Full-scale fire tests and the development of design criteria for sprinkler protection of mobile shelving units

  • Published:
Fire Technology Aims and scope Submit manuscript

Abstract

In early 1991, a new sprinkler system was planned for the existing National Archives/National Library of Canada building in Ottawa. A major challenge in the design and installation of the sprinkler systems was to protect mobile compact shelving units located in the three levels below grade. Storage of documents in these shelving units is typically within 178 mm of the concrete slab ceiling. The minimum clearance permitted by the sprinkler system installation standard is 457 mm from the sprinkler deflector to the top of the storage. To conform with the sprinkler design standard, the top level or levels of storage would have had to be removed and additional storage space acquired. Because of the annual cost of this additional storage, an investigation was begun to determine feasible alternatives that would permit a reduction in clearances between sprinklers and storage, while maintaining an acceptable level of fire safety. This paper describes the series of five full-scale fire tests that were conducted to assess various fire protection options. Based on these tests, design criteria were developed for a sprinkler system using quick response horizontal sidewall sprinklers to protect the mobile shelving units. An overview of this technically based fire protection system for use in protecting shelving units with reduced clearance is also presented.

This is a preview of subscription content, log in via an institution to check access.

Access this article

Price excludes VAT (USA)
Tax calculation will be finalised during checkout.

Instant access to the full article PDF.

Similar content being viewed by others

References

  1. NFPA 13,Standard for the Installation of Sprinkler Systems, National Fire Protection Association, Quincy, Mass., 1989.

    Google Scholar 

  2. National Building Code of Canada, National Research Council of Canada, Ottawa, Canada, 1990.

  3. Chicarello, P.J., Troup, J.M., and Dean, R.K.,Fire Tests for Mobile Storage Systems for Archival Storage, Technical Report JJ. 3A2Nr.RR, Factory Mutual Research Corporation, Norwood, Mass., 1978.

    Google Scholar 

  4. O'Neill, J., private communication.

  5. Nelson, H.E.,FPETOOL: Fire Protection Engineering Tools for Hazard Assessment, NBSTIR 90-4380, National Institute of Standards and Technology, Gaithersburg, Md., 1990.

    Google Scholar 

Download references

Author information

Authors and Affiliations

Authors

Rights and permissions

Reprints and permissions

About this article

Cite this article

Lougheed, G.D., Mawhinney, J.R. & O'Neill, J. Full-scale fire tests and the development of design criteria for sprinkler protection of mobile shelving units. Fire Technol 30, 98–133 (1994). https://doi.org/10.1007/BF01040992

Download citation

  • Issue Date:

  • DOI: https://doi.org/10.1007/BF01040992

Keywords

Navigation