1 Introduction

This recommendation deals with the determination of the stiffening and hardening of fresh cementitious materials, mainly mortar and concrete. The method uses an ultrasonic pulse which is transmitted through a sample of fresh material. The transit time is measured which leads with the known travelling distance to the velocity of the longitudinal wave (simply called pulse velocity) in the material. The pulse velocity correlates with the elastic properties. By taking measurements on a regular basis during the first hours of hydration the transition from the fresh state to the hardening state can be clearly detected.

2 Basic principles of the method

A pulse of longitudinal waves (primary or P-wave) is produced by an electro-acoustical transducer which is held in contact of the wall of a container filled with fresh cementitious material (in the sequel called concrete). After traversing a known path length L in the concrete the P-wave is converted to an electrical signal by a second electro-acoustical transducer which is mounted to the opposite wall of the container. By picking the arrival time of the wave (transit time t) and after some corrections the wave velocity v is calculated as

$$ v = L/t\;({{\text{m}} \mathord{\left/ {\vphantom {{\text{m}} {\text{s}}}} \right. \kern-\nulldelimiterspace} {\text{s}}}) $$
(1)

If the whole arriving pulse is measured it can also be evaluated with respect to the transmitted energy and the frequency spectrum (see Sects. 7 and 8). By repeating measurements, e.g. with a measurement interval of 1–5 min, the method allows for a quasi continuous evaluation of hardening concrete right after mixing.

3 Testing devices

3.1 Principles of container geometry

The container has two parallel side walls made out of a transparent polymer material (polymethyl methacrylate). A principle is shown in Fig. 1. The thickness has to be at least 10 mm. In the middle of the side wall some recesses allow for the insertion of nylon wear caps in which the sensors (preferably Panametrics type V601-RB or V602-RB) are screwed. The thickness of the plastic caps is app. 1 mm. Between the sensors and the plastic caps some silicone oil has to be inserted to achieve adequate coupling. Between the side walls the bottom part of the container—out of U-shaped closed cell EPDM foam—is clamped in which the fresh concrete can be filled. The foam has to be soft and water-impermeable and should be tested with respect to its acoustic wave propagation properties before being used. The distance between the fixations of the side walls is such that waves possibly propagating through the walls and the fixations after signal excitation do not interfere with the signals that are directly transmitted through the concrete. The actually needed distance depends on the type of concrete and has to be predefined before testing (see below). A slower mix (e.g. cellular concrete) requires a longer side wall. For a rough estimation of the needed distance between the fixations the following formula could be used:

Fig. 1
figure 1

3D sketch of a container for concrete measurements in through-transmission

$$ l_{ \min } \ge {\frac{{V_{\text{PMMA}} }}{{V_{ \min } }}}d $$
(2)

at which l min is the clear distance between the fixations, d the distance between the two side walls, v PMMA the pulse velocity of the compressional wave of the side walls and v min the minimum compressional wave velocity of the concrete that is expected to be measured during the test.

The fixation of the walls has to be demountable for calibration and cleaning. This ensures also that the container is reusable. The width of the U-shaped part can be smaller for investigations of mortar and have to be larger for concrete according to the maximum aggregate size. The minimum width and height of the U-shaped part must ensure test specimen dimensions that exceed the sensor dimensions and sensor area. To ensure proper sealing the width of the compressible foam has to be in minimum the distance between the side walls. The distance between the side walls has to be at least three times the biggest aggregate size of the mixture. An optimization of the container size is recommended to minimize the amount of wasted material as well as to minimize the transit path of the ultrasonic waves along with their attenuation. A larger container can generally also be used to test small grain size materials. However, every change in the test setup and test container may influence the results from the measurements. It has to be noted that small distances between the side walls require high sampling rates to assure required accuracy (see Sect. 6.2.3).

3.2 Container geometry for cementitious material of not larger than 4 mm grain size

Figure 2 represents the required dimensions of a container recommended for materials with small grain size (not larger than ∅ 4 mm). The distance between the side walls is 22 mm what results in a volume of about 35 cm3 for the tested material.

Fig. 2
figure 2

Mortar container for materials with grain size of not larger than ∅ 4 mm (measures in mm) [1]

3.3 Container geometry for cementitious material of larger than 4 mm grain size

Figure 3 represents the required dimensions of a recommended container for materials with larger grain sizes (∅ larger than 4 mm but less than 20 mm). The distance between the side walls is 60 mm what results in a volume of about 450 cm3 for the tested material.

