Abstract
A mathematical model for predicting the performance of a desiccant wheel with effective regeneration sector has been used. This model has been used to conduct a comparative performance of desiccant wheel with effective and ordinary regeneration sector. It was found that for all the cases considered in this study like rotation of wheel, regeneration temperature, velocity and ambient moisture, the desiccant wheel with “effective regeneration sector” gives better result as compared to ordinary regeneration sector.
Similar content being viewed by others
Avoid common mistakes on your manuscript.
1 Introduction
Nowadays air-conditioner is becoming a basic need in human life and in future, it is expected to play a vital role in our lives. Conventional air conditioning is based on vapour compression system utilizing HFC and HCFC which are harmful to the environment. Dai et al. [1] suggested that a desiccant cooling system is one of the best options to be used for air conditioning as it deals with the latent load and improves the indoor air quality (IAQ) by adsorbing moisture and preventing the contamination of air simultaneously. Desiccant dehumidifier running in open cycle and characterized by zero noise and low maintenance can be driven by solar energy or waste heat.
San and Hsiau [2] developed a one-dimensional (1-D) transient heat and mass transfer model to analyze the effect of axial heat conduction and mass diffusion on the performance of a desiccant wheel and discussed that Biot number (Bi) and NTU were two important parameters which affected the dehumidification ability. Dai et al. [1] evaluated the dehumidification performance of desiccant wheel on the basis of wave shape through wave analysis using psychrometric chart and discussed the effects of some important parameters, such as heat capacity, adsorption heat, rotational speed, regeneration temperature, thickness of the desiccant matrix and desiccant isotherm on the performance. Zhang and Niu [3] developed a 2D (axial direction and thickness direction) transient heat and mass transfer model for desiccant wheel and took into account both gas side and solid side resistance. They compared the performance of a desiccant wheel used in air dehumidification and enthalpy recovery on the basis of rotary speed, NTU and specific area. Niu and Zhang [4] developed a 2D (axial direction and thickness direction) transient heat and mass transfer model for desiccant wheel to calculate the optimum rotary speed for sensible heat recovery, latent heat recovery and air dehumidification which takes into account both gas side and solid side resistance. They also analyzed the effect of channel wall thickness on the optimum rotary speed used in air dehumidification and enthalpy recovery. Xuan and Radermacher [5] developed a 1-D transient model considering heat and mass transfer for moist air to investigate the performance of the wheel. Their simulation results revealed a significant effect of different regeneration temperatures, air flow rates and wheel speeds on the performance of wheel. Gao et al. [6] described a 1D mathematical model considering the heat and mass transfer in moist air as well as desiccant material to predict the transient and steady state transport in a desiccant wheel. The effect of desiccant thickness (felt thickness) and passage shape on the performance of a desiccant wheel was also investigated. Harshe et al. [7] presented a two-dimensional (2-D) steady-state model pertaining to a rotary desiccant wheel which included the mass and energy balance equations for the air streams and the desiccant wheel. The model was capable of predicting the steady-state behavior of a desiccant wheel for process, purge and regeneration sector. Sphaier and Worek [8] compared 1D and 2D mathematical models for both solid side and gas side resistance and found that 1D formulation could be used in desiccant wheel applications whereas a 2D model was needed for an enthalpy exchanger when thermal resistance in desiccant material was high. Ruivo et al. [9] described a 1D transient numerical solution of the conservation equations for heat, water vapour and adsorbed water inside the porous medium and found that surface diffusion was the most important mechanism of water transport within the porous medium by assuming a lumped heat capacitance model in the cross directions of the channel wall. Nia et al. [10] developed a 1D transient mathematical model by considering the heat and mass transfer for moist air and determined the optimum rotational speed by examining the outlet adsorption side humidity ratio to improve the performance of an adiabatic rotary dehumidifier. Golubovic et al. [11] evaluated the performance of a rotary dehumidifier on the basis of three sectors namely: purge, process and regeneration. The performance of a desiccant wheel with a heated effective purge angle was compared with the performance of the same wheel without a purge angle. It was found that heated effective purge angle had an overall positive effect on the performance of a rotary dehumidifier. Bourdoukan et al. [12] performed a sensitivity analysis of a desiccant wheel dehumidification using the design of experiments and also studied the effect of operating parameters on the dehumidification rate of the wheel by experimental and numerical results. Zhai et al. [13] developed a 1-D transient heat and mass transfer equations for a