Abstract
Fire throttling is the increase in flow resistance due to a large fire in a longitudinally ventilated tunnel. Although the fire throttling effect has been been known and studied for tunnels over the last 40 years, there is not yet a consistent one-dimensional (1D) model that can describe this behaviour or a framework suitable for practical application. We propose a semi-empirical model, based upon pipe flow engineering principles, to describe this effect by separating the resistance to flow, or pressure loses in three parts: upstream of the fire, locally at the fire, and downstream of the fire. The proposed 1D model called TE1D is derived from a simple steady one-dimensional momentum balance in which a semi-empirical mean temperature distribution is assumed across the tunnel. We verify the model by comparing the pressures losses it predicts with those calculated in CFD simulations based on OpenFOAM and Fire Dynamics Simulator. The comparison shows good agreement between the CFD codes for the range of fires sizes considered from 5 to 50 MW and good agreement between TE1D and the CFD results with the proposed 1D model for fire sizes below 30 MW. However, for values above there are large discrepancies between the results obtained by the TE1D and CFD. We posit as a potential explanation that these differences are due to flow and temperature stratification which is not accounted for in the 1D model. The model using pipe flow principles allows engineers to adopt this model for design, together with other pressure losses considered in tunnel ventilation.
Similar content being viewed by others
Avoid common mistakes on your manuscript.
1 Tunnel Ventilation and the Fire Throttling Effect
Globally, tunnel infrastructure is part of a sector with over $ 700 billion dollars of investment in 2017 [1]. For long transport tunnels such as road and rail tunnels, a key component in managing fire safety is the provision of a tunnel ventilation system to manage not only vehicle emissions but also, more importantly, smoke and heat from a fire.
In most tunnels, longitudinal ventilation is preferred to transverse systems due to their comparatively easier design and construction. Longitudinal ventilation can be achieved via jet fans, ventilation shafts or nozzles providing significantly simpler construction compared to extended plenums and smoke ducts for transverse system. The design of a longitudinal ventilation system is a well studied topic including design fires, critical ventilation velocity, tunnel fire ventilation calculations and back-layering [2, 3].
In a longitudinally ventilated tunnel, the ventilation principle in a fire is to push air along the tunnel, usually in the direction of traffic travel so the upstream of the fire is kept free of smoke. See Fig. 1. When designing such systems, the various contributors of pressure losses, such as surface friction, traffic obstructions, tunnel geometry and incline need to be consider. Fire is a key influence in the design of longitudinal ventilation systems.
The size of a fire, and its influence in the airflow velocity required to create a smoke free area upstream of the fire is the well studied topic of critical ventilation velocity. Further, it has been known for over 40 years [4] that a fire in a closed duct, e.g. a tunnel, results in pressure loss. The studies showed that the presence of a fire has a similar effect to that of a narrowing, or blockage, at the location of the fire. The terms fire throttling or fire choking used to refer to this effect may originate from the terminology employed to describe similar aerodynamic behaviour observed in internal flows within ducts and nozzles.
One of the earliest discussions of fire throttling by Greuer et al. [4] was published in 1973. The authors discussed their research on mine tunnels and suggested that when a fire is introduced in a tunnel, the presence of a fire results in additional head loss and pressure loss. A second notable publication by Hwang and Chaiken [5] published in 1978 discussed their research on the effect of a duct fire on the velocity of the air ventilation. This was followed by a publication in 1979 by Lee et al. [6] that documented small-scale duct fire experiments carried out to understand the effect of air flow in a duct fire.
The suggestions from these earlier researchers [4,5,6] indicate that the fire throttling effect is likely made of two main components: a localised flow resistance caused locally at the fire, and an increased resistance downstream of the fire.
Over the last 20 years, this issue has been detailed in various publications [7,8,9,10], and despite renewed interests in recent years [11,12,13], the literature describing this effect, including the understanding remains scattered and inconsistent. There have been several equations proposed to treat the fire throttling effect, and two of such equations are from CETU [7] and Dutrieue and Jacques [9] that consider the pressure drop directly at the fire, but not downstream of the fire. These two equations are examined in later sections, namely eqs. (28–29).
Despite this, it is acknowledged at a fundamental level in the various publications [7,8,9,10], and certainly in design considerations [14], that the occurrence of the fire throttling effect has a material impact in practical applications.
This is because the increase in flow resistance due to the fire requires extra fans to achieve the required critical ventilation velocity [13]. Whilst there is a safety buffer in the sizing of the tunnel ventilation system by oversizing the fan capacity, this is typically in the region of 5% fan capacity. This represents a volumetric increase of 3 m\(^3\) to 8 m\(^3\)/s in volume flow rate for a typical tunnel, and is inadequate to deal with any major losses that are not already accounted for in the design. Practitioners and tunnel designers will know it is impractical to simply increase the fan capacity by a larger margin because this would impact the sizing of the ventilation shaft in tunnel, and therefore the tunnel diameter, i.e. tunnelling cost. In a project, the sizing of the tunnel’s diameter can make or break the capital expenditure of a project.
