Introduction

Electrical energy is the most fascinating form of energy resulting from the flow of electric charge and can be used easily in various applications and needs, especially for residential, commercial, and industrial applications [1]. Electrical energy can be produced from various sources, either renewable or non-renewable. The main problem facing energy in general is the storage of energy. Heating consumes approximately one-third of the electrical energy used in residential applications [2].

Thermoelectric generators (TEGs) are thought of as direct, small solid-state energy conversion devices that can be used to directly convert waste heat into electricity as a heat recovery system [3]. The Seebeck effect is the basis of the electricity generated from the TEGs. When a heat flux passes through a junction of two completely different conductors or semiconductors, an electrical current will be generated. The Seebeck coefficient is defined as the voltage generated per 1 K difference in temperature [4]. Ignoring the hydraulics-thermal behavior associated, one-dimensional heat conduction theory is used to analyze the performance of TEGs when installed on a heat exchanger, especially in solar cell/module applications [5].

HVAC is the operation of adding or eliminating heat to obtain a more comfortable environment, and this could be achieved by using “air conditioners” through negative cooling or ventilation cooling technologies that provide heating, ventilation, and air conditioning (HVAC) [6]. In 2018, it was found that 20% of rated energy use in buildings was consumed by air conditioners, and the value was estimated to increase by three times by 2050. To that end, the United Nations encourages the development of new modified sustainable heating and cooling strategies and technologies to address global climatic changes and increased energy demand [7].

There is a wide range of equipment that could be used in thermal processes and systems where heat is dissipated into the environment as waste energy. In such devices, like heat exchangers, etc., TEGs may be installed to recover the waste energy and convert it into electricity, improving the efficiency of the thermal systems [8]. Air and water heating or cooling systems are the types that will be used to decrease or eliminate environmental impacts and can be used instead of one-time heating or cooling systems to reduce water usage or thermal water pollution [9].

Using renewable energy has become of great interest in thermal system applications, especially in heating, cooling, and power generation. But these technologies suffer from specific disadvantages related to the thermal efficiency or coefficient of performance of the system due to heat lost from the system during operation. To overcome these problems and to improve their performance, energy recovery technologies like TEGs are an excellent choice [10].

A hybrid photovoltaic-thermal water heating system was developed by Chow et al. for domestic applications. The thermal efficiency of the hybrid system was found to be in the range of 37.6–48.65% while the electrical efficiency was in the range of 10.3–12.3% [11, 12].

To improve the thermal efficiency of the solar system, a new design system that combines the traditional solar cell made of silicon with TEGs and a heat collector was developed. The integrated system shows a good improvement in efficiency compared to the PV system alone [13]. For mini and micro power applications, a solar TEG was proposed by using inexpensive solar concentrators like evacuated tube collectors and parabolic or compound parabolic solar concentrators. The incorporated system was studied and showed a noticeable improvement in performance [14,15,16,17].

Recently, because of their flexibility, reliability, small size and weight, and modular scalability, TEGs are being used in a wide range of applications as heat recovery systems. In sensors as low-power supply applications [18, 19], medium-power supply systems include batteries [20], automotive heat systems [21, 22], stoves [23, 24], chiller systems [25], and combined TPV [26] or PV [27] systems. In heavy industries [28], geothermal systems [29, 30] serve as high-power supply applications.

The electric current, voltage, and hence power generated by the TEG depend mainly on the temperature difference across the TEG. The system is considered as a thermally steady-state model with a voltage source integrated in series with an internal resistance [31, 32]. To enhance the generated power by the TEG for a constant temperature difference across it, the TEG load’s impedance should be equal to its internal resistance [33].

This article provides a study of the thermal and electrical performance of a TEG system augmented with an evacuated tube solar water heater using a radiator heat exchanger by means of an Engineering Equation Solver (EES). Additionally, the effects of thermal and electrical contacts as well as free and forced convective heat transfer were considered. To characterize the TEG module’s overall performance, outcomes are presented in figures for numerous essential variables, consisting of temperature, power generated, and TEG efficiencies. The variation of the heat dissipated from the heat exchanger with hot water temperatures is shown with and without installing TEGs.