desiccant wheel allowing lumped formulation. The performance model related the wheel’s design parameters (wheel dimension, channel size and desiccant properties) and operating parameters (rotary speed, condition of process and regeneration air and regeneration air flow rate) to its operating performance. They also discussed the effect of some practical issues such as wheel purge, residual water in the desiccant and the wheel supporting structure on the wheel performance. Ruivo et al. [14] developed 1D transient heat and mass transfer model for desiccant wheel and presented two approaches. In the first approach, the model was valid for thickness lower than 0.1 mm, neglecting the transversal heat and mass transfer resistance in micro porous desiccant while in the second approach, the model was valid for thickness lower than 5 mm, neglecting only thermal resistance. Chung and Lee [15] developed a 1D transient model to examine the operating and design parameters (rotation speed and area ratio of regeneration to adsorption) of desiccant wheel for a range of regeneration temperature (50–150 °C). Performance evaluation was based on MRC (moisture removal capacity). Simulations were focused on the effect of desiccant isotherm at optimal conditions of the operating and design parameters and also the effect of outdoor air temperature and humidity on the optimum design parameters were examined. Antonellis et al. [16] developed a 1-D transient gas side resistance model for desiccant wheel which considered developing temperature and velocity profiles along the channels. This model was used to optimize the influence of working conditions, revolution speed and desiccant wheel configuration on the performance of the desiccant wheel. Ge et al. [17] developed a 1-D transient model to predict the performance of a compound desiccant wheel considering both the gas side resistance and the solid side resistance. The compound desiccant wheel was found to have a better performance in a climate with moderate temperatures or in a climate with a high humidity ratio. Narayanan et al. [18] developed a 1D transient gas and solid side resistance model and compared the performance of different desiccant wheel designs (Parallel flow, counter flow and additional axial cooling). They found counter flow desiccant wheel had much better dehumidification performance than parallel flow and a counter flow with axial cooling improved the dehumidification performance considerably. Yadav and Bajpai [19] presented 1D both gas and solid side resistance model to optimize the design parameters (wheel length, channel height, channel pitch, porosity and volume ratio of desiccant wheel) by taking Nusselt number and Sherwood number same. Yadav and Bajpai [20] presented 1D both gas and solid side resistance model to analyze the performance of two sectors with heated and cooled purge at different regeneration temperature and found that the desiccant system with a higher purge angle and lower regeneration angle performs better at low rph as compared to a lower purge angle and higher regeneration angle.
Many of the existing evaluations of a desiccant wheel are based on various operating parameters and design parameters. Though some researchers focused on a desiccant wheel with the purge sector but none focused on the analysis effective and ordinary regeneration sector so far. The objective of this paper is to use a mathematical model for comparing the performance of desiccant wheel with effective and ordinary regeneration sector.
2 Mathematical model
A desiccant wheel is an air to air heat and mass exchanger, with a relatively low rotational speed (N). The wheel consists of a matrix having layers of desiccant material and matrix material (supporting material). The channels can be of various shapes such as sinusoidal, honeycomb, triangular etc. The desiccant wheel is divided into three sectors according to the air streams passed. In the angular sector of process air, dehumidification of air takes place and in the angular sector of regeneration air of the wheel, humidification of the air takes place. There is another angular sector known as purge sector in which the dehumidification of air takes place and this dehumidified air becomes an input to the angular sector of regeneration. The sector angles of process air, regeneration air and purge air are denoted by ‘θp’,’ θr’ and ‘θpurge’ respectively. The rotation of the wheel causes periodic reactivation of the adsorption area. The schematic Figures of a desiccant wheel and control volume adopted in the model are shown in Fig. 1. One sinusoidal channel with a length ‘dx’ is selected as a differential control volume. It should be noted that matrix material and the desiccant material layer are shared by two channels. Where ‘A f ’ represents cross-sectional area of flow passage of one channel, ‘P e ’ is the perimeter of the air flow passage and ‘A t ’ represents the total cross-sectional area of one channel.
The diagram of single channel is shown in Fig. 1c.
Let,
-
The height of flow passage of one channel = 2a.
-
The pitch of flow passage of one channel = 2b.
-
The cross-sectional area of flow passage of one channel, Af = 2ab.
-
Thickness of the channel wall = δ.
-
Total cross sectional area of one channel, \({\text{A}}_{\text{t}} = \frac{1}{2} \times (2{\text{a}} + {\updelta})(2{\text{b}} + {\updelta}).\)
-
The perimeter and hydraulic diameter is given by [7].