In this research, we aim to amalgamate the conjectures published to date, and distill the fire throttling effect into a concise description. This description is presented in a one-dimensional model based on pipe flow principles that aims to incorporate the effects of a fire. We achieve this in our one-dimensional model by identifying the zones in the tunnel impacted by the fire, and proposing a specific model for each of these zones.
Using this description, we then evaluate their contribution to the fire throttling effect, and this is achieved by comparing the pressure losses calculated by the one-dimensional model to those obtained via CFD simulations. CFD simulations are chosen to verify the one-dimensional model due to the lack of experimental data obtained from simultaneous measurements of pressure and temperature that would be required to validate it.
Our secondary objective is to provide a description of the fire throttling effect that forms the foundation for practical application, or for further research. This is one reason why the one-dimensional model is based on pipe flow principles, i.e. the same principles routinely used in the analysis and design of longitudinally ventilated tunnels.
2 1D Modelling of Fire Throttling
Since the fire throttling effect is characterised by pressure losses, we will describe in this section a 1D model, based on the standard assumptions of pipe flow engineering theory [15], to calculate the pressure losses due to the fire in terms of the temperature distribution it generates along the tunnel.
For the sake of simplicity and ease of analysis, our modelling scenario is that of a single fire in a straight enclosed tunnel of constant section with only two openings: the entrance and exit portals. Flow quantities in the 1D model, such as flow velocity and pressure, are based on area-averaged values. As it is customary in these 1D models [3], we assume the momentum balance of the flow in the tunnel to be the sum of independent contributions of the form
where \(\Delta p_{k}\) represent pressure changes due to the various effects considered in the model. Terms of this form have been proposed to model the effect of wind, obstacles, wall friction, buoyancy, fans, inflow and outflow portals, and tunnel inclination amongst others.
This paper will focus on the terms that are the main contributors to pressure losses in a longitudinally ventilated tunnel in the presence of a fire. We will present and discuss formulations for those terms leading to the throttling effect, and assess their suitability by comparison with CFD results. In what follows we will consider only three independent contributions to the total pressure losses, \(\Delta p\), namely
where the terms in the right-hand side denote the pressure losses in the cold air zone of the tunnel, \(\Delta p_a\), the local pressure losses at the fire site, \(\Delta p_f\), and the pressure losses in the zone filled with hot smoke downstream of the fire, \(\Delta p_s\). The subindices a, f and s are shorthand for air, flame, and smoke, respectively. \(\Delta p_a\) and \(\Delta p_s\) are pressure losses distributed along the length of the tunnel whereas \(\Delta p_f\) is a localised pressure loss at the site of the fire.
3 Calculation of Pressure Losses
The calculation of the pressure losses in eq. (2) will utilize the notation of Fig. 2 in the following sections. This figure shows the domain split into three zones: a zone of cold air at the entrance of the tunnel upstream of the fire where we will assume the values of the flow variables are constant, a zone in the vicinity of the flame that will be assumed to be of negligible length compared to the length of the tunnel, and a zone of hot smoke downstream of the fire where its influence will be felt.
As stated in the previous section, our aim is to calculate the pressure losses corresponding to these three zones, i.e. \(\Delta p_a\), \(\Delta p_f\), and \(\Delta p_s\), respectively.
The distributed pressure losses in the tunnel contributing to the throttling effect are calculated through the pressure gradient calculated via the Darcy-Weisbach friction coefficient, \(\lambda\), using the formula
where \(D_h\) is the hydraulic diameter of the tunnel cross section, and the friction coefficient \(\lambda (\text {Re})\) is given a function of the Reynolds number, \(\text {Re}\), via the commonly used pipe flow engineering formulas [15]. Here we have adopted the explicit approximation to Colebrook’s formula for the friction coefficient [16], namely
where \(\varepsilon\) is the relative surface roughness in the Moody diagram.
The additional distributed friction generated in the hot smoke zone is accounted for through changes in velocity due to temperature as proposed in references [17, 18]. For an enclosed tunnel of constant cross-sectional area, temperature corrections are obtained by a combination of the continuity and the perfect gas equations leading to
Therefore, if the distribution of temperature, T(x), along the tunnel is known, equation (5) will be used to update densities and velocities according to
where the subindex a indicates again the (constant) values in the cold air zone in the tunnel. The form of the temperature distribution adopted in this work is described in the following section.
3.1 Temperature Distribution Along the Tunnel
As noted earlier, this calculation method for evaluating the pressure losses due to a fire relies upon specifying a temperature distribution. This section describes the temperature distribution adopted here.
