Introduction

The convectional air conditioning equipment used for heating and cooling environment systems consume a lot of energy. Hybrid heating systems consist of two types of heating systems, namely radiation and convection. They work together to provide an efficient thermal comfort within an environment. This type of system can supply continuous heating energy even when one of them is off. Therefore, this technique is a very promising method which can reduce the energy consumption without lowering the level of comfort conditions.

In general, the thermal comfort is affected by the air temperature, mean radiant temperature; air velocity and relative humidity are included in the environmental parameters whereas the activity level and metabolic rate are categorized as the personal ones. Hence, in the hybrid system, the radiant heater temperature, surfaces, location, the air flow field, and metabolism are the most important factors affecting the level of thermal comfort in an environment [1].

So far, researchers have proposed different models to obtain higher level of thermal comfort in an environment [2, 3]. Thermodynamic analysis of heat and mass of human body and its effects on thermal comfort were studied by Prek [4]. Jeet at el. [5] have evaluated the effect of high-temperature radiant heaters and windows on the thermal comfort. Despite Jeet’s study, Myhern and Holmberg [6] have shown that low radiant panel temperature is more suitable for indoor environment. A combination of flow field around a human body was studied numerically by Murakumi, at el. [7]. A more complex model which includes the real body shape and physiology was considered by Kilic and Sevilgen [8]. They evaluated the heat transfer, mass, air flow and moisture around the human model.

As of now, the effects of flow and geometric parameters on thermal comfort have been studied in several papers individually. However, no detailed combinations of their interaction effects are seen in the literature. Therefore, in this study, the effects of input parameter such as temperature, surface area, and position of the radiant heaters along with their interactions on a hybrid heating system have been investigated. In addition, the air flow parameters of the convection system were also considered. The main objective of this study is to achieve thermal comfort in an indoor environment. In this simulation, a 3D model of a virtual standing thermal manikin with real dimensions is used. A numerical method was used to solve the flow field around the manikin. Also an optimization toward thermal comfort conditions is done.

Governing equations and solutions

The governing equations, consisting of continuity, momentum, energy, and mass transfer in a room which includes a manikin, are solved here. The radiation and turbulence equations are also considered in this problem. In addition, the Factorial Design Method (FDM) is used to analyze and optimize the variable effective parameters.

The conservation of mass can be written as [9]:

$$ \nabla .\left(\rho \overrightarrow{V}\right)=0 $$
(1)

The conservation of momentum is described by [10].

$$ \nabla .\left(\rho .\overrightarrow{V}.\overrightarrow{V}\right)=-\nabla p+\nabla .\left(\overline{\overline{\tau}}\right)+\rho \overrightarrow{g} $$
(2)

The stress tensor \( \overline{\tau} \) is given by;

$$ \overline{\overline{\tau}}=\mu \left[\left(\nabla \overrightarrow{V}+\nabla {\overrightarrow{V}}^T\right)\right]-\frac{2}{3}\nabla .\overrightarrow{V}I $$
(3)

The energy equation is:

$$ \begin{array}{l}\nabla .\left(\overrightarrow{V}\left(\rho E+p\right)\right)=\nabla .\Big({k}_{eff}\nabla T-\\ {}{\displaystyle {\sum}_j{h}_j}{\overrightarrow{J}}_j+\left(\overline{\overline{\tau}}.\overrightarrow{V}\right)\Big)\end{array} $$
(4)

In Equation 4,

$$ E=h-\frac{p}{\rho }+\frac{V^2}{2} $$
(5)

Where h is defined as

$$ h={\displaystyle \sum_j{Y}_j}{h}_j+\frac{p}{\rho } $$
(6)

Where, Y j is the mass fraction of species j and

$$ {h}_j={\displaystyle \underset{T_{ref}}{\overset{T}{\int }}{C}_{p,j}}dT $$
(7)

Here T ref is 298.15 K.

The conservation equation for the species transport in the general form is:

$$ \frac{\partial }{\partial t}\left(\rho {Y}_j\right)+\nabla .\left(\overrightarrow{V}{Y}_j\right)=\nabla .{\overrightarrow{J}}_j $$
(8)

The mass diffusion \( {\overrightarrow{J}}_j \) in turbulent flow is:

$$ {\overrightarrow{J}}_j=-\left(\rho {D}_{j,m}+\frac{\mu_t}{s{c}_t}\right)\nabla {Y}_j-{D}_{T,j}\frac{\nabla T}{T} $$
(9)

Where, Sc t is the turbulent Schmidt number.

