1 Introduction

Grid connection of large-scale intermittent power sources is an important method for power system restructuring in China. Energy storage systems effectively suppress the fluctuation of intermittent power sources and are therefore an important method to promote the greater use of large-scale intermittent power sources.

However, the high cost of battery energy storage systems is one of negative factors for their commercial use. For example, the cost of batteries was about 20% to 30% of the total cost of the wind and solar storage integrated demonstration project in Zhangbei, China [1], although the prices have already dropped a lot since building Zhangbei project. It is crucial to optimize the type and capacity of the batteries to reduce the cost of the energy storage systems.

Currently, the economics of the power sources in an active distribution network are directly determined by the energy storage systems. However, it is difficult to evaluate the energy storage systems used in an active distribution network. The EnergyPLAN software can analyze and compare the performance of different energy systems, which are based on fossil fuels, nuclear fuels and renewable energy [2], with one-hour resolution. When the characterization of a reference energy system is completed by the EnergyPLAN software, another energy system can be quickly and easily analyzed through the model, which keeps continuity and consistency. Presently, the software has been used to simulate a 100% renewable energy system for Mljet island of Croatia [3, 4] and for the entire country of Denmark [5], a large-scale wind power network [6, 7], the optimal combination of renewable energy sources [8], excess power management [9], vehicle-to-grid (V2G) and other technologies to balance a wind power network [10], the potential role of fuel cells and batteries [11] and the role of electricity storage [12].

Therefore, this paper considers the technical and economic performance of the lithium ion batteries, sodium-sulphur batteries and vanadium redox flow batteries in active distribution networks using the EnergyPLAN software. These kinds of batteries were simulated in specific configurations with grid-connected solar and wind generation, according to the technical and economic characteristic of the energy sources and energy storage devices, and optimal combinations were explored.

2 Active distribution networks and energy systems

2.1 Characteristics of active distribution networks

The definition of active distribution networks has been proposed by the CIGRE C6.11 group, and its technical content can be defined as: “active distribution networks have systems in place to control a combination of distributed energy resources (DERs), defined as generators, loads and storage. Distribution system operators (DSOs) have the possibility of managing the electricity flows using a flexible network topology. DERs take some degree of responsibility for system support, which will depend on a suitable regulatory environment and connection agreement” [13]. Therefore, compared with a passive distribution networks, an active distribution network is a new form of distribution network, with a specific technical goal. It can achieve both energy efficiency and economic benefits.

2.2 Energy systems based on active distribution networks

The active and reactive power of battery energy storage can be controlled through four-quadrant power conversion systems, and used for many demand-side power management applications. For example, with a suitable control system, battery energy storage can reduce the difference between on-peak and off-peak demand, and improve power quality to increase the efficiency of electrical equipment which will reduce their energy consumption. Battery energy storage can also increase the application of renewable energy by reducing the effects of intermittency on the distribution network, particularly through active voltage regulation. Responsive energy storage systems, such as batteries, can also improve the system stability, by providing ancillary services to help maintain the frequency of the system and compensate load fluctuations and generator and transmission line outages. Especially, for large-scale intermittent energy networks, energy storage device systems can reduce grid instability caused by intermittent energy output, when controlled to achieve an appropriate dynamic response.

There are many kinds of battery energy storage, which are divided into those most suitable for energy shifting applications and those most suitable for high-power applications, with different price dependence on the energy storage capacity (kWh) and the charge and discharge rate (kW). Currently, large-scale application of batteries is restricted by their price in comparison to the economics of their application areas, in this case the active distribution networks. Li-ion, NaS and VRB are three mainstream batteries in the present market, and they have distinctive features and advantages. Li-ion battery has the good features of high power density and no memory effect; NaS battery can discharge with high output power and large current; VRB is cost-effective for large energy capacity and very long life due to no chemical change and electrolyte. This paper evaluates the economics of the three energy storage systems in typical operating conditions and configurations of active distribution networks.

3 Understanding typical operating conditions

3.1 Wind resources in Chongming Island

Chongming Island in Shanghai, China is assumed to represent the typical condition of intermittent wind power since it is rich in wind resources.