Let x denote the coordinate along the length of the tunnel, in the direction of the incoming flow of air, with the fire source located at \(x=0\). We assume the minimum flow velocity is equivalent or greater than the critical ventilation velocity which allows us to neglect back-layering and plume deflection effects so that we can assume a temperature distribution of the form
where \(T_a\) represents the (constant) temperature in the cold air zone upstream of the fire, and \(T_s(x)\) represents the variation of temperature in the hot smoke zone downstream of the fire. The adopted form of \(T_s(x)\) will be discussed in Sect. 3.4. Here we are assuming that the presence of the fire leads to a jump in temperature at \(x=0\) with \(\Delta T = T_s(0)-T_a > 0\). The value of \(\Delta T\) is a function of the fire heat release rate (HRR).
Note that, if required, the effects of back-layering and plume deflection could be incorporated in the temperature distribution through empirical formulas such as those proposed in references [19] and [20], respectively. For now, we will proceed on the basis there is negligible back-layering.
We will now proceed to describe how to calculate the three contributions to the pressure losses given such a temperature distribution.
3.2 Pressure Losses in the Cold Air Zone
Following the notation of Fig. 2 and using the assumed temperature distribution, the pressure losses, \(\Delta p_{a}\), in the cold air zone (\(0 \rightarrow 1\)) are obtained by integrating the pressure gradient given by eq. (3) with constant temperature, \(T_a\), and therefore constant velocity. The pressure losses \(\Delta p_{a}\) are given by
where \(\lambda _a\) denotes the constant friction coefficient in the cold air zone. In the comparison with CFD results that will follow in the verification of the method to be presented in Sect. 5, the value of the surface roughness \(\varepsilon\) in eq. (4) is selected to match the (constant) pressure gradient of the computed solution in the cold air zone. This calibration ensures the friction due to cold air flow is the same in the 1D model and the CFD simulation. We recognise there may be uncertainties in the CFD models, and this calibration mitigates this because by matching the friction in the cold region between the 1D model and the CFD simulation, we have certainty any discrepancy is due to the temperature only.
3.3 Pressure Losses Across the Fire
We obtain two alternative expressions of the localised pressure losses caused by the fire, \(\Delta p_{f}\), through a conservation analysis using the control volume in the flame zone (\(1 \rightarrow 2\)) shown in Fig. 2. The first one relates \(\Delta p_{f}\) to the HRR of the fire, \(\dot{Q}\), and the second one to the temperature jump across the fire. This temperature jump can be obtained from semi-empirical formulas such as the plume theory which will be described in detail later in this section. The subindex 2 in the following derivations will denote the values immediately upstream of the flame zone which we recall it is assumed to be of zero length. For instance, \(\rho _2 = \rho _s(0)\) where \(\rho _s(x)\) is the density in the hot smoke zone as illustrated in Fig. 2.
Denoting by \(\dot{m}_f\) the mass flow produced by the fire, conservation of mass, or continuity, states that
where \(A_T\) is the (constant) cross-sectional area of the tunnel. Balance of momentum can be expressed as
where \(F_f\) is the pressure loss due to friction at the fire site. Finally the conservation of energy reads
where \(c_p\) is the specific heat capacity at constant pressure. Note in later sections we will only consider the contribution of the convective energy to the HRR \(\dot{Q}\) following reference [3]. We neglect fire mass flow, i.e. \(\dot{m}_f \approx 0\), with the assumption that fire size and the temperature are the main contributors to the fire throttling effect. The kinetic energy in the conservation of energy has been neglected on the basis that it is orders of magnitude smaller than the thermal energy [12]. The momentum source term due to buoyancy for the fire is neglected on the basis it is small compared to the momentum in the overall tunnel.
Separately, we are assuming that the friction losses at the location of the fire are negligible since the length of the fire location is small compared to the length of the tunnel, namely \(F_{f} \approx 0\) These three assumptions simplify the calculation methods. We can obtain the pressure losses due to changes in temperature caused by the presence of the fire in two alternative ways.
First, combining eqs. (9) and (10), the pressure losses can be written as
and substituting the ratio of velocities by the ratio of temperatures via eq. (5), noting that \(T_2 = T_s(0)\), we obtain the pressure losses as
The temperature \(T_s (0)\) can be calculated using the plume theory method as described in the later part of this same section. This version of the equation and calculation method is referred to as the plume theory method.
An alternative calculation of the pressure losses incorporates eqs. (9) and (10) into the energy eq. (11), together with eq. (5), to get
The final expression of the pressure losses as a function of the HRR, \(\dot{Q}\), is
This equation will be referred to as the energy equation method.
For the plume theory method in eq. (13), the value of the temperature jump due to the fire, \(\Delta T = T_s(0)-T_a\), can be calculated in two alternative ways.
