Introduction

During the past decades, several researches have concentrated on the performance of steel built-up batten columns due to axial loads (Hosseini Hashemi and Jafari 2009, 2012). Following the Bam earthquake of 2003 in south-eastern Iran, several steel structures were damaged (Eshghi et al. 2003). Failure of the built-up batten columns was one of the most observable failure modes in damaged buildings (Hosseini Hashemi and Jafari 2004; Hosseinzadeh 2004). In most of these studies, the behavior of the batten columns due to gravitational loads was investigated. In other words, most of the researchers neglected the effect of the lateral loads on the behavior of steel batten columns (Hosseini Hashemi and Jafari 2004). Following the Bam earthquake, some studies were conducted to investigate the behavior of batten columns due to the earthquake. Razzaghi et al. (2010) investigated the performance of built-up batten columns due to axial and cyclic lateral loads. The results of this study revealed that laterally loaded batten columns had extremely unstable behaviors in the post-buckling region. It was also shown that existing code provisions are not sufficient for seismic design of batten columns. Furthermore, Hosseini Hashemi and Hassanzadeh (2008) studied the performance of the damaged steel building with batten columns due to the Bam earthquake.

Based on the seismic vulnerability of steel batten columns and the large number of buildings with these types of columns in areas with high seismic action potential, retrofit methods are required for steel batten columns. On the other hand, concrete-filled steel tubular columns are widely used in steel structures. Several numerical and experimental investigations revealed the acceptable performance of concrete-filled tubes under different loading conditions (Cai and He 2007; de Oliviera et al. 2010). Hence, it seems that filling the hollow space between column chords would be a suitable method for improvement of seismic performance of built-up batten columns.

This paper aims to investigate the performance of concrete-filled built-up batten columns (CFBBC) as both retrofitted columns and newly designed and/or constructed columns. To this end, nonlinear static analyses were performed using the ANSYS (SAS 2010) software. Herein, parametric studies on the effects of compressive strength of concrete, distances of batten plates and axial loads on the performance of CFBBC were conducted.

Modeling

To conduct a parametric study on the performance of axially and laterally loaded CFBBC, the finite element method was used. In all of the models, both material and geometric nonlinearities were considered.

Geometric specifications of models

Geometric specifications of steel batten columns were adopted from the columns of the ground floor of a building damaged in the Bam earthquake as reported by Hosseini Hashemi and Hassanzadeh (2008). The target building was of steel frame with an X-bracing system. The columns had two IPE 160 chords, 17 cm apart, and battened by 18 × 10 × 1 cm batten plates at a distance of 50 cm c/c. The height of the ground floor was 5.2 m. The geometric specifications of the models are summarized in Table 1. As indicated in Table 1, there are two main categories of models: columns without concrete cores and columns with concrete cores. It should be noted that for those column which were originally designed and fabricated as CFBBC, the axial loads would be distributed to concrete and steel according to their stiffness. Such distributions may not occur in retrofitted batten columns. Hence as indicated in the second column of Table 1, different distribution of axial loads are considered in CFBBC models.

Table 1 Specifications of models

Elements used for FE analyses

Three-dimensional solid elements (Solid 65) have been used to model the concrete core. This element is defined by eight nodes having three translational degrees of freedom at each node. This solid element is capable of cracking in tension and crushing in compression, plastic deformation and creep (SAS 2010). Three-dimensional solid elements (Solid 45) were used to model the steel batten columns. This element is defined by eight nodes having three translational degrees of freedom at each node. This element has suitable compatibility with the solid element of the concrete core. The element has plasticity, stress stiffening, large deflection and large strain capabilities (SAS 2010). Three-dimensional node to node contact element (Contact 178) was used to model the contact between the steel wall and concrete core. The element is located between two adjacent nodes of steel wall and the concrete core and is capable of modeling the separation, sliding and contact between two nodes during the loading process. The element has two nodes with three translational degrees of freedom at each node. The element is capable of supporting compression in the contact normal direction and Coulomb friction in the tangential direction (SAS 2010).

Material properties

The stress–strain behavior materials of concrete core and steel sections are shown in Fig. 1a, b, respectively. It should be noted that the multilinear isotropic stress–strain curve for ordinary concrete is computed with the equation proposed by MacGregor (1992), and for high-strength concrete is computed with the equation proposed by Popovics (1973). The elastic modulus of concrete for ordinary concrete and high-strength concrete is defined by Eqs. 1 and 2, respectively:

$$E_{c} = 5000\sqrt {f_{c}^{\prime } } \;\;\;\;\left( {\text{Mpa}} \right),$$
(1)
$$E_{c} = \left( {3320\sqrt {f_{c}^{\prime } } + 6900} \right)\left( {\frac{\rho }{2300}} \right)^{1.5} \;\;\;\;\left( {\text{Mpa}} \right),$$
(2)

in which f c is the compressive strength of concrete (Mpa) and ρ is the density of concrete (kg/m3).

Fig. 1
figure 1

The stress–strain relationship for the material

Material nonlinearity of steel was accounted for the analyses based on Von Mises yield criterion. The kinematic hardening rule was used to define the material property in these elements. The Willam and Warnke (1974) model was used to define the failure of concrete. The concrete failure criterion can be expressed as follows:

$$\frac{F}{{f_{c}^{\prime } }} - S \ge 0,$$
(3)

where S is the failure surface which is expressed by five input parameters: ultimate uniaxial compressive and tensile strength, ultimate biaxial compressive strength, ultimate compressive strength for a state of biaxial compression superimposed on hydrostatic stress state and ultimate compressive strength for a state of uniaxial compression superimposed on hydrostatic stress state. The failure surface in principal stress space σzp close to zero is indicated in Fig. 2.

