1 Introduction

Since the first decade of this century, the whole refrigeration industry has entered a new stage leading by the replacement of refrigerants, the "blood" of refrigerating and air conditioning machines. Due to the increasing challenge of global warming, third-generation refrigerants represented by hydrofluorocarbons (HFCs such as R134a, R410A, and R404A, etc.) have been facing a phase-out situation for their high Global Warming Potential (GWP). Various regional and global protocols and regulations have been put forward over the last twenty years, represented by the European F-gas regulations [1, 2] and the Kigali Amendment [3]. The Kigali Amendment, which came into effect on Jan. 1st, 2019, provides a clear schedule for the phasing-out of high GWP HFCs. therefore, searching and testing new alternative refrigerants became more important and urgent.

Hydrofluoroolefins, the fluoride unsaturated hydrocarbons, are now widely accepted as the most promising alternatives besides natural refrigerants [4]. With unsaturated carbon–carbon bonds, these synthetic compounds have very short expectancy when exposed to the atmosphere, resulting in their ultra-low GWPs [5, 6]. Despite mild flammability, two hydrofluoroolefins (R1234yf and R1234ze(E)) have already been well studied by researchers and introduced into different commercial applications. However, other potential hydrofluoroolefins are not sufficiently understood even in labs at present. Researchers at the National Institute of Standard and Technology (NIST) have carried out a series of work on the screening of potential compounds from all chemical databases [7]. Lists of limited candidates were provided in different application areas and most of them were hydrofluoroolefins.

Thermophysical properties are the foundation of pre-evaluation for alternative refrigerants and performances of their systems. A critical review of thermophysical experimental reports has been contributed recently and shown a lack of data available for HFOs except for R1234yf and R1234ze(E), which largely restrict potential applications [8]. Among various properties, isobaric heat capacity (cp) is a special one, which associated directly with enthalpy and entropy, making it the basis for thermodynamic calculation and modeling. Meanwhile, as a typical caloric property which is calculated from both 1st and 2nd order derivatives of Helmholtz free energy, cp also plays an important role in the development of accurate and stable fundamental equations of state.

Flow calorimetry [9], quasi-steady calorimetry [10] and thermal relaxation method [11] can be used to obtain reliable experimental isobaric heat capacity data for liquids under different temperatures and pressures. These methods have already been used on liquid R1234yf and R1234ze(E). However, there are still no experimental data available for other HFOs to our best knowledge. Therefore, theoretical predictions become essential and will be beneficial for researchers and engineers in exploring alternative refrigerants in the current situation.

2 Isobaric Heat Capacity Prediction Methods

The isobaric heat capacity of liquids is split into two parts: an ideal gas term and a residual term. Nowadays, the ideal gas heat capacity is usually obtained by gas sound-speed experiments [12] or vibrational energies [13] and then correlated to a temperature-dependent polynomial function. Alternatively, ideal gas heat capacity can be calculated from ab initio or group contributions without experiments [14]. On the other hand, the residual part, which comprises molecular interactions (dispersive and electrostatic interactions) but no contributions from bond stretching, angle bending, and torsion, can be calculated by different theoretical methods.

Theoretical prediction of residual isobaric heat capacity is a representative application of classic thermodynamic relations. It can be performed with different equations of state, such as traditional cubic EOS (CEOS) [15], multi-parameter fundamental EOS (FEOS) [16], perturbation EOS [17] etc. In this study, we selected Peng-Robinson (PR) EOS and Helmholtz free energy EOS. PR EOS is a cubic EOS with volume translation, it has a general expression with only characteristic parameters needed for calculation, and it is predictive among different fluids. Helmholtz free energy EOSs are multi-parameter fundamental EOSs with the highest accuracy in all thermodynamic properties’ calculations. Modern FEOSs consist of polynomial, exponential, and Gauss-bell shaped terms. The final structure and coefficients are different for each fluid, which were determined by optimization regression with experimental property data. These FEOSs are predictable for each fluid, which means one can establish a FEOS with for example only vapor pressure and saturated density data, and apply it to calculate other properties such as isobaric heat capacity. It should be noticed that the accuracy of this prediction is not easily guaranteed because 2nd order derivatives are needed in isobaric heat capacity and they are extremely sensitive to the Helmholtz free energy surface.