The Predicted Mean Vote, PMV which is the response of large groups of people to the temperature sensitivity of an environment based on ASHRAE Standard is stated as the following equation [11].

$$ \begin{array}{l}PMV=\Big(0.303 \exp \left(-0.035M\right)+\\ {}0.028\Big)L\end{array} $$
(10)

The heat balance equation of a human body is given as;

$$ \begin{array}{l}S=M\mp W\mp R\mp C\mp K-{E}_{sk}\\ {}-\left({C}_{res}+{E}_{res}\right)\end{array} $$
(11)

By solving the flow field, all terms in equation 11can be calculated.

When S = 0, the thermal equilibrium will be satisfied [6]. In equation 11 E sk , C res and E res terms can be calculated as follows

$$ {E}_{sk}=\frac{w\left(P-{P}_a\right)}{R_{cl}} $$
(12)
$$ {C}_{res}= 0.0014M\left( 34-T\right) $$
(13)
$$ {E}_{res}=1.72\times {10}^{-5}M\left(5867-{P}_a\right) $$
(14)

The Factorial Design Method (2k) or two level design is used here for optimization [12]. The input and output parameters’ range must also be specified. The input parameters are the area of convection flow, inlet flow rate, temperature, location, and the surface area of radiant heater. The output effective parameters are the radiation flux, convection flux, and PMV index. In this technique, the impact of the factor is defined as the difference between the high and low level of responses.

The values of input parameters based on some primary calculations are given in Table 1. The critical and major effects of parameters are defined in Pareto and normal probability graphs. Their effects can also be stated as a regression equation. Then, the model is optimized for the objective function with the method of least squares and logistic regression [13].

Table 1 Range of input parameters

A 3D computational code was used to solve the flow field, energy, and mass equation. The PISO algorithm has been used [14]. In this approach, higher-order accuracy is achieved at cell faces. Pressure discretization is done by second order method. The KεRNG is also suitable for low-Reynolds numbers and more accurate and reliable for a wider range of indoor environments and flows with heat transfer.

The DO radiation model is used to consider the radiation effects of heating surfaces and sources in the flow fluid simulation. It allows the solution of radiation at semi-transparent walls.

Geometry of the problem

As be shown in Fig. 1 the problem consists of a manikin model stand and a radiant heater located within a room. One window, a door, and two vents at the bottom and top of the door have been considered for the circulation of air flow. Room dimensions are 3 × 4 × 4 m. The manikin has a height of 1.75 m and weight of 75 kg. The dimension of the window and door is 1 × 1.2 m and 1 × 2 m, respectively. The size of the inlet, outlet and the heater are assumed to be variable for the optimization purpose.

Fig. 1
figure 1

The room with heater and manikin

The segments of the manikin model have been shown schematically in Fig. 2 and their values are tabulated in Table 2.

Fig. 2
figure 2

The segment of the manikin model

Table 2 Segment of the manikin and their area

This problem was first modeled using Solid Work and, then, meshed by Hypermesh software. The problem is solved for several different heater locations to optimize its position in the room.

Computational grid

Due to complex geometry and fine surfaces in this problem, generating structured grid for all sub regions is not an easy task. Therefore, a combination of unstructured-structured grid system is applied using Algorithm T-Grid. It has been shown in Fig. 3. Since the flow field around the manikin includes high gradients of flow parameters, an appropriate distribution function starts from the lower layer around the surface and continues to the maximum step. The problem was solved for several different grid sizes for its independency. As shown in Fig. 4 the final results are independent numbers of grids when it is selected as 3,900,000 [15].

Fig. 3
figure 3

The computational domain in the room

Fig. 4
figure 4

The effects of the cell number on the volume-averaged temperature of room

Boundary conditions

The boundary conditions are given in Table 3. These values are taken based on ASHRAE standard [15]. The characteristics of building materials are given in Table 4.

Table 3 Boundary condition
Table 4 Physical characteristic of material [15]

Validation of results

For the validation of the present model, the calculated result was compared to the available experimental data in the literature [16]. The compression for the velocity, temperature and relative humidity are shown in Figs. 5, 6 and 7, respectively. As shown in these figures, the obtained values have a high agreement with the experimental data [16]. The maximum difference between the experimental and numerical velocity, temperature and relative humidity is 0.03 m/s, 0.4 °C and 0.5 %, respectively.

Fig. 5
figure 5

Comparison the computed velocity with Numerical and experimental results of ref. [16]

Fig. 6
figure 6

Comparison the computed temperature with Numerical and experimental results of ref. [16]

Fig. 7
figure 7

Comparison the computed RH% with Numerical and experimental results of ref. [16]

Results and discussion

The impact of input parameters on the objective functions

The effect of input parameters on the objective parameters using Pareto and normal charts are compared and discussed in Figs. 8 and 9 The Pareto chart presents the significant effect of the parameters whereas the normal chart indicates their percentage. The effect of input parameters on the total heat flux, PMV index, radiation heat flux, and relative humidity are shown in these Figures, respectively.

