The insertion of current-limiting reactors into electrical equipment operating at a voltage of 110 and 220 kV produces a change in the parameters of the transient recovery voltages at the contacts of the circuit breakers for disconnecting short circuits, which could be the reason for the increase in the duration of the short circuit, damage to the electrical equipment and losses in the power system. The results of mathematical modeling of the transients, caused by tripping of the short circuit in a reactive electric power transmission line are presented, and data are given on the negative effect of a current-limiting resistor on the rate of increase and peak value of the transient recovery voltages. Methods of ensuring the standard requirements imposed on the parameters of the transient recovery voltages when using current-limiting reactors in the high-voltage electrical equipment of power plants and substations are proposed and analyzed.
Similar content being viewed by others
References
Regulating Document RD 34.20.175. Directions for Limiting Short-Circuit Currents in 110 kV and Higher Voltage Networks [in Russian].
T. A. Bellei, E. H. Camm, and G. Ransom, “Current-limiting inductors used in capacitor banks applications and their impact on fault current interruption,” in: Proc. of the 2001 IEEE/PES Transmission and Distribution Conference, Atlanta, Georgia, Oct. 28, 2001, Vol. 1, Nov. 2.
D. Shoup, J. Paserba, J. R. G. Colclaser, T. Rosenberger, L. Ganatra, and C. Isaac, “Transient recovery voltage requirements associated with the application of current-limiting series reactors,” Electric Power Syst. Res., 77 (2007).
Yu. I. Sklyarevskii, Determination of the Parameters of the Recovery Voltages when Short Circuits are Tripped [in Russian], Izd. MÉI, Moscow (1977).
State Standard GOST 687–78. AC Voltage Circuit Breakers at Voltages above 1000 V. General Technical Requirements [in Russian].
State Standard GOST R 52565–2006. AC Circuit Breakers at Voltages from 3 to 750 kV. General Technical Requirements [in Russian], Standartinform, Moscow (2007).
Directions for Limiting High-Frequency Switching Overvoltages and for Protecting Electrical Equipment from them in Distributed 110 kV and Higher Equipment [in Russian], Izd. ORGRÉS, Moscow (1998).
IEC 62271-100. High-Voltage Switchgear and Controlgear. Part 100. High-Voltage Alternating-Current Circuit-Breakers.
M. S. Volkov and Yu. P. Gusev, “Analysis of transient recovery voltages on the contacts of circuit breakers when short-circuit currents are tripped in high-voltage networks with current-limiting reactors,” Vestnik MÉI, No. 4 (2013).
Author information
Authors and Affiliations
Additional information
Translated from Élektricheskie Stantsii, No. 7, July 2015, pp. 6 – 8.
Rights and permissions
About this article
Cite this article
Volkov, M.S., Gusev, Y.P., Monakov, Y.V. et al. The Effect of Current-Limiting Reactors on the Tripping of Short Circuits in High-Voltage Electrical Equipment. Power Technol Eng 49, 375–377 (2016). https://doi.org/10.1007/s10749-016-0631-9
Published:
Issue Date:
DOI: https://doi.org/10.1007/s10749-016-0631-9