Method

With the evacuated tube solar heating system, 50 TEG modules were installed around the heat exchanger, the main heat supply for space heating. As shown in Fig. 1, the hot side of the TEG is contacted perfectly on the outer surface of the heat exchanger while the cold one is in direct contact with the surrounding space air to be heated.

Fig. 1
figure 1

TEG module-heat exchanger connection

When the hot water from the solar collector flows through the heat exchanger, conduction heat transfers to the hot side of the TEGs, and the heat will be rejected from the cold side into the room space air as a supply heating source. As shown in Fig. 2, heat is convected from the water to the inside surface of the heat exchanger, then conducted through its wall and within the TEGs before being rejected out to the space air to be warmed. The hot and cold sides of the hybrid system are presented in Fig. 3.

Fig. 2
figure 2

Solar heat exchanger for space heating hybridized with TEG modules

Fig. 3
figure 3

Hot and cold sides of the hybrid system

It is well known that TEG is composed of p-type (positive charge) and n-type (negative charge) composites connected by a conductor. Since there is a temperature difference between the two sides of the TEG surfaces, electrical energy will be generated depending on the value of the temperature difference as shown in Fig. 4. The main variables that the amount of energy generated by the TEG will be affected by are the hot water temperature and circulation ratio, the space room temperature surrounding the TEG, and the space air speed when force convection occurs using fans. For the TEG to operate properly, there should be some differences in the physical properties (electrical resistance, thermal conductivity, Seebeck effect) of the two semiconducting pellets. The main specifications of the heat exchanger and the input parameters of the TEG modules are summarized in Tables 1 and 2, respectively.

Fig. 4
figure 4

Thermoelectric P/N module

Table 1 Heat exchanger specifications
Table 2 TEG module input parameters at standard conditions [1]

Mathematical model and energy balance

The mathematical model of the hybrid system under investigation was made based on several assumptions which can be summarized as follows:

  • Steady-state, one-dimensional heat transfer.

  • The outer surface area of the heat exchanger is a uniform temperature.

  • Thermal and contact resistance are negligible.

  • Neglecting the effect of temperature on TEG properties,

  • Thermal and electrical contact resistances are negligible.

  • TEG connections are considered in series thermally and in parallel electrically.

The energy balance for the heat exchanger with TEG module shown in Fig. 5 is given by Eq. (1). Note that the energy generated is negligible.

$$ {\dot{E}}_{1, in}-{\dot{E}}_{1, out}=0 $$
(1)
Fig. 5
figure 5

Heat exchanger with TEG module

where \( {\dot{E}}_{1, in} \), \( {\dot{E}}_{1, out} \) are the rate of energy in and out of the between hot water and TEG module, respectively.

The rate of energy in\( {\dot{E}}_{1, in} \) is the rate of heat transfer from the hot water (Qh) into the TEG while the hot side heat absorption is the rate of energy out (Qh,TEG). Solar heated water convective thermal resistance, Rconv., w, is given by Eq. (2):

$$ {R}_{conc,w}=\raisebox{1ex}{$1$}\!\left/ \!\raisebox{-1ex}{${h}_w$}\right.\bullet {A}_{TEG} $$
(2)

where hw is coefficient of convective heat transfer of water (W m−2 K−1) which can be given by ref. [34] as:

$$ {h}_w=N{u}_w\bullet \frac{K_w}{D_H} $$
(3)

where Kw is the hot water thermal conductivity (W m−1 K−1) and DH represent the hydraulic diameter of the heat exchanger which can be defined in terms of cross-sectional area, Ac, and wetted perimeter of the heat exchanger as:

$$ {D}_h=4\frac{A_c}{P_w} $$
(4)

where Ac is the multiplication of the width by height of the heat exchanger (Ac = Wex × hex). Nuwis the Nusselt number of the water which can be given in terms of Reynold’s number (Rew) and Prandtl number (Prw) of the water as [35]

$$ N{u}_w=0.023\ast {{\mathit{\operatorname{Re}}}_w}^{\left(\frac{4}{5}\right)}\ast {{\mathit{\Pr}}_w}^{0.3} $$
(5)