-
Perimeter of flow passage of one channel, \(\text{P}_{\text{e}} { \approx 2b + 2}\sqrt {\text{b}^{\text{2}} { + (a\uppi )}^{\text{2}} } \text{ }\frac{{\text{3 + }\left( {\frac{{\text{2b}}}{{{a\uppi }}}} \right)^{\text{2}} }}{{\text{4 + }\left( {\frac{{\text{2b}}}{{{a\uppi }}}} \right)^{\text{2}} }}.\)
-
Hydraulic diameter of flow passage of one channel, \({\rm{D}}_{\rm{h}} =\frac{{\rm{4A}_{\rm{f}}}}{{\rm{P}_{\rm{e}}}}.\).
2.1 Model assumptions
The following assumptions have been considered:
-
All air channels are assumed to be adiabatic.
-
Rotary speed is constant and low enough to neglect the effect of centrifugal force.
-
Axial heat conduction and mass diffusion in the moist air are negligible.
-
No leakage between different regions.
-
All channels in the desiccant wheel are made of the same material and configuration. There is a uniform distribution of matrix material and desiccant material along the channel.
-
The matrix material does not adsorb any moisture.
-
The inlet air conditions are uniform through the channel air domain, but may vary with time.
-
The thermodynamic properties of the dry air and the properties of the dry desiccant material as well as of the matrix material are constant.
2.2 Governing equation
In the mathematical model, the used equations are taken from Ge et al. [17]. These equations are derived from the fundamental laws of heat and mass transfer. There are two control volumes in the channel, one for moist air and the another for the layer of desiccant material.
Taking conservation of moisture and heat, four governing equations derived for moist air and desiccant material are as follows:
Mass balance of water vapour in moist air:
The first term of the left hand side \(\uprho_{\text{a}} {\text{A}}_{\text{t}} {\text{A}}_{\text{r}} \left( {\frac{{\partial {\text{Y}}_{\text{a}} }}{{\partial {\text{t}}}}} \right)\) represents the moisture storage in the air and the second term \(\uprho_{\text{a}} {\text{A}}_{\text{t}} {\text{A}}_{\text{r}} \left( {{\text{u}}\frac{{\partial {\text{Y}}_{\text{a}} }}{{\partial {\text{x}}}}} \right)\) represents the change of moisture content in control volume (dx) of air. The term of the right hand side \({\text{h}}_{\text{m}} {\text{P}}_{\text{e}} \left( {{\text{Y}}_{\text{d}} - {\text{Y}}_{\text{a}} } \right)\) represents the convective mass transfer.
Energy balance in moist air:
The first term of the left hand side \(\uprho_{\text{a}} \left( {{\text{c}}_{\text{pa}} + {\text{Y}}_{\text{a}} {\text{c}}_{\text{pv}} } \right)\left( {{\text{A}}_{\text{t}} {\text{A}}_{\text{r}} } \right)\left( {\frac{{\partial {\text{T}}_{\text{a}} }}{{\partial {\text{t}}}}} \right)\) represents the energy storage in the air and the second term \(\uprho_{\text{a}} \left( {{\text{c}}_{\text{pa}} + {\text{Y}}_{\text{a}} {\text{c}}_{\text{pv}} } \right)\left( {{\text{A}}_{\text{t}} {\text{A}}_{\text{r}} } \right)\left( {{\text{u}}\frac{{\partial {\text{T}}_{\text{a}} }}{{\partial {\text{x}}}}} \right)\) represents the rate of energy variation in control volume of air. The first term of the right hand side \({\text{hP}}_{\text{e}} \left( {{\text{T}}_{\text{d}} - {\text{T}}_{\text{a}} } \right)\) represents the heat transfer due to convection and the second term \({\text{h}}_{\text{m}} {\text{P}}_{\text{e}} \left( {{\text{Y}}_{\text{d}} - {\text{Y}}_{\text{a}} } \right){\text{c}}_{\text{pv}} \left( {{\text{T}}_{\text{d}} - {\text{T}}_{\text{a}} } \right)\) represents the sensible heat transfer between air and desiccant.