Fig. 8
figure 8

The effect of the input parameter on the PMV index

Fig. 9
figure 9

The effect of the input parameter on the radiation flux

In these Figures, the letter A is the cross section area of the inlet vent, B is the input velocity, C is the heater temperature, D and E are the positions of heaters along the horizontal and vertical directions, and F is the surface area of the heater. The impacts of these parameters as well as their combinations are studied individually.

Hence, by glancing at all Figs. 8 and 9 it can be concluded that:F has the most effect on the object function and requires more energy C has the most effect on the objective function and needs no more energy. The combination of input parameters has different impacts on the objective function in comparison to their individual ones due to their interaction. Some of these combinations which can be used as useful tools have significant effect on thermal comfort and require no more energy

The optimization

The effect of input parameters on the objective parameters is determined in previous section and they are optimized here for different cases. In this case, the problem is optimized for the values of total flux 110w/m2, radiation flux 40w/m2, relative humidity 50 % and PMV 0.001. The optimized values are calculated and tabulated in Table 5.

Table 5 Optimized value for objective parameter

Velocity, temperature and relative humidity distribution around the manikin

The Velocity, temperature, and humidity contours around the manikin surface are shown in Figs. 10, 11 and 12. A better symmetrical velocity distribution around the manikin is also presented in the hybrid system. The maximum velocity occurs near the head of the manikin due to larger temperature gradient. The all distribution values around the manikin are within the ASHRAE standard [15] and there is almost no stagnation zone which provides a proper thermal comfort for a person According to temperature contour in Fig. 11.

Fig. 10
figure 10

The velocity contribution for optimum case

Fig. 11
figure 11

The temperature contribution for optimum case

Fig. 12
figure 12

The humidity contribution for optimum case

Thermal comfort

The fraction of convection and radiation heat flux in heating systems, convection and hybrid, for all segments of the manikin are tabulated in Table 6.

Table 6 Heat losses rate from body

Table 7 presents the heat losses from the body and walls, and PMV values for both heating systems. As the values of PMV indicate, the heating hybrid systems can provide faster and better human thermal comfort in a residential room. The PMV value for the convection heating systems is −0.86 whereas for the hybrid system, it is 0.0034 which is almost near the ideal condition (PMV = 0) Despite the fact that the maximum velocity in this system is lower than the conventional heating system but it falls within the ASHRAE standard. This lower velocity makes lower heat losses through the walls and the manikin segments up to 25 %.

Table 7 Heat losses rate from body, room and PMV values in two cases

Conclusion

In this study, two heating systems, conventional and hybrid, are individually optimized and then compared with each other to have thermal comfort conditions. The Factorial Design Method (2K) or two level designs has been used for optimization. The effect of input parameters and their interaction is investigated on the objective function, such as PMV index, relative humidity and heat fluxes. The effects of the input parameters in normal and Pareto charts are presented. Based on the present study, the individual and the interaction of input parameters effect are significant and different. Heater temperature has the most effect on the object function and requires more energy whereas C has the most effect on the objective function but needs no more energy thus some combination can be used as useful tools in designing heating systems. The thermal comfort can be obtained using less input energy by just increasing the surface area of the heater and its location. A better symmetrical velocity distribution around the manikin is also presented in the hybrid system. The lower velocity makes lower heat losses through the walls and the manikin segments up to 25 %. The heating hybrid systems can provide faster and better human thermal comfort in a residential room.

Thanksgiving

I would like to thank all those who have helped me in doing the research. Also, I want to thank you for giving us the opportunity to publish our paper in the Journal of Environmental Health Science and Engineering.

Nomenclature

C, Convective heat loss(w/m2)

C res , Convection heat loss due to respiration(w/m2)

D i,m , Mass diffusion coefficient for species

D T , Turbulent diffusivity

E res , Evaporative heat loss due to respiration(w/m2)

E, Total energy (J)

E sk , Evaporative heat loss of skin

\( \overrightarrow{g} \), Gravitational acceleration

h, Sensible enthalpy

I, Unit tensor

\( {\overrightarrow{J}}_j \), Diffusion flux of species

k eff , Effective conductivity

k t , Turbulent thermal conductivity

L, The heat load of the body

M, Metabolic heat production(w/m2)

P α, ambient pressure air (kpa)

PMW, Predict mean vote

R cl , Resistance of clothes

R, Radiative heat loss(w/m2)

S, Heat storage(w\m2)

\( \overrightarrow{V} \), Velocity vector

W, External work(w/m2)

Y j , Mass fraction of species

μ, Molecular viscosity

ρ, Density

\( \overline{\overline{\tau}} \), Stress tensor