In terms of water velocity, Vw (m/s); density, ρw (kg m−3); and dynamic viscosity, μw (N m−2 s−1), Reynold’s number of the water could be given by:

$$ {\mathit{\operatorname{Re}}}_w={\rho}_w\ast {V}_w\ast \frac{D_h}{\mu_w} $$
(6)

Also, Prandtl number of the water could be given by:

$$ {\mathit{\Pr}}_w=\frac{\mu_w\bullet {Cp}_w}{K_w} $$
(7)

The conduction resistance between heat exchanger surface wall and the internal surface of TEG [R cond (K/W)] may be given in terms of heat exchanger thickness, t (m), heat exchanger thermal conductivity, K (W m−1 K−1), and TEG area, ATEG (m2) by [34].

$$ {R}_{cond}=\frac{t}{K\ast {A}_{TEG}} $$
(8)

Following Eqs. (1) to (8), the rate of heat flux to the TEG from the hot water could be evaluated in terms of hot water temperature, Tw, and TEG hot side temperature, Th, as

$$ {Q}_h=\frac{\left({T}_w-{T}_h\right)}{R_{conv,w}+{R}_{cond,w}} $$
(9)

Similarly, the energy balance equation is applied between the TEG module and the surrounding air with neglecting energy generation (see Fig. 5):

$$ {\dot{E}}_{2, in}-{\dot{E}}_{2, out}=0 $$
(10)

\( {\dot{E}}_{2, in} \), \( {\dot{E}}_{2, out} \) are, respectively, the rate of energy in and out between TEG module and surrounding air to be heated.

Heat transferred to the surrounding air (Qc) occurs in combined convection and radiation modes (see Fig. 2). Thus, convective (natural and forced) and radiative heat transfer coefficients [hc, a, hr, a (W/m K)] between the TEG module and the surrounding air are the most effective. According to Ref. [34], the air convective heat transfer coefficient (hc, a) could be expressed in terms of Nusselt number (Nua) as:

$$ {h}_{c,a}={Nu}_a\bullet \frac{K_a}{L_r} $$
(11)

The Nusselt number is related to the Rayleigh number of air (Ra) as Nua = Ra1/3 and Rayleigh number of air is well known in heat transfer and given in terms of volumetric thermal expansion coefficient of air βa (K−1) and thermal diffusivity of air αa (m2/s) by:

$$ Ra=\frac{g\ast {\beta}_a\ast {\rho}_a\ast \left({T}_c-{T}_a\right)\ast {l_r}^3}{\alpha_a\ast {\mu}_a} $$
(12)

The volumetric thermal expansion coefficient of air is a function of the average value of water and the surrounding air temperatures Tf (K) while the value of thermal diffusivity of air αa depends on the thermal conductivity of air Ka (W/m K), air density ρa (Kg/m3), and the specific heat of air Cpa (kJ/kg .K)

$$ {\alpha}_a=\frac{K_a}{\rho_a\ast {Cp}_a} $$
(13)

The heat dissipated from the TEG to the surroundings by radiation with a normalized coefficient hr,a (W/m K) which can be written in terms of TEG emissivity εTEG, Stephan Boltzmann constant σ (W m−2 K−4), and surrounding air temperature Tsurr. (K) as:

$$ {h}_{r,a}={\varepsilon}_{TEG}\ast \sigma \ast \left({T}_c+{T}_{surr}\right)\ast \left({T_c}^2+{T_{surr}}^2\right) $$
(14)

Now, the rate of heat transfer from the cold side of the TEG (Qc) to the ambient air can be given as:

$$ {Q}_c={h}_a\ast {A}_{TEG}\ast \left({T}_c-{T}_a\right) $$
(15)