In recent years, novel EOS such as perturbation EOS (such as PC-SAFT) and cubic plus association EOS (CPA) have also been proposed for alternative refrigerants R1233zd(E), R1234yf, R1234ze(E), and R1234ze(Z) [18]. PC-SAFT is Helmholtz free energy-based and its calculation for isobaric heat capacity follows the same process with FEOS, while CPA is pressure-based, adding an association part to traditional cubic EOS. Both of these EOS have semi-empirical parameters that need to be determined by fitting experimental data. The different fitting strategies would result in different EOS performance. If there were no experimental cp available in parameter-fitting, the calculation from PC-SAFT and CPA for cp are unacceptable.

Molecular simulation (MS) is another powerful way to predict the thermodynamic properties of fluids. A series of work on the simulation of the HFOs and their mixtures have been carried out by researchers in the last few years [19,20,21]. Based on either complicated all-atom force fields or simplified LJ2C force fields, these simulations could provide satisfying results for the volumetric and vapor–liquid equilibrium properties, with several molecular parameters transferred or correlated by experimental data. However, regarding cp calculation from molecular simulations, the uncertainty is of the same order of magnitude as the uncertainties for residual configurational energy due to interpolation, which reflects the difficulty of MS in heat capacity calculation [20].

Empirical and semi-empirical methods have also been provided by researchers to predict isobaric heat capacity, such as Group Contribution Method (mostly used for ideal gas heat capacity), Corresponding State Method [22], and data-driven artificial neural network [23]. In this work, a pre-proposed corresponding state equation (CSE) [24] explicit in isobaric heat capacity for hydrofluorocarbons was studied in comparison with selected EOS. The CSE was a four-parameter semi-empirical function with its structure and coefficients correlated from traditional hydrofluorocarbon refrigerants. Since the objects in this study belong to the same class of compounds (short-chain molecules consisting of Hydrogen, Fluorine, and Carbon atoms), they are thought to be more likely to satisfy the assumptions of the corresponding state principle.

The detailed information for the three methods and their calculation form for isobaric heat capacity is listed in Table 1.

Table 1 Description of the models studied in this work

3 Comparison and Results

A total of 9 HFOs were investigated in this study and their basic information is shown in Table 2. These HFOs were divided into 3 classes, according to whether they have available experimental data, the fundamental equation of state, and characteristic parameters used in CEOS and CSE.

Table 2 Information table for HFO refrigerants

R1234yf and R1234ze(E) were assigned as Class 1 refrigerants, with experimental cp data [10, 11, 25, 26] and FEOS reported [27, 28]. Class 2 refrigerants were those who had preliminary FEOS established without experimental cp, including R1123, R1216, R1234ze(Z), R1243zf, and R1336mzz(Z). Class 3 refrigerants consisted of R1141 and R1225zc, these two HFOs had neither experimental cp nor FEOS, but only reliable critical points and acentric factors. Other HFOs with only estimated characteristic parameters were not concerned, such as R1132(E), R1234ye(E), R1225ye(Z), R1132(Z), and R1225ye(E).

As shown in Table 1, CEOS and CSE were easily self-programmed, while FEOS used in this study were embedded in the latest version of the NIST Refprop Database [30]. Available information of these FEOSs is listed in Table 3, including their terms and calorimetric properties used in correlation, which is an important factor for evaluating the ability of FEOS in second-order derivative property calculations. Characteristic parameters used for CEOS and CSE were referred to in the recent review [8]. Ideal gas heat capacities were obtained from NIST Refprop Database for class 1 and class 2 refrigerants, and group contribution method for class 3 refrigerants [32]. All the calculation results from CEOS and CSE can be found in the Appendix.

Table 3 FEOS information for Class 1 & 2 refrigerants

For class 1 refrigerants, calculated liquid cp data by FEOS, CEOS, and CSE were compared to the experimental reports. As can be seen in Fig. 1, both CSE and FEOS well-presented experimental data of R1234yf and R1234ze(E) in a wide range. The average absolute deviation (AAD %) and maximum absolute deviation (MAD %) between CSE and experimental data were 0.9 % and 4.0 % for R1234yf, and 1.0 % and 3.6 % for R1234ze(E), as listed in Table 4. AAD % and MAD % between FEOS and experimental data were 0.6 % and 3.3 % for R1234yf, and 1.1 % and 4.7 % for R1234ze(E). However, CEOS generally provided calculated values with positive deviations, and the deviations tended to be larger at higher temperatures where the absolute value of cp became larger. The AAD % and MAD % of CEOS were 6.2 % and 15.6 % for R1234yf, and 4.4 % and 18.4 % for R1234ze(E). An interesting phenomenon is that, despite unacceptable deviations, predicted values of CEOS nearly followed a strong linear relationship to the real values, seen in Fig. 1. The Pearson factor between CEOS calculations and experimental data were 0.9925 for R1234yf and 0.9826 for R1234ze(E), respectively.