Fig. 3
figure 3

Concrete container for materials with grain size larger than ∅ 4 mm but less than 20 mm (measures in mm) [1]

3.4 Container geometry for cementitious material with low pulse velocity

The small and the big containers presented in the last sections were recommended to be used for materials with pulse velocities of not less than app. 250 m/s. If lower pulse velocities are expected, the distance between the fixations has to be increased according to Eq. 2 and checked by preliminary tests.

3.5 Transducers

The type of sensors that have to be used are sensors that exploit the piezoelectric effect. Their characteristics play an influential role in the recommended measurements (Fig. 4). Since the attenuation of cementitious materials is relatively high right after mixing one would probably try to operate such piezoelectric sensors in resonance, i.e. the signals are recorded within a small frequency range due to the frequency characteristics of the transducer (Fig. 4a). The disadvantage is that an analysis of the frequencies present in the signal is of no value, because these frequencies are always the same. Very well damped sensors, such as those used for vibration analysis, are operated outside of their resonant frequency allowing broadband analyses to be performed, but are usually less sensitive. It is recommended to use broadband displacement sensors that have a flat frequency response (i.e. the sensor gives the same response over a wide frequency range, see Fig. 4c) that are as sensitive as possible. Appropriate broadband sensors are the Panametrics V601-RB with a center frequency of 0.5 MHz and the Panametrics V602-RB with a center frequency of 1.0 MHz. If other sensors are used their applicability has to be checked and validated in a separate test series. To enhance the signal-to-noise ratio a power amplifier can be used on the emitter side.

Fig. 4
figure 4

Frequency transfer functions (sensitivity over frequency) of piezo electric sensors with different characteristics

If a characterization of the material under test allows an investigation of pulse velocities only (i.e. no energy or frequency analysis is needed) the use of resonant sensors can be discussed. However, since these sensors are limited in their frequency band the determination of onset times can be inaccurate due to a similar effect as described in Sect. 6.2.3. In this case broadband transducers need to be used. A work-around could be the use of multi-resonant sensors (Fig. 4b) that have a frequency transfer function combining several resonances over a broad frequency range. However, the use of such a sensor type for frequency interpretations is very limited. It is not acceptable to compute and interpret the frequency response of the material during setting with resonant or multi-resonant sensors.

3.6 Description of the measurement device

A DataAcQuisition (DAQ) system has to be used for logging data and simultaneously as a triggered function generator which enables to record the start of the outgoing signal for example by using a positive slope with amplitude of 4 V as a trigger pulse (see Sect. 5.2). Figure 5 describes a typical test setup. For most applications the test system consists of a frequency generator, a power amplifier, a measurement container and a preamplifier as well as of an A/D converter and a computer. For the pulse excitation it is recommended to use hardware that could generate rectangular pulses with amplitudes up to 800 V and a signal length down to 2.5 μs to excite broadband pulses. Excitation with half sine waves could be used as an alternative, but results on smaller bandwidth of the excited pulses. In most cases it might be good to interconnect a preamplifier between the receiving transducer and the A/D converter to improve the signal quality. In regard to recording signals two parameters are crucial: the sampling interval τ (μs) and the number of samples n. The measurement time is then equal to the total recorded time of each ultrasonic signal and is calculated by the product of the two. While the sampling interval should not be larger than 1 μs (i.e. less data points) it is recommended to record signals with not less than 1 ms length including the pre-trigger time (see Sect. 5.3). An even shorter sampling interval is recommended if the precision of the onset time determination (see Sect. 6.2.3) is not good enough as can be seen from velocity/time graphs. In these cases a digitizer with at least 5 MHz sampling frequency at 12 bit amplitude resolution would be required.

Fig. 5
figure 5

Typical elements of the test equipment

4 Sample preparation

Testing of the setting and hardening of different materials requires reliable conditions with respect to:

  • Ambient temperature (20°C recommended for standard test procedure)

  • Mixture composition and ingredients

  • Mixture equipment and mixture procedure

  • Filling the container and compaction of the material

  • Storage of the container during the testing.

To keep variation in the testing procedure as low as possible it is recommended to follow the standard EN 196-1 [2] for most of the above mentioned aspects, i.e. the arrangements for testing cementitious materials are well defined. Special arrangements could be made with respect to the individual testing objectives. However, such other arrangements should also be traceable, clearly specified and documented.