Respectively, the electric and thermal resistances [Re (Ohm), Rth (K/W)] and thermal conductivity (K) of each TEG module are given in terms of positive and negative electric conductivity (σp = 1/ρp, σn = 1/ρn) as:

$$ R=n\bullet \left[{\left({\sigma}_p\bullet \frac{A_p}{L_p}\right)}^{-1}+{\left({\sigma}_N\bullet \frac{A_N}{L_N}\right)}^{-1}\right] $$
(16)
$$ K=n\bullet \left[\left({\lambda}_p\bullet \frac{A_p}{L_p}\right)+\left({\lambda}_N\bullet \frac{A_N}{L_N}\right)\right] $$
(17)

The rate of heat absorbed by the TEG’s hot side from solar heated water (Qh) and the rate of heat rejected to the surrounding air by the TEG’s cold side (Qc) are given by:

$$ {Q}_h=n\bullet \overline{\alpha}{T}_c\bullet I+K\bullet \left({T}_h-{T}_c\right)-\frac{1}{2}{I}^2R $$
(18)
$$ {Q}_c=n\bullet \overline{\alpha}{T}_c\bullet I+K\bullet \left({T}_h-{T}_c\right)-\frac{1}{2}{I}^2R $$
(19)

The power produced by TEG:

$$ P={I}^2{R}_l $$
(20)

The power generated by the TEG is considered as the difference between the hot and cold heat transfer rates and is given by:

$$ P={Q}_h-{Q}_c $$
(21)

Manipulating Eqs. (9) through (21) provides two non-linear equations with Th and Tc as unknowns. EES was used to solve these equations and the results are presented.

Finally, the overall efficiency of the thermo-electric module (TEM) can be given as:

$$ \eta =\frac{P}{Q_h}\ast 100\% $$
(22)

Heat exchanger specifications and TEG module input parameters used in this study are presented in Tables 1 and 2, respectively.

Results and discussion

Figure 6 shows the effect of the surrounding temperature on the TEG generated power for different temperatures of hot water flowing in the heat exchanger from the solar field. The heat transfer to the surrounding air by natural convection and the temperature inversely affect the generated power. The explanation for this behavior is that any increase in the surrounding temperature will cause a decrease in the temperature difference and hence decrease the heat flux across the TEG.

Fig. 6
figure 6

Variation of power produced from TEGs with surrounding air temperature for different hot water temperatures and fixed hot water flow rate of 3 kg/s

Increasing the velocity of the hot water shows an increase in the power generated by the TEG since any increase in the velocity will enhance the heat absorption by the hot side of the TEGs due to the increase in convective heat transfer coefficient of water with velocity, and this is clearly shown in Fig. 7. The figure also shows a slight effect of hot water velocity on power generated as compared to the surrounding temperature effect because the flow velocity values were low, hence the low Reynolds number and a slight increase in the hot water heat transfer coefficient.

Fig. 7
figure 7

Variation of power produced from TEGs with surrounding air temperature for different hot water flow velocities under the condition of natural convection at hot water temperature of 85 °C

It is clearly obvious that the amount of electrical power generated is small in value due to the low TEG efficiencies. Despite the low TEG efficiencies, it may be possible to generate reasonable amounts of power by increasing the heat exchanger surface area and the number of TEG modules used, especially when large amounts of waste or renewable energy are available. At least, these amounts of energy can operate wireless sensing and control devices in power plants, buildings, and so on.

Figure 8 shows the effect of hot water temperature on the power generated by the TEG for different velocities of hot water flowing in the heat exchanger from the solar field. The results presented show that the TEGs generate more power as the hot water temperature increases due to the increase in heat flux from the hot water side and the TEG hot side, resulting in a larger temperature difference across the TEGs.