The first one follows the suggestion by Ingasson [3] to estimate the average temperature at the fire source as originating from the convective part of the HRR. From the control volume analysis carried out earlier, and replacing \(\dot{Q}\) by its convective contribution \(\dot{Q}_c\), namely
where \(\dot{m} = \rho _a u_a A_T\) is the mass flow of air in the tunnel. The convective HHR, \(\dot{Q}_c\), is often assumed to be \(\dot{Q}_c = 2/3 \, \dot{Q}\) [3] which is the value that we will adopt hereFootnote 1.
The second one is obtained from a semi-empirical formula for the maximum temperature at the fire, \(T_{max}\), derived via the axisymmetric fire plume theory proposed by Li [19] as follows.
According to McCaffrey’s fire plume theory [22], the maximum ceiling temperature can be assumed to be flame temperature when the fire is sufficiently large and impinges on the tunnel ceiling. In other words, maximum ceiling temperature should be a constant. This constant value was found to be approximately 1350\(^\circ\)C based on several tunnel fire experiments [3].Footnote 2
Relating interaction of fire plume and ventilation flow is a crucial consideration in application of fire plume theory. Therefore, a dimensionless ventilation velocity, \(v'\), was defined [3] where both ventilation velocity, \(u_a\), and characteristic plume velocity, \(w^*\), can be correlated according to
where \(b_0\) is the equivalent radius of the fire source, and g is the gravitational acceleration.
In this model, the maximum ceiling temperature increment, \(\Delta T= T_{\max } - T_a\), is given in \(^\circ C\), by two separate formulas depending on the value of the non-dimensional ventilation velocity, \(v'\), namely
Finally we will obtain \(T_s(0)\) using the convective part contribution of the HRR, i.e. substituting \(\dot{Q}\) by \(\dot{Q}_c\), in the calculation the value of \(T_{\max }\) in the formulas above. Note that \(T_{\max }\) is the value of the temperature at the ceiling, given that we use it here as a proxy for the smoke temperature in all the perimeter of the tunnel section, we could expect pressure losses obtained with this parameter to be an upper bound.
3.4 Pressure Losses in the Hot Smoke Zone
The pressure losses, \(\Delta p_s\), in the hot smoke zone (\(2 \rightarrow 3\)) are calculated by integrating the pressure gradient once the velocity is written in terms of the temperature, according to eq. (6), as
Here we will consider the friction coefficient in the hot smoke zone, \(\lambda _s\), to be dependent on the velocity and thus on the temperature, therefore we will have \(\lambda _s(x)\). This means that the pressure gradient in the hot smoke zone, \(\frac{dp_s}{dx}\), will not be constant but a function of x of the form
where \(C_a\) is a constant. This expression, that relates the slopes of the pressure losses in the cold air and hot smoke zones of the tunnel, will be useful in analysing the results to be presented and discussed in Sect. 5. Note we have simplified this description by considering the deceleration of the flow and hence the recovery of static pressure to be negligible. For a longitudinally ventilated tunnel designed to minimise smoke back-layering, smoke is expected to be diluted (cooled) over a short distance from the fire, and therefore the temperature distance (cooling to the tunnel wall) over the remaining distance of the tunnel is not expected to be significant.
The temperature distribution in the hot smoke zone (\(x \ge 0\)) is considered as below. The adopted form of the temperature distribution, \(T_s(x)\), in the hot smoke zone (\(x \ge 0\)) is defined as
where the effect of the fire is assumed to be localised and represented as a sudden jump of temperature \(\Delta T= T_s(0)-T_a\), and the decay of the temperature upstream of the fire is represented by the function \(\mathcal {F}(x)\).
The temperature decay function \(\mathcal {F}(x)\) could be modelled using heat transfer assumptions as suggested by Ingason [3] and calculated as the solution of the heat equation, i.e.
which illustrates how the temperature decays as we move away from the fire in the direction of the flow. Note that \(h_t\) is the heat transfer coefficient (kW/m\(^2\)K), \(\pi D_h\) represents the wetted perimeter of the whole tunnel cross-section (m) and x is the distance from the fire along the tunnel (m).
Alternatively, one could adopt an empirical exponential form to fit an expression to experimental or field tunnel temperature data such as
where H is the height of the tunnel. This decay function has been generated from large-scale fire experiments [24] in tunnels, and the equation is documented in reference [3]. Equation 24 is used as a representative temperature profile that can be adopted in 1D calculations. This equation was chosen as it was derived from both the Runehamar and Memorial Tunnel fire tests and is found [3] to fit well to the experimental data. We acknowledge there may be more realistic or suitable temperature profiles that could be used. An investigation of the effect of different temperature profiles is outside the scope of this paper, but incorporating them in future analyses should be straightforward.