4.1 Mixing the material

A traceable mixing procedure is needed for all kinds of mixtures to be tested. If the mixture is prepared for the ultrasonic testing only, a minimum amount of 0.5 l of material should be mixed. Mixing procedure as described in EN 196-1 is recommended if applicable.

4.2 Filling the container and compaction of the material

The container should be moulded immediately after the preparation of the mix. For stiffer mortar as well as for concrete mixtures that have to be compacted it is recommended to follow the procedures mentioned in EN 196-1. For most of the ultrasonic testing cases the procedure should be the following:

  • Fix the container to a jolting apparatus or other reliable compaction equipment similar to that described in EN 196-1 and its Appendix

  • Fill the container with the first of two layers of material

  • Compact the first layer with the compaction apparatus

  • Fill in the second layer of material

  • Compact the second layer with the compaction apparatus.

For free-flowing or self compacting mixtures no compaction is needed. However, for filling the container a trough with an adequate length has to be used to allow self-compaction during the flowing process and to achieve homogeneous filling.

The filling height of the container should be kept within the following limits (see Fig. 6):

Fig. 6
figure 6

Filling height

  • For the small container: h min = 40 mm; h max = 47.5 mm

  • For the big container: h min = 80 mm; h max = 100 mm.

4.3 Protection of the test specimen against evaporation and specimen storage

The filling height should be about 5 mm less than the height of the container. To avoid evaporation and drying out the mix during the test period the specimen should always be sealed with adhesive tape or equivalent material. Covering the specimen right at the beginning of the test with a thin water layer (2–3 mm) might also be effective. Former tests have shown that this does not affect the mixture composition (especially W/C ratio) neither the velocity measurements significantly [1].

The container should be stored on top of an EPDM rubber foam similar to that of the U-shaped form of the container. If ambient temperature conditions are not guaranteed to be constant over the testing period additional temperature measurements are obligatory for validation purposes.

5 Time signals and determination of the transit time

5.1 Ultrasonic time signals

The signals received in through-transmission have to be recorded and stored for documentation and later verifications. All necessary information about the recording procedure like the sampling rate, pre-trigger interval, signal length, amplifications, absolute time of the measurement, filter settings and so far have to be recorded along with the time series.

The signal recordings can be plotted afterwards as shown in Fig. 7. The amplitude of the signals is usually recorded in relative amplitude units, if no absolute calibration is available. Changes of amplitude or energy, respectively, as well as of the frequency content can separately be investigated to characterize the setting and hardening process (see Sects. 7, 8).

Fig. 7
figure 7

Example of changes of the recorded time signals (time after mixing is given above each signal in h:min), amplitudes in relative units

As will be discussed in Sect. 5.3 it is recommended to do repetitive signal recordings in a time window of not more than one second to reduce the statistical error. The average signal usually has a better signal-to-noise ratio by a factor of \( \sqrt n , \) if n is the number of repetitions. The number of repetitions has to be stored along with the data as well.

5.2 Measurement of the emission time

The transit time is the time difference between outgoing and incoming signal. The transit time is together with the distance between the side walls the basis for any pulse velocity calculations (see Sect. 6). The outgoing time corresponds to the trigger time of the piezoelectric transmitter sensor. A trigger pulse (e.g. transistor–transistor logic, TTL) is used to start the emission of the pulse—the emitting part of the ultrasound equipment has to be able to produce this TTL signal with an accuracy of better than 1 μs and to record it. Any delay between the trigger time and the actual emission time of the signal from the first side wall needs to be subtracted according to Sect. 5.4 with at least the same precision as the TTL pulse time. Such a delay can occur due to the time necessary to travel through the container wall and the sensor case.

5.3 Measurement of the arrival time

The transmitted signal is recorded by a sensor attached to the opposite side wall. This signal has to be converted from analogue to digital and to be recorded by a transient recorder. The most crucial part is then to extract as accurate as possible the onset time (i.e. the arrival time) of the signal in relation to the trigger time. If the total recording time t tot is 1 ms (see Sect. 3.6) a pre-trigger time interval of at least 15% (i.e. 150 μs) has to be set to establish for a reliable onset time detection. These first 15% of the signals can be considered as noise. The onset of the signals has to be discriminated from noise. There are various possibilities to do this since there are, threshold and energy based methods and auto-regressive processes. An example how to use the Akaike Information Criterion (AIC) [3] as a detector algorithm is given in the Appendix.