Mass balance of water in the desiccant material:
The first term of the left hand side \(\uprho_{\text{a}} {\epsilon} \left( {1 - {\text{A}}_{\text{r}} } \right){\text{A}}_{\text{t}} \frac{{\partial {\text{Y}}_{\text{d}} }}{{\partial {\text{t}}}}\) represents the moisture storage term inside the desiccant pore and the second term \(\uprho_{\text{d}} \left( {1 - {\epsilon} } \right)\left( {1 - {\text{A}}_{\text{r}} } \right){\text{A}}_{\text{t}}\upphi\frac{{\partial {\text{W}}}}{{\partial {\text{t}}}}\) represents the moisture storage on the desiccant surface. The first term of the right hand side \(\uprho_{\text{a}} {\epsilon} \left( {1 - {\text{A}}_{\text{r}} } \right){\text{A}}_{\text{t}} {\text{D}}\frac{{\partial^{2} {\text{Y}}_{\text{d}} }}{{\partial {\text{x}}^{2} }}\) represents the mass diffusion in the pores due to ordinary and Knudsen diffusion and the second term \(\uprho_{\text{d}} \left( {1 - {\epsilon} } \right)\left( {1 - {\text{A}}_{\text{r}} } \right){\text{A}}_{\text{t}}\upphi{\text{D}}_{\text{S}} \frac{{\partial^{2} {\text{W}}}}{{\partial {\text{x}}^{2} }}\) represents the surface diffusion in an axial direction. The last term of the right hand side \({\text{h}}_{\text{m}} {\text{P}}_{\text{e}} \left( {{\text{Y}}_{\text{a}} - {\text{Y}}_{\text{d}} } \right)\) represents the convective mass transfer.
Energy balance in the desiccant material:
The first term of the left hand side \({{\uprho}}_{\text{m}} {\text{c}}_{\text{m}} \left({1 - {{{\epsilon}}}} \right)\left({1 - {\text{A}}_{\text{r}}} \right){\text{A}}_{\text{t}} \left({1 -\upphi} \right)\frac{{\partial {\text{T}}_{\text{d}}}}{{\partial {\text{t}}}}\) represents the energy storage terms in the matrix material and the second term \({{\uprho}}_{\text{d}} {\text{c}}_{\text{d}} \left({1 - {{{\epsilon}}}} \right)\left({1 - {\text{A}}_{\text{r}}} \right){\text{A}}_{\text{t}}\upphi\left[{\frac{{\partial {\text{T}}_{\text{d}}}}{{\partial {\text{t}}}}} \right]\) represents the energy storage term in the desiccant material and the third term \(\uprho_{\text{d}} {\text{c}}_{\text{d}} \left( {1 - {\epsilon}} \right)\left( {1 - {\text{A}}_{\text{r}} } \right){\text{A}}_{\text{t}}\upphi\left[ {\frac{{{\text{k}}_{\text{d}} }}{{\uprho_{\text{d}} {\text{c}}_{\text{d}} }}\frac{{\partial^{2} {\text{T}}_{\text{d}} }}{{\partial {\text{x}}^{2} }}} \right]\) represents the heat conduction in the desiccant material. The first term of the right hand side \({\text{hP}}_{\text{e}} \left( {{\text{T}}_{\text{d}} - {\text{T}}_{\text{e}} } \right)\). represents the heat transfer due to convection and the second term \({\text{h}}_{\text{m}} {\text{P}}_{\text{e}} \left( {{\text{Y}}_{\text{a}} - {\text{Y}}_{\text{d}} } \right) {\text{c}}_{\text{pv}} \left( {{\text{T}}_{\text{a}} - {\text{T}}_{\text{d}} } \right)\) represents the sensible heat transfer between air and desiccant and the last term \({\text{h}}_{\text{m}} {\text{P}}_{\text{e}} \left( {{\text{Y}}_{\text{a}} - {\text{Y}}_{\text{d}} } \right){\text{q}}_{\text{ad}}\) represents the heat of adsorption released to the desiccant layer.
2.3 Boundary and initial conditions
The inlet conditions for the air are:
For process sector
For purge sector
For ordinary regeneration sector
For effective regeneration sector
The initial temperature and humidity ratio of the air are assumed to be uniform and also initial temperature and water content of the desiccant are assumed to be uniform:
2.4 Auxiliary conditions
Humidity ratio and relative humidity are related as [17]
where \(P_{vs}\) is the saturation pressure of water vapour which can be found using the following relation [17]
The equilibrium isotherm is given by [23]
The adsorption heat of regular density silica gel as recommended by [2]
The latent heat of the water vapour at a different temperature is given by [21]
The vapour can diffuse through pores of desiccant by three mechanisms, namely surface diffusion, ordinary diffusion and Knudsen diffusion with diffusion coefficient of \({\text{D}}_{\text{S}}\), \({\text{D}}_{\text{o}}\) and \({\text{D}}_{\text{k}}\). The ordinary diffusion coefficient and Knudsen diffusion coefficients are combined by combine diffusivity \({\text{D}}_{\text{comb}}\). These coefficients can be estimated by the following expressions [23].
where, τ is tortuosity factor that account for the increase in diffusion length due to the tortuous path of real pores and its value is 2.8 for regular density silica gel.