4 Summary of the Pressure Losses Calculations in the TE1D Framework
This section collects the formulas, presented in the previous sections, for the calculation of the pressure losses along the tunnel due to the throttling effect. These calculations, which will be employed in the 1D code TE1DFootnote 3 framework, proceed as follows.
In the cold air zone of the tunnel upstream of the fire (\(x < 0\)) the pressure losses are given by
At the location of the fire \(x = 0\), the localised pressure loss is calculated in two alternative forms. The approach based on the energy equation writes the pressure losses across the fire in terms of the HRR, \(\dot{Q}\), as
Alternatively, we could use eq. (13) with \(T_s(0) = T_{\max }\) as per eq. (22), leading to
This formula refers to ceiling temperatures and this is somewhat inconsistent with the use of area-averaged quantities in the one-dimensional theory in which this framework is based. We will see however in Sect. 5 that the values obtained this way provide an upper limit boundary of \(\Delta p_f\). In the following, we will refer to eq. (13) as the plume theory method and to eq. (26) as the energy equation method.
In the hot smoke zone, the pressure losses are calculated as
Given that the friction coefficient \(\lambda _s\) in the hot smoke zone will be in general a function of the location t through the velocity, that varies along the tunnel due to temperature changes as stated in eq. (6), numerical integration will be required to evaluate the integral in eq. (27).
An indicative sketch of the three contributions to the total pressure losses in the tunnel is depicted in Fig. 3.
5 Verification of the TE1D Framework Via Comparison to CFD Simulations
This section verifies the results from the 1D theory by comparison with CFD simulations obtained with OpenFOAM [12] and FDS 6.7.6 [26]. The objective of this comparison is to verify the consistency of CFD, and its suitability as a reference for the verification of the one-dimensional model, by considering two independently carried out simulations.
Briefly, FDS, or Fire Dynamics Simulator [26] is an open source CFD package based on incompressible LES, or large-eddy simulation, modelling and that is widely used by the tunnel ventilation community for fire and smoke modelling in research and practical applications. FDS is the primary simulation tool used in this paper. The OpenFOAM simulations have been carried out with FireFOAM, which is an application specifically designed for fire modelling, using a compressible LES model. More details on the FireFOAM simulations cited in this paper can be found in the work by Riess [12].
We have used CFD simulations because there is a lack of suitable experimental or field data from real fires with measurements of both pressure loss and temperature distribution along the tunnel which would be required for validating the simulation and analysis of the throttling effect.
Although some experimental and field data exist separately for either pressure or temperatureFootnote 4, to the best of our knowledge, there is no data available for both in the same configuration. Tunnel fire experiments remain limited, and we take this opportunity to encourage development of more tunnel fire experiments especially considering the large number of new tunnel infrastructure to be built in the future [32].
5.1 FDS vs OpenFOAM Comparison
We have compared the FDS 6.7.6 results to those modelled independently by Riess [12] using OpenFOAM. The FDS simulations model a 34 MW fire in a 600 m long rectangular tunnel at 10 m (w) \(\times\) 5.2 m (h) with a surface roughness of 2.5 mm. A methane fire is located at 100 m from the inflow portal, and the tunnel is longitudinally ventilated with an air velocity of 4 m/s. A uniform grid of 0.2 m is used noting the large fire sizes being modelled and therefore the grid is considered to be adequate. Adiabatic surface is used and is considered reasonable noting the simulations are run to reach steady state. The pressure profile in the FDS models are measured at fixed intervals as mean values across the cross section area of the tunnel.
The results in Fig. 4 show a reasonable agreement between the pressure losses calculated by OpenFOAM and FDS. The small discrepancies observed can be attributed to the difference in the method employed to measure the pressure drop. We have specifically chosen FDS 6.7.6 because its pressure solver has been modified to prevent the appearance of unphysical oscillations in the modelling of fires in long tunnels reported in previous versions [33, 34].
The subsequent three sections describe the evaluation of the terms \(\Delta p_a\), \(\Delta p_f\) and \(\Delta p_s\) in the TE1D framework and verify them by comparing their values against those obtained in CFD simulations.
5.2 Calibration of the Term \(\Delta p_a\)
The value of the pressure losses, \(\Delta p_a\), in the cold air zone upstream of the fire, depends on the surface roughness coefficient, \(\varepsilon\), in the friction factor given by eq. (4). Here we choose the value of \(\varepsilon\) that matches the pressure gradient in the cold air zone calculated by the TE1D model to the pressure gradient in both CFD simulations. Figure 4 shows that both CFD models produce the same pressure gradient in the cold air zone.