It is recommended to do repetitive measurements of t tot in a time window of not more than one second to reduce the statistical error (see Sect. 5.4). The resulting \( \bar{t}_{\text{tot}} \) value has to be recorded together with the estimated error that consists of a standard deviation and a systematic error. Regarding the error analysis the ones considered by the procedure described in Sect. 5.4 (averaging of t tot) as well as the ones due to measurements of t c (see following section) and L have to be included.

5.4 Correction of the transit time

When the total transit time t tot has been measured the real transit time has to be computed by subtracting the time which is necessary to travel through the container wall and the sensor case t c (see Sect. 6.2.1; calibration). So the real transit time \( t^{\prime}_{\text{tot}} \) is

$$ t^{\prime}_{\text{tot}} = t_{\text{tot}} - t_{c} \;({\text{s}}) $$
(2)

t c has to be determined on the container material according to Sect. 6.2.1. Afterwards the mentioned repetitive measurements of t tot in a time window of not more than one second to reduce the statistical error have to be done. If n (with n ≥ 3) is the number of these measurements the influence of noise is reduced by this averaging by a factor of \( {1 \mathord{\left/ {\vphantom {1 {\sqrt n }}} \right. \kern-\nulldelimiterspace} {\sqrt n }} \) and then \( \bar{t}_{\text{tot}} \) results in:

$$ \bar{t}_{\text{tot}} = {\frac{{\sum\nolimits_{n = 1}^{n} {t_{{{\text{tot}},n}} } }}{n}}\;({\text{s}}) $$

This results with \( t^{\prime}_{\text{tot}} \) from Eq. 2 in

$$ \bar{t^{\prime}}_{\text{tot}} = {\frac{{\sum\nolimits_{n = 1}^{n} {t^{\prime}_{{{\text{tot}},n}} } }}{n}} = {\frac{{\sum\nolimits_{n = 1}^{n} {\left( {t_{{{\text{tot}},n}} - t_{\text{c}} } \right)} }}{n}}\;({\text{s}}), $$
(3)

where \( \bar{t^{\prime}}_{\text{tot}} \) is the sum of the corrected total transit times. For simplification this is further on called t:

$$ t \equiv \bar{t^{\prime}}_{\text{tot}} \;({\text{s}}). $$
(4)

In most cases a repetition of three times (n = 3) is good enough, but it depends on the type of material under investigation.

6 Pulse velocity

6.1 Calculation of the pulse velocity

When the average corrected total transit time t has been calculated the pulse velocity v of the compressional wave yields analogue to Eq. 1

$$ v = L/t\;({\text{m/s}}), $$
(5)

with L the clear distance of the container walls. Since L is subjected to errors this effect has to be taken into account for the error estimation of the total error.

6.2 Calibration, accuracy and reproducibility of the pulse velocity

6.2.1 Calibration of the time/velocity measurement

As mentioned in Sect. 5.4 the time the signal needs to travel through the sensor case and the walls of the concrete/mortar container have to be measured prior to investigations of setting and hardening. Usually, this calibration time t c is in the range of several μs, but it is necessary to subtract this time, because its influence is increasing during the setting observation reciprocal to the reduction of the travel time. This calibration should be redone from time to time or even prior to each measurement campaign. It is done by removing the U-shaped rubber foam part of the container. Both side walls are pressed together and the time t c is determined without any material in between. If repetitive measures of t c show deviations an average value can be calculated similar to t.

6.2.2 Calibration of the sensors

The calibration of the sensors used can be done according to international standards. We recommend the phase-to-phase calibration [4] because it is easy to be implemented and can be done with less time and little expenses.

6.2.3 Accuracy and reproducibility of the velocity calculations

It also has to be ensured that the distance L is not changed throughout the measurements. Usually, the measurement of L is—in addition to t—subjected to errors as well. If that is the case, error propagation algorithms considering L and t have to be used to determine the overall accuracy of v. The error calculated in this way represents the reproducibility of the velocity determination.

If in particular during the initial phase of the measurements the calculated velocity values are not changing and/or are abnormally high, it has to be checked, whether the side wall distance is too small resulting in waves travelling around the container instead of through it (see Sect. 3.1).