The annual average wind power density of this region at 50 m high is 339.1 W/m2, which is much higher than 150 W/m2, the level normally required for wind energy to be extracted efficiently. In the island, the total capacity of wind power that may be installed is up to 1500 MW, and if the average utilization time of wind is 2000 hours per year (or 23% capacity factor), the achievable energy generation is 3 TWh per year or more, which would be equivalent to the largest wind farms in the world. Cost-effective development of wind power will occur where the average utilization time of wind exceeds 2000 hours per year, so that the generated electricity is greater than or equal to 1.2 GWh for a wind turbine with 600 kW capacity. When the average utilization time reaches 2500 hours per year, it may be economic to develop wind farms rather than individual turbine installations. In Chongming Island, the annual duration of effective wind is 8418 hours and the average utilization time is 2208 hours per year. In addition, the peak wind speed and peak wind power density both coincide with the peak period of residential electric load each day. According to studies, it is advantageous to mitigate the peak electric load though the use of wind power at 18:00 of August, coinciding with the strongest wind generation [14].

3.2 Energy mix in Chongming Island

According to the comprehensive analysis of the statistical data in recent years, in this paper the region’s peak load is 364 MW, and the annual consumption and losses are about 1570 GWh, where the power generation is 1238 GWh [15]. The difference of 332 GWh is imported using the power transmission capacity of 250 MW from Jiangsu power grid, supplying about 20.5% of the total annual electricity consumption. The total installed power plant capacity is 204.5 MW [16], of which the coal-fired power plant is 89.9%, wind farms are 9.5%, and photovoltaic arrays are only 0.6%. The maximum power capacity is 454.5 MW.

The intermittent energy generation in the island mainly comprises: ① 380 V photovoltaic power plants at some office buildings and other small-scale photovoltaic power generation not connected to the electricity grid; ② a 10 kV photovoltaic power plants with rated capacity of 1.04 MW, and annual generation capacity of 1.05 GWh; ③ a 35 kV wind farm: there are 13 turbines with unit capacity of 1.5 MW, hence total capacity of 19.5 MW.

3.3 Energy system based on an active distribution networks

In 2020, the active distribution network in this region should be completed. According to the goal of eco-island construction (2010–2020) for the island, a gas power plant project was started, located in the south of the Yangtze River at the central region, in order to reduce the energy production and greenhouse gas emissions from the city. The predicted maximum load is set as 1500 MW and the annual electricity consumption is set as 3500 GWh in 2020 according to the moderate prediction scheme of this region [17].

In order to reduce CO2 emissions, the proportion of wind energy is gradually increased from 0% to 30%, 50%, 70%, 90% and 100% of electricity consumption. To reach very high proportions of wind energy, the availability of wind power should reach 8760 (8784) hours per (leap) year, and this requirements allows the necessary installed capacity and energy generation of thermal power and wind power under different proportions of wind power, as shown in Table 1.

Table 1 Amount of installed capacity and power generation of thermal power and wind power under different percent of wind power

As shown in Table 1, if the demand for electricity is totally supplied by wind power, wind power capacity must be increased at a greater rate than would be required for thermal power capacity. Although it hardly happens now, the condition 5 is studied as an extreme case.

3.4 CEEP based on an active distribution networks

As shown in Fig. 1, adding a high proportion of wind power creates a problem of energy systems. Because of the imbalance between the demand and intermittent supply of electricity, wind power is unable to completely supply the grid demand due to instability of wind power, resulting in CEEP of energy systems represented by curtailed wind. When there is excess capacity, many turbines are turned off, and some units of the coal-based energy system must run continuously to ensure the stability of power grid. In this case, compared with refurbished plant and improved energy efficiency, enhancing the ability to coordinate the intermittent wind energy is a better method to reduce greenhouse gas emissions and increase economic benefit, which could be achieved by applying energy storage technologies in an active distribution network.

Fig. 1
figure 1

CEEP with increasing of installed wind capacity when there is no battery energy storage system

4 Economic benefits of wind-battery power storage system

Considering the energy storage system as the principle balancing mechanism of active distribution networks, its capacity and configuration have been researched to make the wind power output smooth and efficiently matched to the load.