Sutherland’s formula can be used to calculate the dynamic viscosity of an air as a function of the temperature [24].
Where, μ = dynamic viscosity (Pa s) at temperature \({\text{T}}\); \(\upmu_{0}\) = reference viscosity (Pa s) at reference temperature \({\text{T}}_{\text{so}}\); T = temperature of air in Kelvin; \({\text{T}}_{\text{so}}\) = reference temperature in Kelvin; \({\text{C}}_{0}\) = Sutherland’s constant for the air; \(\upmu_{0} = 18.27 \times 10^{ - 6} \, {\text{Pa s}}\); \({\text{T}}_{\text{so}}\) = 291.15 K; \({\text{C}}_{0}\) = 120 K.
The Nusselt number for the fully developed flow depends on the channel geometry is given by [16]
where, Aspect ratio, \({\upalpha} = \frac{{2{\text{a}}}}{{2{\text{b}}}}\)
In order to develop the temperature and velocity profile along the channel, Nusselt number is evaluated by [16]
The following heat transfer coefficient is adopted
The following relations are adopted from Chilton Colburn analogy.
The following mass transfer coefficient is adopted
The mass diffusion coefficient of vapour in the air is given by [17]
where,
2.5 Solution method
In this model the four governing equations of heat and mass transfer are non-linear and coupled. The four governing equations are being solved using a PDE solver. This PDE solver is based on the finite element method (FEM). The programming is done in the script language of solver. Two programs in the script language are made for process and regeneration in two sectors of a desiccant wheel and three programs in the script language are made for process, purge sector and regeneration of a desiccant wheel. These three programs are coupled in the solver to simulate real conditions.
3 Model validation
3.1 Heat and mass transfer
Experimental results related to the desiccant wheel Kodama [22] are also adopted to validate the present model. The desiccant wheel channel pitch, height and wall thickness are 0.0032, 0.0018 and 0.0002 m respectively and the desiccant wheel length is 0.2 m operating under a wide range of operating conditions which are given in Table 1.
Experimental data and simulation results shown in Fig. 2 agree well under the various conditions. The mathematical model is fully validated and ready for implementation for different wheel designs.
3.2 Pressure drop
The experimental data available for a commercial desiccant wheel verifies the pressure drop correlation where the geometry of channel is triangular (channel height = 0.002 m, channel pitch = 0.004 m and wheel length = 0.2 m) Antonellis et al. [16].
The pressure drop was calculated as Harshe et al. [7]
where f is the friction factor and \({\text{K}}_{0}\) represents the velocity head loss at the entry and exit of the desiccant wheel.
The friction factor f is given by Antonellis et al. [16].
Friction factor, \({\text{f}} = 13/{Re}\;\) \({\text{K}}_{0}\) = 0.5 = constant for sudden contraction loss.
Table 2 shows both experimental data and simulation results of pressure drop for different values of the face velocity.
Experimental data and simulation result closely match.
Good agreement of experimental and simulation result for pressure difference.
4 Numerical results and discussion
The performance of the desiccant wheel of the specification listed in Table 3 is analyzed under various operating and structural conditions as listed in Table 4.
4.1 Performance index
The main function of a desiccant wheel is to remove the water vapour from the process air. Therefore, the performance indices represent the dehumidification capacity of the desiccant. There are several performance indices such as moisture removal, relative moisture relative efficiency, effectiveness of wheel and DCOP (Dehumidification coefficient of performance) of wheel. Moisture removal (MR) is adopted as an index to represent the absolute dehumidification capacity of desiccant dehumidifier.
where, \({\text{Y}}_{{{\text{p}},{\text{in}}}}\) is the humidity ratio of the process air at the inlet and \({\text{Y}}_{{{\text{p}},{\text{out}}}}\) is the humidity ratio of the process air at the outlet.
4.2 Introduction of effective and ordinary regeneration sector and its effect on the performance of desiccant wheel under various operating condition
4.2.1 Theory for 3(a) and 3(b) figure
Schematic diagrams of desiccant wheel with effective and ordinary regeneration sector are shown in Fig. 3a–d.