The transit time gets significantly shorter during the setting process. The determination of onset times is therefore more and more difficult the lower the t value becomes. A sampling interval (see Sect. 3.6) short enough to enable for accurate onset picking is recommended.

6.3 Presentation of the pulse velocity over setting time

For the presentation of the pulse velocities over setting times a graph showing the evolution of the velocities calculated as described in Sect. 6.1 and based on the onset time data measured as described in Sect. 5 can be plotted. Usually the velocity is a function of the setting time as well as of the material tested – velocity plots of different materials can be combined into one graph. An example for material mixes with different additives added to a standard CEM 42.5 N is given in Fig. 8.

Fig. 8
figure 8

Example of velocity development over setting time of concrete (age of concrete) depending on the type of additives added to a standard mix (curves are smoothed)

The curves can be represented in different ways including the single data points or just showing the data curve. It is valid to smooth the plots by using interpolation algorithms as long as the curvature is not significantly changed. In this case it is mandatory to mention the smoothing of the plots. This could in particular be helpful for the higher velocity values where the accuracy is usually lower (see Sect. 6.2.3). Generally, the determined errors should also be represented in the graph.

7 Transmitted energy ratio

7.1 Calculation of the energy ratio

The transmitted ultrasonic energy E is determined by numerical integration of the squared amplitude values following the onset time.

$$ E = \Upsigma x_{i}^{2} \;\;\;\;{\text{with}}\;i = i_{\text{onset}} \ldots N $$
(6)

x i is the amplitude at sample point i of the signal with N sampling points.

This value is then divided by the reference energy E ref to eliminate the energy loss due to divergence (beam spreading) and reflection at the contact interfaces (transducer–couplant, couplant–plastic wear cap, plastic wear cap–sample). The reference energy is measured during the calibration of the set-up. The reflection at the plastic–sample interface changes in time as the mortar or concrete sets so it cannot be completely eliminated.

To allow an unambiguous determination of the energy ratio, the following specific settings for the transducer RB-602 were obtained from comprehensive examinations and are preferred to be:

  • Rectangular pulse excitation: Excitation pulse length: 2.5 μs (mortar samples), 5 μs (concrete samples); Excitation pulse amplitude: at least 400 V (mortar samples), 750 V (concrete samples)

  • Recording length: 1.638 ms (0.164 ms pretrigger, 1.474 ms recorded signal).

7.2 Calibration, accuracy and reproducibility of the energy ratio

7.2.1 Calibration of the energy measurement

The reference energy E ref is measured with the same set-up and settings as during actual measurements, but with the container filled with water. The average value of at least six measurements of E ref is calculated.

7.2.2 Accuracy and reproducibility of the energy calculations

Shrinkage of the tested specimen can cause the ultrasonic transducers to decouple from the sample. Due to the large impedance mismatch between air and concrete, a small air gap can already cause the energy transmission coefficient to decrease significantly. Due to this large sensitivity of the energy measurements to poor sensor contact, care should be taken to limit drying shrinkage (see Sect. 4.3).

In the period ranging from 4 to 48 h after mixing, an average repeatability error lower than 7% can be obtained.

7.3 Representation of the energy over setting time

Analogously to the velocity measurement, a graph showing the change of the energy calculated as described in Sect. 7.1 can be made (see Fig. 9). The energy is plotted on a logarithmic scale in correspondence with the wave attenuation which is commonly expressed in dB. Generally, smoothing of the energy curves is not required to produce clear graphs.

Fig. 9
figure 9

Example of the change in energy ratio over setting time of concrete for several cement replacement percentages by fly ash (FA)

7.4 Criteria to determine initial and final setting

The initial and final setting times according to the penetration resistance test (ASTM C403) [5] can also be indicated by threshold values of the ultrasonic wave energy [6].

For mortar mixtures:

$$ t_{{{\text{initial\_set}}}} \left( {\text{h}} \right) = t_{{E/E_{\text{ref}} = 0.02}} \left( {\text{h}} \right) $$
(7a)
$$ t_{{{\text{final\_set}}}} \left( {\text{h}} \right) = t_{{E/E_{\text{ref}} = 0.13}} \left( {\text{h}} \right) $$
(7b)

For concrete mixtures:

$$ t_{{{\text{initial\_set}}}} \left( {\text{h}} \right) = t_{{E/E_{\text{ref}} = 0.02}} \left( {\text{h}} \right) $$
(8a)
$$ t_{{{\text{final\_set}}}} \left( {\text{h}} \right) = t_{{E/E_{\text{ref}} = 0.07}} \left( {\text{h}} \right) $$
(8b)

For mixtures with OPC, an average repeatability error lower than 5% can be obtained for these threshold times.