Fig. 2
figure 2

Failure surface in the principal stress space close to zero (SAS 2010)

Boundary conditions and loading pattern

The boundary conditions and loading pattern of the models are illustrated in Fig. 3. Two loading conditions were considered: constant axial loads along with monotonic increasing lateral displacement and constant axial load along with cyclic lateral displacement. To this end, a constant axial force of 350 kN was applied to all of the models. Coincidentally, lateral cyclic displacement (δ) is applied to the top of the columns, as indicated in Fig. 3. It is worth mentioning that the parameter (δ y) in Fig. 3 is the lateral displacement of the yielding point of batten columns without concrete core. It should be noted that two independent conditions were considered for lateral loads: parallel to batten plates and perpendicular to them.

Fig. 3
figure 3

Cyclic lateral loading history and loading conditions used in FEM

Results

Figure 4 indicates the pushover curves of the steel batten columns and CFBBC models. As indicated in this figure, the behavior of CFBBCs in which the axial load had just been applied to the steel chords was not acceptable. In such columns, both pre- and post-buckling performance was the same as those of built-up batten columns. Figure 4 also illustrates that even hollow batten columns with short distances of batten plates perform slightly better than CFBBCs without axial load bearing of concrete core. It is obvious that in such a case, using high-strength concrete does not noticeably change the performance of CFBBC. Those CFBBCs in which the concrete core contributed to bearing axial loads, the behavior changed dramatically. Distribution of the Von Mises stress in column chords and batten plates is indicated in Fig. 5.

Fig. 4
figure 4

Comparison of shear force–displacement curves in batten columns and CFBBCs

Fig. 5
figure 5

Deformed shapes and Von Mises stress contours in the displacement to 9.5 cm and parallel battens

Comparison of shear force–displacement behavior of CFBBCs and distribution of Von Mises stress on their deformed shapes are shown in Figs. 6 and 7, respectively. As illustrated in Fig. 6a, in CFBBC columns in which concrete cores contributed in bearing the axial load according to their stiffness, the buckling was not the major failure mode of the columns. Minor local buckling happened in some of the models after formation of plastic hinges. In locally buckled columns, the post-buckling behavior was rather stable. Concrete-filled batten columns with high-strength concrete cores had the highest ultimate strength. Variation of the compressive strength of concrete from 20 to 60 MPa made 13–20 % change in the ultimate strength of CFBBCs. Furthermore, decreasing the spacing of batten plates at the bottom of the column increases the ultimate capacity of the columns by about 5 %. As indicated in Fig. 6b when the lateral loads are applied to the column in a direction perpendicular to the batten plates, the spacing of batten plates do not have any contribution in the bearing capacity of CFBBCs.

Fig. 6
figure 6

Shear force–displacement curves for different CFBBCs

Fig. 7
figure 7

Deformed shapes and Von Mises stress contours in the displacement to 9.5 cm and parallel battens

Figure 8 shows the envelope curves of hysteretic loops for the batten columns with and without concrete cores. As illustrated in this figure, there is an observable load drop in envelope curve of the steel batten column. Such a drop happened because of buckling. It is observable in Fig. 8a that no drop happened in the envelope curve of the hysteresis loops of CFBBCs. In other words, even in CFBBCs without load carrying in the concrete core, the hysteretic behavior is noticeably more stable than that of steel batten columns. Figure 8b shows that load-carrying cores had observable change in the hysteretic behavior of steel batten columns.

Fig. 8
figure 8

The envelope curves of hysteretic loops

To investigate the effects of load carrying of the concrete core on the performance of the CFBBCs, the pushover curves of CFBBCs with different axial load carrying in concrete cores are compared in Fig. 9. As indicated in this figure, the ultimate strengths of the CFBBCs were noticeably increased by increasing the axial load carrying of the concrete core. Furthermore, similar results were observable in the hysteretic behavior of these columns (See Fig. 10).

Fig. 9
figure 9

Shear force–displacement curves, parallel to battens

Fig. 10
figure 10

The envelope curves of hysteretic loops, parallel to battens

Conclusions

In this paper, parametric study on nonlinear performance of steel batten columns with and without concrete cores was conducted. To this end, nonlinear static analyses were carried out. Results of this study revealed that:

  • Axial load-carrying concrete cores can increase the ultimate strength of the steel batten columns.

  • Despite the steel batten columns in CFBBCs with axial load-carrying cores, buckling is not the major failure mode of the column.

  • In CFBBCs with axial load-carrying cores, changing the compressive strength of concrete from 20 to 60 Mpa causes about 13–20 % increase in the ultimate capacity of the column.

  • The spacing of the bottom batten plates in the built-up batten columns with and without concrete core makes a noticeable contribution in ultimate capacity and hysteretic behaviors of columns.

Based on the results of this study, using concrete core would be a suitable approach for strengthening of the built-up batten columns. But in implementation of this method, attention should be given to ensure that axial loads are distributed between both steel chords and concrete cores.