1 Introduction

With rapid urbanization and continuous improvement of construction techniques, a variety of high-rise buildings with different layouts have emerged in large numbers and resulting environmental problems of outdoor wind patterns have become increasingly prominent (He et al., 1997; Murakami, 1997; Yoshie et al., 2007). For example, high wind velocity in narrow channels between high-rise buildings and increased wind velocity can make pedestrians uncomfortable, disturb their outdoor activities or even expose them to potential risks, such as walking with difficulty and being blown over by the wind (Blocken et al., 2008). Alternatively, improper building layouts or building size may contribute to the formation of a dead air eddy zone between the buildings, a stagnant area with poor circulation (Ying et al., 2013). Therefore, it is necessary to explore how wind conditions are created to avoid adverse wind environments.

The main approaches to predict the wind environment around buildings are field measurements, wind tunnel tests, and numerical simulation (Stathopoulos and Baskaran, 1996; Chang and Meroney, 2003). At present, there are still some errors in predicting the subtle pressures of building surfaces using numerical simulation, but the overall wind environment has been simulated with high accuracy and practical value (Stathopoulos and Baskaran, 1996; Cochran and Irwin, 1999). Stathopoulos and Baskaran (1996) applied numerical simulation to a group of seven rectangular and parallel buildings and found that the resulting wind velocity distribution around the buildings was in good agreement with wind tunnel test results. Chang and Meroney (2003) applied Fluent (a computer software program) and four different k-ε models (turbulent models) to calculate the vortex condition within a street canyon where high-rise residential buildings were arranged in parallel, analyzing the influence of the width-height ratio of the building. Stathopoulos (1997) studied the influence of variation in the height of buildings on wind velocity around the streets using a wind tunnel test. Hu and Wang (2005) used Phoenics (a computer software program) to carry out numerical simulation. The results showed that when a central building and the surrounding buildings were of equal height, the calculated and experimental values agreed with each other, while they differed if the heights were unequal. Taking the impact of different spacing into account, Li (2001) used Fluent to simulate three models based on existing high-rise buildings. In general, recent studies have focused on a single or simple layout of buildings and there has been no systematic analysis or assessment of the impact of a series of layout changes on the wind environment.

Oke and his colleagues, who have studied the relevant urban form and urban thermal environment, presented the effects of residential area patterns on outdoor air temperature (Oke, 1973). Arthur-Hartranft et al. (2003) pointed out that the pattern of significant land use would affect microclimate changes in a city. Further, Voogt and Oke (2003) identified the mechanism of impact of the outdoor landscape on urban climate. Atkinson (2003) discussed a computer model of heat island effects on urban areas of 20 km2. Overall, research has focused on larger urban areas and has not considered thermal environment issues in smaller scale residential areas. This should be of great concern as residential areas constitute the major part of urban construction in a developing city.

On the other hand, Coceal et al. (2006; 2007) investigated small building layouts, taking four homogeneous building cubes with a staggered layout, to develop a computer model (building density λ=0.25). The distribution of surrounding air and eddies was observed. Coceal et al. (2006) expanded the layout of the building cubes to staggered, aligned, and square arrays (Fig. 1), and compared the air flow for each layout. Claus et al. (2012) focused on a model where all buildings were of the same height. They recorded the differences in the airflow field when changing the initial wind direction in the model. Ying et al. (2013) analyzed the wind environment around a group of six square high-rise buildings. Their studies were confined to layouts with a fixed height and did not examine the relationship between a series of floor area ratios and building heights. However, designers such as architects need such studies during the planning stage of an actual design project.

Fig. 1
figure 1

Plan view of computational domains with staggered (a), aligned (b), and square (c) arrays of dimension 4h×4h×4h (h is the cube height). Reprinted from (Coceal et al., 2006), Copyright 2006, with permission from Springer Science+Business Media

In this study, a computational fluid dynamics (CFD) model developed and validated by Ying et al. (2013) was used to study the influence of two planning indicators, namely the floor area ratio and building height, in the layout of a residential area on the wind environment. It was developed by Reynolds averaged equations and the renormalization group (RNG) k-ε turbulence model (Ramechecandane and Gravdahl, 2012). By analyzing and comparing the wind speed ratios at the pedestrian level (1.5 m), the relationship between the wind environment condition and the layouts was obtained. This was then used to provide a reference and evaluation indicators for the layout of a residential area.

This study examined the influence of height variation and the distribution density of buildings on wind velocity around buildings using a computational simulation tool. By comparing the size of the area with a comfortable wind speed ratio, the study proposed developing indicators for outdoor wind environments to assist in planning high-rise residential buildings.