4.2.2 Performance comparison of desiccant wheel with effective and ordinary regeneration sector at different rotational speeds
Figure 4 shows that moisture removal initially increases and then becomes steady for both effective and ordinary regeneration sector with the increase in rotational speed of desiccant wheel. For all the ranges of speed of rotation, moisture removal of process air with effective regeneration sector is better as compared with ordinary regeneration sector because in case of effective regeneration sector output of purge sector is the input of regeneration sector due to which humidity ratio at the inlet of regeneration decreases. Hence performance of process sector increases. At low speed of rotation, effect of regeneration sector is less and it increases with increase in rotational speed of desiccant wheel; for example at rotational speed of 10 rph and 60 rph the difference in moisture removal between effective and ordinary regeneration sector is 0.000891 and 0.001665 respectively. Maximum value of moisture removal for effective regeneration sector is 0.006104 at 40 rph and maximum value of moisture removal for ordinary regeneration sector is 0.00443 at 35 rph.
Figure 5 shows that with an increase in rotational speed of desiccant wheel, the temperature difference of process air initially increases and then becomes steady for both effective and ordinary regeneration sector. For all the range of speed of rotation, the temperature difference of process air with effective regeneration sector is greater as compared with ordinary regeneration sector. At low speed of rotation, effect of regeneration sector is less and it increases with increase in rotational speed of desiccant wheel; for example at rotational speed of 10 and 60 rph, the temperature difference of process air between effective and ordinary regeneration sector is 1.61 °C and 3.2 °C respectively. Maximum value of temperature difference of process air with effective regeneration sector is 11.22 °C at 40 rph and maximum value of temperature difference of process air with ordinary regeneration sector is 8.02 °C at 35 rph.
4.2.3 Performance comparison of desiccant wheel with effective and ordinary regeneration sector at different regeneration temperatures
Figure 6 shows that moisture removal increases for both effective and ordinary regeneration sector with increase in the regeneration temperature. Maximum value of moisture removal for effective and ordinary regeneration sector is 0.006048 and 0.006019 respectively, at a regeneration temperature of 373 °C. But difference in moisture removal between effective and ordinary regeneration sector is small, which means an increase in regeneration temperature does not affect moisture removal to a great extent.
Figure 7 shows that temperature difference of process air increases for both effective and ordinary regeneration sector with increase in the regeneration temperature. Maximum value of temperature difference of process air for effective and ordinary regeneration sector is 11.08 and 11.02 °C respectively, at a regeneration temperature of 373 °C. But difference in temperature between effective and ordinary regeneration sector is small, it means increase in regeneration temperature does not affect temperature difference to a great extent.
4.2.4 Performance comparison of desiccant wheel with effective and ordinary regeneration sector at different velocities
Figure 8 shows that moisture removal initially increases and then decreases for both effective and ordinary regeneration sector with the increase in velocity. At low velocity, difference of moisture removal of process air between effective and ordinary regeneration sector is small. As velocity increases difference of moisture removal is maximum and it is maximum at optimum velocity of 2 m/s. Maximum value of moisture removal for both effective and ordinary regeneration sector is 0.004506 and 0.004375 respectively, at a velocity of 2 m/s.
Figure 9 shows that with the increase in velocity, temperature difference of process air initially increases and then decreases for both effective and ordinary regeneration sector. At low velocity, difference of temperature of process air between effective and ordinary regeneration sector is small, as velocity increases, temperature difference is maximum and it is maximum at optimum velocity of 2 m/s. Maximum value of temperature difference for effective and ordinary regeneration sector is 8.15 and 7.91 °C respectively, at a velocity of 2 m/s.
4.2.5 Performance comparison of desiccant wheel with effective and ordinary regeneration sector at different ambient moisture
Figure 10 shows that moisture removal increases for both effective and ordinary regeneration sector with increase in the ambient moisture. As the ambient moisture increases, difference of moisture removal of process air between effective and ordinary regeneration sector remains same. Maximum value of moisture removal for effective and ordinary regeneration sector is 0.004859 and 0.004792 respectively at ambient moisture of 0.0025 kgwater vapour/kgdry air.
Figure 11 shows that with an increase in the ambient moisture, the temperature difference of process air increases for both effective and ordinary regeneration sector. As the ambient moisture increases, difference of temperature of process air between effective and ordinary regeneration sector is same. Maximum value of temperature difference of process air for effective and ordinary regeneration sector is 8.77 and 8.65 °C, at ambient moisture of 0.0025 kgwater vapour/kgdry air.
5 Conclusion
The main conclusions of this paper are summarized as
-
1.
For all the given rotational speeds of desiccant wheel, the moisture removal for effective regeneration sector is better as compared with ordinary regeneration sector. At low speed of rotation, effect of effective regeneration sector is less and it increases with increase in rotational speed of desiccant wheel.