Fig. 1
figure 1

Comparison between calculated liquid heat capacity for Class 1 refrigerants by FEOS, CEOS and CSE

Table 4 Comparison between predictions and experimental data for Class 1 refrigerants

For class 2 refrigerants, cross-comparisons between the theoretical methods were performed, with no available experiments. The testing temperature range was set as 210 K to 430 K (different for each one) and pressure range 1 MPa to 10 MPa, respectively. Comparison results are shown in Fig. 2 and Table 5. CSE and FEOS showed very good agreements for class 2 refrigerants with all the AADs % less than 3.6 %, and MADs % less than 7.2 %. Larger deviations trended to occur at higher temperatures. The pair plot between CEOS and FEOS showed similar trends to that between CEOS and CSE. Average deviations between CEOS and CSE were less than 5.1 %, and also a strong linear relationship could be detected for all class 2 refrigerants.

Fig. 2
figure 2

Cross comparison of liquid heat capacities predicted by CSE, FEOS and CEOS for Class 2 refrigerants

Table 5 Cross comparison between CEOS, FEOS and CSE for Class 2 refrigerantsa

For Class 3 refrigerants, the comparison can only be performed between two general methods CSE and CEOS. The results are shown in Fig. 3 and Table 6. The AAD % and MAD % between CSE and CEOS were 6.6 % and 24.4 % for R1141, and 3.6 % and 17.4 % for R1225zc. As with class 1 and class 2 refrigerants, heat capacity values calculated from CEOS were bigger than those from CSE. The deviations became larger at higher temperatures, and a strong linear relation was also observed with Pearson factors of 0.9988 for R1141 and 0.9845 for R1225zc. Furthermore, the calculated points of CSE for R1141 and R1225zc are exhibited in Fig. 4 to show their variation trends versus temperature and pressure. The isobaric heat capacity would increase with the rise of temperature, and trended to be infinite near the critical point.

Fig. 3
figure 3

Comparison of predicted heat capacities for Class 3 refrigerants by CSE and CEOS

Table 6 Comparison between CEOS and CSE for Class 3 refrigerants
Fig. 4
figure 4

Liquid heat capacity of Class 3 refrigerants (R1141 (a) and R1225zc (b)) predicted by CSE

4 Discussion and Conclusions

In this paper, three different theoretical models were compared in liquid isobaric heat capacity prediction for hydrofluoroolefins refrigerants, which were general cubic EOS, specific fundamental EOSs, and a general corresponding state equation (CSE). To perform calculations for a certain object, CEOS and CSE need only several characteristic parameters (critical points and acentric factor), while FEOS needs at least volumetric experimental data (e.g., vapor pressure, saturated liquid density) to determine its specific structure and coefficients. Considering that isobaric heat capacity is a second-order derivative property, the accuracy of FEOS in this calculation highly relies on whether calorimetric property data were used in correlation.

Nine HFOs were selected for this study and were divided into 3 classes based on whether experimental cp data and FEOS were available. The comparison showed that both CSE and FEOS represent available experimental data well with AADs % less than the reported experimental uncertainties. For refrigerants without experimental heat capacity, CSE and FEOS showed good agreements with all the AADs % less than 3.6 %.

The selected CEOS always provided relatively bigger predictions than experiments or the other two methods, and the deviations tended to be larger at higher temperatures. Despite that, calculated data of CEOS showed a strong linear relation with the others, which suggested that there might be a potential linear modification or correlation for CEOS in improving its heat capacity calculations. Finally, when there were no experimental data available, CSE used in this study could be a very useful and reliable preliminary evaluation tool for the liquid heat capacity of hydrofluoroolefins, considering its performance and easy application. It also indicated that for liquid isobaric heat capacity, the corresponding state principle works well within hydrofluoroolefins, and this conception could be possibly used in other thermophysical properties.