2 Research method and simulation model

The building density and floor area ratio are two major building capacity control indicators in a master plan. Planning and management departments control the development intensity and space usage comfort through developing these two indicators. This helps to avoid wasting land by building fewer houses, or reducing comfort because of high building density. The designers will follow the general process of a residential design project since they get the project task. The first step is to calculate the average residential building storeys by dividing the floor area ratio by building density. The height of the building is the average residential building storeys multiplied by the height of typical floor. Then the allowable maximum number of buildings in the site can be determined with the height of buildings. Following these indicators calculated, designers will seek reasonable building cluster layout and the number of the buildings in the site under the dual control of sunshine spacing analysis and fire spacing requirements through the “trial and error” method only.

2.1 Definition of indicators

The building density is a term used in master planning that refers to the construction coverage. The development density of a project is calculated by dividing the base area by the total site area in square meters. It reflects the extent of the land use and building density.

The floor area ratio is calculated by dividing the total floor area by the total site area. It will determine the proportion of the land price in the total housing cost for developers and is directly related to the living comfort of the occupants.

The building height refers to the height of the roof surface layer above the outdoor ground level.

The average residential building storey is the ratio of the total square footage of the residential building to the total base area, which reflects the characteristics of the space, form, and landscape of the residential area.

The fireproof distance is a requirement for fire fighting, security personnel evacuation, and reduction of fire thermal radiation between two adjacent buildings. In consideration of high-rise building fires, the planning and management department requires that the fireproof distance between two adjacent buildings should not be less than 13 m (MOHURD, 2005).

2.2 Assessment method

The research was designed to develop an assessment to assess the effect of the layout on the local wind conditions. The three indicators included in the model are the floor area ratio, building density, and building height. In a typical high-rise residential project in China, the floor area ratio is usually between 2.0 and 4.5. This is because when the floor area ratio is less than 2.0, multi-level buildings will dominate the site. However, if the floor area ratio is larger than 4.5, the buildings would be higher than 100 m (30 floors), resulting in a substantial increase in construction cost. This is unusual for residential development in China. According to China’s construction regulations, buildings with different floor numbers require different fire separation spacing and minimum sunlight intervals. Consequently, buildings with 11, 18, 25, and 30 floors are commonly accepted by designers and planners.

For simplicity and clarity, each layout is coded with the “floor area ratio-number of floors”. For example, the layout 2.0-11f represents a building with a floor area ratio of 2.0, with 11 floors (Table 1).

Table 1 Cases designed and simulated for comparison

2.3 Layout model setting

Using the indicators of floor area ratio and building density, architects calculate the building capacity and list the possible combinations of the project construction quantity and the height of the building (the average number of storeys). A preliminary design is then developed. A typical master plan involves setting buildings along the boundary of the site and developing a concentrated green space in the middle area. Another plan involves arranging the buildings in a uniform pattern and combining the entrance and high-rise buildings in favor of highly efficient land use. In this study, the layout of all the cases was designed following this principle.

Most high-rise buildings residential development projects in China have the same number of storeys and a similar load-bearing structure because variable building storeys would make the architectural design and main load-bearing structures more complex (Chao et al., 2010). Therefore, the simulation cases in this study had the same number of storeys.

Based on statistical data from the Planning Bureau of Hangzhou, China and by considering the effectiveness of the simulation results, the study assumed that the total site area in the model was about 100 000 m2 (350 m×290 m) (Fig. 2). The study did not consider inner streets which do not form part of a planning indicator. As streets will not affect the volume rate and building density, they are also not considered. The buildings were all point-type high-rise buildings and the typical floor area of each building was 1000 m2 (about 31.6 m×31.6 m).

Fig. 2
figure 2

Possible layout cases for floor area ratios from 2.0 to 4.5 and results of sunlight analysis (a)—(f)

According to the planning regulations in Hangzhou, China, the distance between adjacent buildings must meet the fireproof requirements and should not be less than 13 m apart (MOHURD, 2005). Fig. 2 shows the possible layouts of the case study buildings with floor area ratios from 2.0 to 4.5.

The planning and management department has developed an assessment of sunlight distance among buildings to avoid mutual occlusion of sunlight due to the high density and building height, and to allow some natural lighting of the indoor space (MOHURD, 2005). A sunlight analysis was conducted according to Tarch (a computer software program) to simulate the path of the sun. The results indicated that seven of the 20 layouts did not meet the sunlight standard of 2 h of full window sunshine during the day with the lowest annual elevation angle of the sun.

Consequently, after considering all these requirements, Table 2 summarizes 13 possible layouts with different floor area ratios.

Table 2 Thirteen possible layouts with floor area ratios from 2.0 to 4.0

2.4 Boundary conditions

The approaching wind was created from a power-law model to approximate the mean velocity profile:

$$U(z) = {U_{\rm{G}}}{(z/{z_{\rm{G}}})^{0.25}}.$$
(1)

The gradient height zG was assumed to be 400 m and the mean wind velocity UG at the gradient height was 13 m/s. Since the k-ε model was used, the values of k were required to account for the turbulence in the approaching wind. The turbulent kinetic energy k can be calculated if the turbulence intensity at a given height is known. The turbulence intensity was set to 12%–13% at a height of 50 m above the ground, as suggested by Hu and Wang (2005).