5.3 Verification of the Term \(\Delta p_f\)
This section compares the CFD results with those obtained using the energy and plume equations in the TE1D framework, i.e. eqs. (13) and (26) respectively, and with the semi-empirical formulas:
where \(C_1\) and \(C_2\) are empirical constants, \(\dot{Q}_c\) is the convective component of the fire HRR, u is the airflow velocity, and \(D_h\) is the hydraulic diameter of the tunnel cross section.
Formulas (28–29) have been proposed by CETU [7] and Dutrieue and Jacques [9] respectively, and their empirical constants \(C_1\) and \(C_2\) have values \(C_1 = 9 \times 10^{-5}\) and \(C_2 = 41.5 \times 10^{-5}\) s\(^{1.9}\)kg\(^{0.2}\)/m\(^{2.6}\).
Figure 5 shows a comparison of the values of \(\Delta p_f\) for different fire sizes calculated by TE1D, the semi-empirical formulas (28–29), FDS and OpenFOAM [12]. The main differences are the fire size and the ventilation velocities of the rectangular and arched tunnel profiles.
By considering the plume method and the energy method as an upper and lower bound, the comparison shows the TE1D prediction is within this boundary compared to CFD models. In practical applications where there can be uncertainties, in particular early on the project where 1D method is most likely used, we recommend if TE1D is used to predict \(\Delta p_{f}\), that TE1D plume theory is used. This is because the over prediction of the pressure drop will provide a level of safety buffer, and as per Fig. 5, TE1D energy equation under predicted the pressure drop when compared to the OpenFOAM values [12].
5.4 Verification of the Term \(\Delta p_s\)
The simulations of the pressure losses in the hot smoke zone show that the pressure gradient is approximately constant for all the fire sizes considered. Therefore, to verify the 1D model we have compared the values of the pressure gradient obtained by TE1D with those evaluated using FDS and OpenFOAM [12] for different fire sizes. Figure 6 shows the relative error of the value of the pressure gradient in TE1D with respect to the CFD value, which is used as reference, for a range HRR. Note that the eqs. (28–29) proposed by CETU [7] and Dutrieue and Jacques [9] respectively only account for localised pressure losses at the fire and therefore have not been used for comparison here.
The comparison in Fig. 6 shows for a fire size under 30 MW, the error is tolerable when viewed from a preliminary design for practical application perspective. The results show beyond 30 MW, the error increases significantly. Keeping in mind the only variable here is the fire size with the velocity and tunnel geometry remain consistent, we postulate temperature alone, when it comes to a larger fire size, is not the critical contributor to pressure loss in the hot smoke zone.
To confirm this, using the FDS model we obtained the average of the temperature distribution in the hot smoke zone downstream of a 34 MW fire, and derived a fitted temperature curve given by \(T_s(x) = T_a + 107\, e^{(-0.019x)}\). The corresponding pressure drop \(\Delta p_{s}\) is calculated using this fitted temperature distribution and it is shown in Fig. 7.
The results in Fig. 7 show with the fitted temperature curve, the slope is marginally steeper, i.e. closer to the steeper FDS slope, but the difference is negligible. This supports our suggestion for a larger fire the temperature is not the main contributor to the pressure loss in the \(\Delta p_s\) region.
Recall eq. 21 that relates to the slopes of the pressure losses in the cold air and hot smoke zones of the tunnel. Figure 8 shows the slopes for different fire sizes. The results show the effect of the additional pressure losses due to the increased temperature reduces materially at about 150 m away from the fire, which does not explain the significant difference in the slope shown in Figs. 6 and 7 for the bigger fires.
This is further reinforced by the plot in Fig. 9. This figure that shows that if temperature were the main contributor, we would expect the \(\lambda T\) curve to show a much larger difference between the TE1D temperature and the FDS fitted temperature curve, as opposed to a negligible difference in the region of 5 to 6 observed here.
The analysis so far shows with TE1D, the increased friction due to changes in velocity (increased in temperature) is sufficient to capture the effect of the fire for smaller fire sizes. However for larger fire sizes beyond 30 MW, the increase in temperature alone does not fully account for the pressure loss due to the fire throttling effect in the hot smoke region, \(\Delta p_s\).
As suggested by Riess [12], temperature stratification and the resultant shear stress to the tunnel walls appears to play a significant contribution to pressure loss in the \(\Delta p_s\) region. Figure 10 shows a comparison of the 2D velocity profile and smoke stratification for a small and a large fire, where the large fire can be seen to have much greater temperature stratification at the ceiling level.
Based on the above, this means for a 1D model and a large fire, e.g. beyond 30 MW, the increased temperature alone downstream of the fire is not the main contributor to the pressure loss. We surmise that a 1D model, when there is a sufficiently large fire where significant stratification is expected to occur, cannot capture the 3D effect of a fire, which is the bigger contributor to the pressure loss. This means when dealing with scenarios where large fires or where significant stratification are expected, additional corrections are required for a 1D model to correct for the prediction of pressure loss downstream of the fire, or \(\Delta p_s\). One example of a correction is proposed by Riess [12]. Alternatively, CFD models should be used in these scenarios.
