Table 2).

Fig. 3
figure 3

Effects of coolant flow rate on CPU temperature for (a) no load conditions and (b) full load conditions

Table 2 Accuracy and uncertainty of measurements

Figure 4 shows the effect of channel height of heat sink on the CPU temperature of PC for no load condition and full load condition. Due to higher heat transfer surface area, the heat transfer rate from CPU to the heat sink increases. Therefore, the CPU temperatures obtained from the heat sink with higher channel height are lower than those with lower channel height, especially for full load condition. It can be seen from the figure that the CPU temperatures for the full load condition are higher than those from the no load condition for the whole range of the period time as shown in Fig. 5. This is because the full load condition generates the heat higher than the no load condition. The CPU temperatures obtained from the liquid cooling for micro fin heat sink with thermoelectric are compared those from the other cooling techniques as shown in Fig. 6a. The CPU temperature and the energy consumption obtained from the water cooling with thermoelectric technique are compared with those from the full load condition as shown in Fig. 6b.

Fig. 4
figure 4

Effects of channel height on CPU temperature for (a) no load conditions and (b) full load conditions

Fig. 5
figure 5

Variations of CPU temperature with time for different load conditions

Fig. 6
figure 6

Effects of cooling technique on CPU temperature for (a) no load conditions and (b) full load conditions

The CPU temperature obtained from the water cooling without thermoelectric technique, water cooling with thermoelectric technique, air cooling with heat pipe technique, are compared with those from the conventional air cooling technique where the plus symbol is represented the higher value while the minus symbol is represented the lower value as compared with the value from the air cooling technique. It can be seen from Table 3 that thermoelectric has significant effect on the cooling of the CPU of PC.

Table 3 Comparison of the temperature between various cooling techniques with air cooling technique

4 Conclusions

Due to the air cooling limitation of the electronic devices with high level of heat generation, the liquid cooling in the micro fin channel heat sink with and without thermoelectric for CPU has been investigated with de-ionized water as working fluid. Effect of channel height of heat sink, coolant flow rate and run condition of PC on the CPU temperature are considered. The results obtained from this technique are compared with those from other cooling techniques. The results of this study are expected to lead to guidelines that will allow the design of the cooling system with improved heat transfer performance of the electronic devices.