8 Frequency spectrum

8.1 Calculation of the transmitted frequency spectrum

The frequency bandwidth of the generated signal depends on the pulse width. The representation in the frequency domain of a rectangular pulse is the sinc function and the width of the first lob (in Hz) is the reciprocal of the pulse width (in s). Consequently, a narrow pulse leads to a broader frequency spectrum, but with smaller amplitude at the lower frequencies. Higher frequencies reduce the penetration of the wave but are more sensitive to small discontinuities. Therefore, for concrete samples, which have a larger travelling distance between the sensors, a broader pulse (5 μs) is used than for the mortar samples (2.5 μs), as mentioned in Sect. 7.1.

8.1.1 Filtering

To eliminate the DC component and low- and high-frequency noise from this signal, a band-pass filter (100 Hz–1 MHz) is applied.

8.1.2 Fast Fourier transform

The calculation of the fast Fourier transform (FFT) of a transient signal is described in many publications. The relevant issues in relation to the described application are summarized in Appendix.

8.1.3 Smoothing windows

During the signal sampling, only a finite record of the signal is obtained. This finite sampling record results in a truncated waveform whose spectral characteristics differ from the original continuous-time signal. The discontinuity at the edges of the signal produces leakage of spectral information, resulting in a discrete-time spectrum that is a smeared version of the original continuous-time spectrum. The amount of spectral leakage increases with the amplitude of the discontinuity. Smoothing windows can be applied to reduce the amplitude of the discontinuities at the boundaries. The time record is then multiplied by a function whose amplitude decreases gradually towards zero at the edges.

The received ultrasonic signals are transient signals. When these signals are shorter than the length of the window, no window function should be used. Otherwise, the Hanning window is recommended. The choice of window should not be changed during measurements.

8.2 Representation of the frequency spectrum over setting time

The change of the frequency spectrum in time can be visualized in a contour plot with concrete age on the horizontal axis and frequency on the vertical axis (see Fig. 10). Analogously to the energy, the frequency spectrum is plotted on a logarithmic scale expressed in dB.

Fig. 10
figure 10

Contour plots of a fresh concrete sample (w/c = 0.5, CEM I 52.5): the frequency content is presented by the contour lines in function of the concrete age and the frequency (−54, −70, and −100 dB(μV))

The first 3–4 h no significant changes are noticed in the spectra, which corresponds with the dormant period of the cement hydration. The high frequencies gradually appear when the concrete starts to set.

9 Necessary additional measurements

9.1 Temperature

As the ambient and hydration temperature (in the container and in the structural component) essentially influence the measurements, the ambient temperature has to be recorded during the experiment in intervals of an hour or shorter as well as—if possible—the hydration temperature in the container and of a separate sample in an adiabatic or semi-adiabatic container. Parallel measurement of three temperatures is of advantage and can contribute on one hand to increasing the confidence and on the other giving additional information.

The ambient and the hydration temperature in the container can be measured using commercially available thermo-couples. To obtain quasi-adiabatic data, a Dewar container can be used additionally (Fig. 11). Here, account must be taken of the fact that the hydration process in the Dewar container, which simulates a thick structural component, takes place at a much faster rate and can therefore not be directly compared with the sample. This is also the reason why a direct comparison of these data with the ultrasonic measurements is problematic.

Fig. 11
figure 11

Example showing the evolution of the hydration temperature in a Dewar container and in the specimen compared to the ambient (“air”) temperature

10 Test report

The following information for each test shall be given:

  1. 1.

    Identification of type of product

  2. 2.

    Ambient temperature

  3. 3.

    Date of manufacture

  4. 4.

    Size of container

  5. 5.

    Settings of the test device (e.g. measurement intervals, excitation pulse characteristics, sampling rate, etc.)

  6. 6.

    Transit time as function of recording time

  7. 7.

    Pulse velocity as function of recording time

  8. 8.

    Transmitted energy as function of recording time

  9. 9.

    Frequency spectrum as function of recording time

  10. 10.

    Special observations

    1. a.

      air bubbles

    2. b.

      shrinkage

    3. c.

      bleeding

    4. d.

      segregation

    5. e.

      other observations.