4.1 Excess capacity (CEEP) of wind-battery power storage system

Fig. 2 shows the comparative effect on CEEP between different levels of wind power and storage capacity in energy systems composed of thermal power and wind power. The installed capacity of wind power is 505 MW, 845 MW, 1180 MW, and 1688 MW, and the total installed capacity of thermal power is shown in Table 1. A reference configuration with no storage is also included.

Fig. 2
figure 2

Impacts on CEEP between wind power and storage capacity

It can be seen that when the installed capacity of wind power was 505 MW, 845 MW and 1180 MW, the value of CEEP significantly improves even when the capacity ratio was 5:1 for wind:battery, while as the proportion of the energy storage capacity increased, the value of CEEP gradually decreased, which indicates the effectiveness of the energy storage system in reducing excess generating capacity and keeping the power grid stable. For different storage systems, the order of decreasing value of CEEP was lithium-ion batteries, sodium sulfur batteries, and vanadium redox flow batteries.

When the wind power capacity is 505 MW, the values of CEEP with different types of energy storage system are all close to zero. There is no CEEP after meeting the local load demand for electricity due to the small installed capacity of wind power, and energy storage systems are not required for economic optimization. When the wind power capacity is 1688 MW, a large number of wind energy cannot be absorbed by the power grid, and this provides an economic incentive to use energy storage systems.

For the sodium-sulfur battery, as the ratio between wind power and batteries changes from 5:1 to 2:1, the curve of CEEP shows a slow decreasing tendency. As the ratio changes from 2:1 to 1:1, the value of CEEP drops by the largest amount, and when the ratio of wind power and batteries reaches to 1:1, the value of CEEP is reduced by more than half. Therefore, the ratio of wind power and sodium sulfur battery energy system should be less than 2:1 in order to efficiently reduce the CEEP value. But for the lithium ion battery, the curve of CEEP also shows a slow decreasing tendency as the ratio of wind power and batteries changes from 5:1 to 3:1. Due to the increased energy storage capacity, the value of CEEP drops by the largest margin as the ratio of wind power and batteries changes from 2.5:1 to 1:1, and when the ratio reaches 1:1, the value of CEEP decreases by nearly 70%. Therefore, the ratio of wind power and lithium ion battery energy system should be less than 2.5:1 to 2:1. It is the same to the vanadium redox flow battery.

4.2 Cost of wind-battery power storage system

The impact of wind power installed capacity and energy storage capacity on the total annual cost of the energy system (total annual costs TAC) is shown in Fig. 3. Obviously, the overall cost of the system increases due to the battery storage system, and is much higher than the total cost without energy storage system.

Fig. 3
figure 3

Impact of wind power installed capacity and energy storage capacity for total annual cost of the energy system TAC

Through an analysis of economic viability, when the ratio of wind power and sodium sulfur battery energy system reaches 2.5:1, the total annual cost is gradually increased. Meanwhile, the cost of lithium ion battery and vanadium redox flow battery increase sharply, and will not be commercially viable, when the ratio of wind power and battery is greater than 2:1–1.5:1.

5 Conclusions

The CEEP and the total annual cost of an example energy storage system were calculated and analyzed for three kinds of battery energy storage system: lithium ion batteries, sodium sulfur batteries, and vanadium redox flow batteries. Proportions of wind energy between 0% and 100% were considered, the remainder of load being met by thermal generation, thus an energy system comprising 100% intermittent energy was included as an extreme case. The results show that the optimum ratio of wind power and battery is 2.5:1–2:1 for the three types of battery under certain wind capacity. The lithium ion battery has the strongest ability to reduce the CEEP, resulting in energy savings and emission reductions, but the total cost is much higher than the other two, which limits its large-scale application. The comprehensive performance of the sodium sulfur battery is best, due to its longer life, and its stronger economic and environmental benefits. Our work will continue to research complex energy storage systems including an economic benefits model, their applications, and their optimal power and capacity to meet the requirements of active distribution networks.