Fig. 8
figure 8

Effect of hot water temperature on the TEGs’ generated power for different hot water flow velocities under the condition of natural convection at a surrounding temperature of 20 °C

It is well known that enhancing the heat transfer will improve the electric power generated from the TEGs. Figure 9 shows that natural convection produces less power than that in the case of forced convection, and this is due to the lower heat transfer coefficient in the case of natural convection as compared to forced convection. Also, in the case of forced convection, the velocity of space air surrounding the cold side of the TEGs directly affects the rate of heat transfer and enhances the power generated. The coefficient of convective heat transfer increases with the speed of air, which causes the heat transfer exchanged through the heat exchanger. According to ISO7933, the recommended value of the moving air heat transfer coefficient was taken as 6 (W/m °C) at 0.5 m/s air speed [36]. With natural convection, the heat transfer rate will be lower.

Fig. 9
figure 9

Effect of surrounding temperature on the power produced from TEGs’ forced convection (V = 0.65 m/s) and natural convection at a hot water temperature of 85 °C

When investigating the effect of hot water temperature on TEG efficiency for different surrounding conditions, it was found that the efficiency was found to increase with increasing hot water temperature and decreasing surrounding temperatures due to the increase in temperature differences across the TEGs as mentioned earlier. The effect of combined hot water and surrounding temperatures is presented in Fig. 10.

Fig. 10
figure 10

Variation of TEG efficiency with hot water temperature for different surrounding temperatures

The effect of combined surrounding temperature and hot water flow velocity on TEG efficiency is shown in Fig. 11. The results indicate that the efficiency decreases as the surrounding temperature increases due to the decrease in heat dissipated to the TEGs’ cold side and, hence, decreases the temperature difference across the TEGs, which lowers the electric power generated.

Fig. 11
figure 11

Effect of the surrounding temperature on TEG efficiency for different hot water temperatures

Figure 12 compares the heat dissipated to the surroundings when the heat exchanger is operated with or without TEGs installed on the heat transfer surface area. The results show a negligible difference between the two cases.

Fig. 12
figure 12

Variation of the heat dissipated from the heat exchanger with hot water temperatures with and without TEGs

Model validation

To validate the results obtained in the present investigation, a published study by Al-Widyan et al. [1] was selected. Al-Widyan et al. investigate a heating radiator with TEGs installed on both sides (cold and hot). The published study’s input data was applied to the current investigation model. Figures 13, 14, and 15 show the model validation by comparing the effect of the surrounding temperature on the power produced from TEGs for hot water temperatures of 345 K with a fixed water mass flow rate of 3 kg/s for both models, the variation of the power produced by one TEG’s module with the temperature difference across the heat exchanger, and the variation of the TEG’s efficiency with the temperature difference across the heat exchanger. The present model shows high agreement with the published (true) model, with an error of less than 6%.

Fig. 13
figure 13

Variation of power produced from TEGs with surrounding temperature for hot water temperatures of 345 K with fixed water flow rate of 3 kg/s (model validation)

Fig. 14
figure 14

Comparing the effect of the temperature difference across the heat exchanger on the power produced by one TEG’s module with ref. [1]

Fig. 15
figure 15

Variation of the TEG’s efficiency with temperature difference across the heat exchanger and comparison of the results with ref. [1]

Conclusion

The present investigation proposes the installation of TEGs at the outer surface of the heat exchanger in which hot water is heated by an evacuated tube solar collector and flows through it to heat the surrounding space. This study may not be the first one that addresses solar space heating systems, but it is one of the first that professes the concept of augmenting TEGs for space heating systems. The results of the present work clearly indicate that such kinds of TEG applications hold a promising potential for solar and other renewable sources of energy as well as recovering waste energy.

In this study, the effect of various parameters on TEG efficiency and power generation was examined. The surrounding air temperature and the hot water temperature coming from the evacuated solar collector represent the most significant parameters affecting the performance of the TEGs. Besides heating the space, the heat exchanger with TEGs installed on the outer surface produces a maximum electric power of 1.03 W at a temperature difference across the TEG of 60 °C. The optimum air velocity that gives the optimum power generated was found to be 0.5 m/s. Furthermore, a decrease in the surrounding temperature by 5 °C increases the power produced by about 17.47%, while it increases by about 11% as the hot water temperature increases by 5 °C.