The ground at the bottom of the computing domain was simulated by a rough wall, as it was assumed that the model buildings were mounted on a plate with roughness of 0.28 (Janour et al., 2005) in their wind tunnel test. The power-law wall function was applied to resolve the flow field near the walls and the building surfaces. The other boundary conditions, such as the outlet and the upper boundary, were not modified and thus the default settings were used. The boundary conditions applied in the computing domain are summarized in Table 3.

Table 3 Boundary conditions for the computing domain

2.5 Domain size

There are no explicit rules dictating the size of a computing domain. Many researchers determine their domain size by a trial-and-error approach because the domain size influences the computation results, as demonstrated by Baetke et al. (1990). Baskaran and Kashef (1996) suggested that the size of the domain can be a multiple of the characteristic height of the building and that the distance between any edge of the domain and the buildings must be at least five times the H (characteristic height of the building). Following this suggestion, for this study the domain size was 13.8H, 14.6H, and 5H in the longitudinal (x), lateral (y), and vertical (z) directions, respectively.

This study follows research which compared CFD wind field modeling and field measurement data to study wind resources in a highly complex terrain (Jimenez et al., 2014). The comparison showed a good agreement between measured and modelled data that improved the simulation accuracy for long-term estimations. The validated model is modified and applied in this study.

2.6 Evaluation criterion

This study aimed to analyze the typical wind conditions around buildings in the east China monsoon region, where Hangzhou city is located. Although wind in the real environment is in an unstable state with velocity and direction, there is a wind direction in summer or winter which occurs much more frequently than other directions, ignoring the effect of the terrain. Therefore, this analysis was based on the direction of the prevailing winds.

When comparing wind speeds around different layouts in the actual environment, the situation is complicated due to the difference between the initial value of the wind inflow into the layouts in the boundary condition settings and the actual wind velocity. Therefore, the wind speed ratio was introduced so that the impact of the building layout on the wind environment could be assessed (Kubota et al., 2008; Kono et al., 2010). The wind speed ratio is the ratio of wind velocity (scalar velocity) at each point (height=1.5 m) to the wind velocity at the identical height at the inflow boundary. The wind speed ratio equation is

$$R = {{{V_{\rm{s}}}} \over V},$$
(2)

where R is the wind speed ratio, Vs is the velocity of a point, and V is the inflow velocity.

The areas where the wind speed ratios are larger than 2.0 are recognized as strong wind flow areas. In these areas people would feel uncomfortable. On the other hand, the areas where the wind speed ratios are less than 0.5 are recognized as weak wind flow areas (Kubota et al., 2008; Kono et al., 2010). A comfortable wind speed ratio for all the year round is from 0.5 to 2.0, typically taken as about 1.85 (Kubota et al., 2008). This ratio is considered as the main criterion for judging different layouts.

The assessment also compared the cost of different master plan cases. This helps architects to make economical, practical, and acceptable designs for clients who are more concerned about the value of construction.

3 Results and analysis

After wind simulation, the wind speed distribution was plotted for all the 13 layouts. Fig. 3 shows the wind speed distribution of layout 2.0-11f as an example.

Fig. 3
figure 3

Wind velocity distribution in a simulation result (layout 2.0-11f)

By masking areas with uncomfortable wind speed ratios, we could clearly identify the comfort zones of different layouts and make comparisons (Fig. 4).

Fig. 4
figure 4

Areas with a comfortable wind speed ratio between 0.5 and 2.0 (layout 2.0-11f)

Further, using the histogram plot tool in Photoshop CS (a graphic software program), the percentage of the area in the comfort zone can be calculated (Table 4).

Table 4 Proportion of comfort zone in 13 possible layouts

3.1 Analysis of wind simulation results

Due to the high density of buildings, the form of an 11f building layout could not meet the standard sunlight spacing. The simulation result revealed that under the 2.0-11f layout, the proportion of the area in the comfort zone was only about 43%, which was the lowest among all the combinations. It was known that intensive building distribution would cause low wind speed. Therefore, if considering the external wind environment, 11f is not a suitable option for floor levels (Table 4).

During the stage of building layout planning, when the level reaches 18, the lower floor area ratio would normally be associated with a higher comfort area ratio:

The comfort area ratio was 66% when the floor area ratio was 2.0, 61% when the floor area ratio was 2.5, and only 50% when the floor area ratio was raised to 3.0.

For a residential site of development, it is unacceptable to have only half of the outdoor area considered to be within the comfort zone. Hence, during the planning stage of a residential site, if the floor area ratio is specified as 3.0, the architect should avoid the use of 18-level individual buildings in the design.