Conversely, we have now identified a threshold value where 1D model, e.g. TE1D, holds up reasonably well for fire sizes up to 30 MW. We acknowledge the cases tested in this research may not be universal, and that a parametric study considering the tunnel geometry and other variables that impact the stratification beyond fire sizes should be considered.
That said, from a practical application perspective, especially for the early stages of a project where speed of computation matters more and that designers are only interested in an approximate tunnel ventilation requirement, 1D models such as TE1D can be considered to estimate the impact of fire throttling effect, in particular for smaller fire sizes, e.g. 5 MW to 15 MW that reflects a typical passenger car or metro train design fire sizes.
6 Conclusions
In this research, we have firstly amalgamated the previously fragmented understanding of fire throttling. We do this by using a one dimensional model. The model, implemented in the code TE1D, analyses the contributions to the pressure losses caused by the fire by splitting the tunnel length downstream from the fire into flame and hot smoke zones, and using the temperature distribution along the tunnel to account for the effect of the fire on pressure losses. The 1D model used here is based on a longitudinally ventilated tunnel, with adequate velocity such that back-layering can be minimised.
With the 1D model established, we then compared the prediction using this model to CFD models for varying fire sizes from 5 to 50 MW. The comparison shows the 1D model holds up well (within the predictions between TE1D Plume and Energy methods) in predicting the localised pressure drop at the fire location across the varying fire sizes. For the region downstream of the fire, the comparison shows 1D model predicts reasonably (approximately 10% error) for fire sizes up to 30 MW, and subsequently under predicts the pressure losses for large fire sizes beyond 30 MW.
By using a temperature curve derived from the CFD model, we have shown for larger fire sizes, the increase in temperature alone is not the main contributor for the pressure losses downstream of the fire. We believe the 3D effect of temperature stratification and the resultant stratification of shear stress effect on the tunnel wall could be a main contributor to the pressure loss. Additional corrections are needed to the 1D model to account for the full impact of the fire throttling effect for a larger fire beyond 30 MW where significant stratification is expected to occur.
For smaller fire sizes, we believe 1D model can be used in particular for earlier stages of design where engineers needed to prioritise approximating the fan thrust needed to overcome the losses expected in a tunnel.
We acknowledge the calculation methods presented here rely heavily on CFD models. It is well-known that the availability of only a small number of experiments and fire tests to validate CFD models is a challenge that the tunnel fire safety community has faced for a long time [33]. Unlike a safety critical but simple problem, the calculation of pressure losses is safety critical in the design of a tunnel ventilation system, and the presence of the fire throttling effect complicates the calculations.
With a safety critical and complex problem, this issue requires significantly more investment including tunnel fire tests to better understand the fire throttling effect, and to provide better validation benchmark. We strongly believe the tunnel fire safety community needs to continue promoting the importance of fire experiments to support better model validation, in particular as these computational methods are now the primary tools for tunnel fire safety design.
This article has gathered and analysed some of the ideas and methods proposed in the available literature to model the throttling effect with a view to gain a better understanding of the phenomenon and the limitations of these methods, and to develop a one-dimensional framework (our TE1D code) as a starting point for practitioners and researchers to build upon when considering the fire throttling effect.
We conclude with a quote from George Box: All models are wrong, but some are useful. This is a reminder on the importance to understand the limitations of models, including 1D models prior to using them. Furthermore, it is our belief that improved, more accurate, models would be developed and validated if full scale tunnel fire tests relevant to the fire throttling effect were to be performed and the acquired data made available to researchers and practitioners in the fire ventilation community.
Notes
The HRR ratio, \(\dot{Q}_c / \dot{Q}\), is not constant in general. For instance, the Austrian code RVS 09.02.31 [21] recommends a value of the HRR ratio of 0.85 for 5 MW fires and of 0.75 for 30 MW to 50 MW fires, suggesting that the ratio should be, at least, a function of \(\dot{Q}\) since as a larger fire causes higher temperature and more radiation.
We recognise the value of 1350\(^\circ\)C is high, given it is the maximum temperature and that a lower representative value of 900\(^\circ\)C has been reported in other fire plume and flames studies. We proceeded with 1350\(^\circ\)C [23] as we will show later on this provides an upper bound value when compared to CFD models.
The TE1D (pronounced as TED) framework is available as a MATLAB code and can be obtained from the Zenodo repository [25].