-
2.
At any regeneration temperature, the moisture removal is slightly better for effective regeneration sector as compared with ordinary regeneration sector.
-
3.
At any velocity between 1 and 4 m/s, the moisture removal for effective regeneration sector is better as compared with ordinary regeneration sector and maximum difference of moisture removal for effective and ordinary regeneration sector is 0.000131 at 2 m/s.
-
4.
At any ambient moisture, the moisture removal is slightly better for effective regeneration sector as compared with ordinary regeneration sector.
Abbreviations
- A:
-
Cross sectional area (m2)
- Af :
-
Cross sectional area of flow passage of one channel (m2)
- Ar :
-
Area ratio of air flow passage to the total area of one channel
- AR:
-
Aspect ratio (ratio of height to pitch) for channel
- At :
-
The total cross-sectional area of one channel (m2)
- cd :
-
Specific heat of silica gel (J/kg K)
- cm :
-
Specific heat of matrix material (J/kg K)
- cp :
-
Constant pressure specific heat J/kg K
- dpore :
-
Diameter of pores (nm)
- D:
-
Diameter of wheel (m)
- Dcomb :
-
Combined diffusivity including ordinary and Knudsen diffusivity (m2/s)
- Dh :
-
Hydraulic diameter of flow passage of one channel (m)
- Dk :
-
Knudsen diffusivity (m2/s)
- Dm :
-
Mass diffusion coefficient of vapour in the air
- Do :
-
Ordinary diffusivity/molecular diffusivity (m2/s)
- DS :
-
Surface diffusivity (m2/s)
- f:
-
Friction factor
- Gz:
-
Graetz number
- h:
-
Convective heat transfer coefficient (W/m2K)
- hfg :
-
Latent heat of water vapour (J/kg)
- hm :
-
Convective mass transfer coefficient (kg/m2s)
- k:
-
Thermal conductivity (W/mK)
- Le:
-
Lewis number
- Lw :
-
Wheel length (m)
- M:
-
Molecular weight of water (kg/mol)
- Mr :
-
Moisture removal (kgwater vapor/kgdry air)
- N:
-
Rotational speed (rph)
- Nu:
-
Nusselt number
- NuFd :
-
Nusselt number for fully developed region
- P:
-
Pressure (Pa)
- Pa :
-
Atmospheric pressure
- ΔP:
-
Pressure drop (Pa)
- Pe :
-
Perimeter of air flow passage of one channel (m)
- Pr:
-
Prandtl number
- qad :
-
Heat of adsorption (J/kgadsorbate)
- r:
-
Pore radius (m)
- RH:
-
Relative humidity
- Re :
-
Reynold number
- Sh:
-
Sherwood number
- t:
-
Time (s)
- T:
-
Temperature (°C)
- u:
-
Velocity (m/s)
- W:
-
Water content of desiccant (kgadsorbate/kgadsorbent)
- x:
-
Axial direction
- Y:
-
Humidity ratio (kgwater vapor/kgdry air)
- θp :
-
Sector angle of process air (°)
- θr :
-
Sector angle of regeneration air (°)
- ρ:
-
Density (kg/m3)
- ε:
-
Porosity
- τ:
-
Tortuosity factor
- ϕ:
-
Volume ratio of desiccant material in layer
- µ:
-
Dynamic viscosity (Pa s)
- θ:
-
Sector angle (°)
- θpurge :
-
Angular sector of purge air
- δ:
-
Thickness of channel wall (m)
- η:
-
Relative moisture removal efficiency
- a:
-
Air
- d:
-
Desiccant
- da:
-
Dry air
- in:
-
Inlet
- m:
-
Matrix material
- 0:
-
Initial state
- out:
-
Outlet
- p:
-
Process air
- r:
-
Regeneration air
- v:
-
Water vapor
- EXP:
-
Experimental
- PDE:
-
Partial differential equation
- PS:
-
Process sector
- RS:
-
Regeneration sector
- SIM:
-
Simulation
References
Dai YJ, Wang RZ, Zhang HF (2001) Parameter analysis to improve rotary desiccant dehumidification using a mathematical model. Int J Therm Sci 40:400–408
San JY, Hsiau SC (1993) Effect of axial solid heat conduction and mass diffusion in a rotary heat and mass regenerator. Int J Heat Mass Transf 36(8):2051–2059
Zhang LZ, Niu JL (2002) Performance comparisons of desiccant wheels for air dehumidification and enthalpy recovery. Appl Therm Eng 22:1347–1367
Niu JL, Zhang LZ (2002) Effects of wall thickness on the heat and moisture transfers in desiccant wheels for air dehumidification and enthalpy recovery. Int Commun Heat Mass Transf 29(2):255–268
Xuan S, Radermacher R (2005) Transient simulation for desiccant and enthalpy wheels. International sorption heat pump conference, Denver, co, USA, June 2005