When the building level was greater than 25, no significant difference was observed when the floor area ratio varied.

When the building level reached 30, the comfort area should rank from high to low: 3.0-30f=3.5-30f> 2.0-30f>2.5-30f>4.0-30f. Generally speaking, a lower floor area ratio means fewer buildings and greater external comfort areas. However, the simulation reflected different results.

3.2 Comparison of construction costs due to the increasing number of floors

From the analysis in Section 3.1, the increase in the number of building storeys did not bring significant improvement in the external wind environment.

Because of the requirements for elevators, wires, and civil water, introducing an additional level will increase the construction costs of a high-rise building. According to the statistics of construction cost of high-rise residential buildings in Hangzhou, the cost of completing a building unit of 11f to 18f was somewhere about 2750–2800 CNY/m2, and the cost for 25f to 30f was about 3450–3500 CNY/m2.

Fig. 5 indicates that the construction costs fell into two groups: one containing 11f and 18f, and the other containing 25f and 30f. Comparing Fig. 6 with Fig. 5, it can be concluded that:

Fig. 5
figure 5

Gross construction cost of each layout cost per square meter: 2750 CNY/m2 of 11f; 2800 CNY/m2 of 18f; 3450 CNY/m2 of 25f; 3500 CNY/m2 of 30f (Cao, 2014)

Fig. 6
figure 6

Percentage of comfort area in each layout

During the building layout planning, for the purpose of improving the outdoor wind environment, simply replacing the 11f–18f units with building units above level 25 may raise the comfort area size of the external wind environment by only 2%–5% (the floor area ratio would be 2.0, 2.5, or 3.0). However, the capital investment would increase dramatically, by 22%–24%. Thus, this layout is not a cost-effective option.

Furthermore, the only layout option of 4.0-30f turned out to be a less suitable choice because of the low comfort area ratio and the high cost of construction.

Overall, if dealing with a layout with a floor area ratio of 2.0, any combination is viable except for a layout of 2.0-11f. When the ratio is 2.5, the solution could be either a 2.5-18f or 2.5-25f layout. When the ratio is 3.0, a layout of 3.0-18f is a cost-effective choice while 3.0-25f are 3.0-30f layouts are also suitable if sufficient funds are provided. When the ratio is 3.5, there is only a minor difference between layouts 3.5-25f and 3.5-30f. Hence, we recommend considering both options during planning. When the ratio is 4.0, only one type of layout is suitable, namely 4.0-30f. This requires significant finance and the enhancement of the wind environment is only modest. Therefore, special designs should be considered, such as introducing a bottom overhead or body reverse effect to optimize the wind environment.

4 Conclusions

This study considered the layout planning of 13 common types of high-rise building in Hangzhou, China with floor area ratios from 2.0 to 4.0.

Through simulations and comparisons of the outdoor wind environment and consideration of potential construction cost increments induced by raising building height, we draw the following conclusions as a reference for architects who wish to achieve a balanced state between the living space and the outdoor physical environment in their designs:

  1. 1.

    With increasing numbers of storeys, the outdoor wind zone is more comfortable for pedestrians. However, the increase in the comfort area is limited when the number of floors increases from 25 to 30.

  2. 2.

    In the case study of 2.0-11f with a building density of 18%, the proportion of the area in the comfort zone was only 43%. We do not recommend increasing the number of building units in this case because it will worsen the outdoor wind environment around the building. This result contradicts the traditional opinion that a lower floor area ratio means fewer buildings and greater external comfort areas.

  3. 3.

    The cases of 2.5-18f with a building density of 14% and 2.5-25f with a building density of 10% could be given prime consideration when planning the layout of a cluster of buildings.

  4. 4.

    The case of 3.0-18f with a building density of 17% is an economical strategy for a master design. The cases of 3.0-25f (with a building density of 12%) and 3.0-30f (with a building density of 10%) could be considered if the project is adequately financed.

  5. 5.

    There was not much difference between the cases of 3.5-25f (with a building density of 14%) and 3.5-30f (with a building density of 12%). Thus, both are recommended.

  6. 6.

    In the case with a floor area ratio of 4.0, only a cluster of 30-storey buildings met the sunlight requirement. Moreover, special design features should be considered, such as a bottom overhead or a twisted building shape, to improve the outdoor wind environment around the buildings.

One limitation of this study is that the assessment did not take account of the buildings around the site which can greatly influence the wind environment and external comfort. In particular, the number of storeys in these buildings may be a major factor affecting the external environment. In addition, the plans of all the buildings were square in this study. However, in practice there are various plan forms. Different kinds of plans and building shapes would also be influencing factors. In future study, the method proposed in this study should find an application to a real plan and show how it can help in decision-making.