Gao Z, Mei VC, Tomlinson JJ (2005) Theoretical analysis of dehumidification process in a desiccant wheel. J Heat Mass Transf 41:1033–1042
Harshe YM, Utikar RP, Ranade VV, Pahwa D (2005) Modeling of rotary desiccant wheels. Chem Eng Technol 28(12):1473–1479
Sphaier LA, Worek WM (2006) Comparisons between 2-D and 1-D formulation of heat and mass transfer in rotary regenerators. Numer Heat Transf Part B 49:223–237
Ruivo CR, Costa JJ, Figueiredo AR (2006) Analysis of simplifying assumption for the numerical modeling of the heat and mass transfer in a porous desiccant medium. Numer Heat Transf Part A 49:851–872
Nia FE, Paassen DV, Saidi MH (2006) Modeling and simulation of desiccant wheel for air conditioning. Energy Build 38:1230–1239
Golubovic MN, Hettiarachchi HDM, Worek WM (2007) Evaluation of rotary dehumidifier performance with and without heated purge. Int Commun Heat and Mass Transf 34:785–795
Bourdoukan P, Wurtz E, Joubert P, Sperandio M (2008) A sensitivity analysis of a desiccant wheel. International congress on heating, cooling and buildings, Lisbon–Portugal, October 2008
Zhai C, Archer DH, Fischer JC (2008) Performance modeling of desiccant wheel (1): Model development, Energy Sustainability, Jacksonville, Florida USA, August 2008
Ruivo CR, Costa JJ, Figueiredo AR (2008) On the validity of lumped capacitance approaches for the numerical prediction of heat and mass transfer in desiccant air flow systems. Int J Therm Sci 47:282–292
Chung JD, Lee DY (2009) Effect of desiccant isotherm on the performance of desiccant wheel. Int J Refrig 32:722–726
Antonellis SD, Joppolo CM, Molinaroli L (2010) Simulation, performance analysis and optimization of desiccant wheels. Energy Build 42:1386–1393
Ge TS, Ziegler F, Wang RZ (2010) A mathematical model for predicting the performance of a compound desiccant wheel (a model of compound desiccant wheel). Appl Therm Eng 30:1005–1015
Narayanan R, Saman WY, White SD, Goldsworthy M (2011) Comparative study of different desiccant wheel designs. Appl Therm Eng 31:1613–1620
Yadav A, Bajpai VK (2012) Design parameter analysis to improve the performance of desiccant wheel using a mathematical model. Chem Eng Technol 35(9):1617–1625 Wiley Publications
Yadav A and Bajpai VK Analysis of various designs of a desiccant wheel for improving the performance using a mathematical model. J Renew Sustain Energy 5(2). American Institute of Physics
Charoensupaya D, Worek WM (1989) Dynamic sorption of porous adsorbents-comparison of experimental results with numerical predictions. Int Commun Heat Mass Transf 16:681–691
Kodama A (1995) PhD. Thesis, kumamoto University Japan
Pesaran AA, Mills AF (1987) Moisture transport in silica gel bed packed beds-1. Theoret Study Int J Heat Mass Transf 30(6):1037–1049
Sutherland W (1893) The viscosity of gases and molecular force. Philos Mag S5(36):507–531
Acknowledgments
The evacuated tube solar air collector in this project was provided by Mr. H.S. Chadha (M.D), Sunson Energy Devices (P) LTD, New Delhi, India. The authors acknowledge the support from Mr. Deepak Pahwa (Chairman), Desiccant Rotors International (DRI), India.
Author information
Authors and Affiliations
Corresponding author
Rights and permissions
Open Access This article is distributed under the terms of the Creative Commons Attribution License which permits any use, distribution, and reproduction in any medium, provided the original author(s) and the source are credited.
About this article
Cite this article
Yadav, A., Yadav, L. Comparative performance of desiccant wheel with effective and ordinary regeneration sector using mathematical model. Heat Mass Transfer 50, 1465–1478 (2014). https://doi.org/10.1007/s00231-014-1349-6
Received:
Accepted:
Published:
Issue Date:
DOI: https://doi.org/10.1007/s00231-014-1349-6