Abbreviations
- \(_a\) :
-
Subindex denoting values in the cold air zone upstream of the fire
- \(_f\) :
-
Subindex denoting values in the flame zone at the fire
- \(_s\) :
-
Subindex denoting values in the hot smoke zone downstream of the fire
- \(\Delta p\) :
-
Pressure losses [Pa]
- F :
-
Pressure losses due to friction [Pa]
- 1D:
-
One-dimensional
- 3D:
-
Three-dimensional
- HRR:
-
Heat release rate [MW]
- \(\rho\) :
-
Density of air flow [kg/m\(^3\)]
- u :
-
Longitudinal velocity [m/s]
- T :
-
Temperature [K]
- p :
-
Pressure [Pa]
- \(\dot{m}\) :
-
Mass flow rate [kg/s]
- \(A_T\) :
-
Tunnel cross-sectional area [m\(^2\)]
- \(c_p\) :
-
Specific heat capacity at constant pressure [kJ/kg K]
- \(D_h\) :
-
Hydraulic diameter of tunnel [m]
- \(h_t\) :
-
Total heat transfer coefficient [kW/m\(^2\)K]
- H :
-
Height of tunnel [m]
- L :
-
Length of tunnel [m]
- \(H_{\textrm{eff}}\) :
-
Effective tunnel ceiling height [m]
- \(T_{\max }\) :
-
Maximum temperature on tunnel ceiling [K]
- \(\dot{Q}\) :
-
Heat release rate [W]
- \(\dot{Q}_c\) :
-
Convective heat release rate [W]
- \(\dot{Q}^*\) :
-
Non-dimensional heat release rate [-]
- \(b_{0}\) :
-
Radius of fire source [m]
- \(v'\) :
-
Non-dimensional ventilation velocity [m/s]
- \(w^*\) :
-
Characteristic plume velocity [m/s]
- g :
-
Gravitational acceleration [m\(^2\)/s]
- \(\epsilon\) :
-
Relative surface roughness in the Moody diagram [−]
- \(\lambda\) :
-
Friction coefficient [−]
- \(\mathcal {F}\) :
-
Temperature decay function [−]
- \(C_1\) :
-
Empirical constant in formula for \(\Delta p_f\) [-]
- \(C_2\) :
-
Empirical constant in formula for \(\Delta p_f\) [s\(^{1.9}\)kg\(^{0.2}\)/m\(^{2.6}\)]
References
International transport forum: transport infrastructure investment and maintenance (2017). https://doi.org/https://doi.org/10.1787/g2g55573-en. https://www.oecd-ilibrary.org/content/data/g2g55573-en
Hurley MJ (ed) SFPE Handbook of Fire Protection Engineering, fifth edn. Springer, Berlin (2016)
Ingason H, Li Y, Lönnermark A (2015) Tunnel fire dynamics. Springer
Greuer R (1973) Influence of mine fires on the ventilation of underground mines. Open file report 74-73, US Bureau of Mines . USBM Contract Report No SO122095
Hwang C, Chaiken R (1978) Effect of duct fire on the ventilation velocity. Report of Investigations 8311, US Bureau of Mines
Lee C, Chaiken R, Singer J (1979) Interaction between duct fires and ventilation flow: an experimental study. Combust Sci Technol 20(1–2):59–72
Centre d’Études des Tunnels: Les dossiers pilotes du CETU – Ventilation. CETU (2003)
Collela F, Rein G, Verda V, Borchiellini R (2011) Multiscale modelling of transient flows from fire and ventilation in long tunnels. Comput Fluids 51:16–29
Dutrieue R, Jacques E (2006) Pressure loss caused by fire in a tunnel. In: 12th International Symposium on Aerodynamics and Ventilation of Vehicle Tunnels, pp 77–84. BHR Group, Portoroz, Slovenia
U.S. Department of Transportation (2001) Subway environmental simulation computer program, 4.1 edn. Federal Transit Administration
Hansen R (2020) Mass flow during fire experiments in a model-scale mine drift with longitudinal ventilation. Mining Technol 129(2):68–81
Riess I (2020) Aerodynamic resistance of fires in tunnels. Tech. rep, Riess Ingenieur-GmbH
Vaitkevicius A, Colella F, Carvel R (2016) Investigating the throttling effect in tunnel fires. Fire Technol 52:1619–1628
Bickel J, Kuesel T, King E (eds) (1996) Tunnel engineering handbook, second edn. Kluwer Academic Publishers, Netherlands
Idelchik I (2007) Handbook of hydraulic resistance, third edn. Jaico Publishing House
Genic S, Arandjelovic I, Kolendic P, Jaric P, Budimir M, Genic V (2011) A review of explicit approximations of Colebrook’s equation. FME Trans 39:67–71
Fleming C, Clark G, Meeks K, Wicht T (2016) The treatment of the throttling effect in incompressible 1D flow solvers. In: 8th International Conference on Tunnel Safety and Ventilation. Graz
Litton C, DeRosa M, Li JS (1987) Calculating fire throttling of mine ventilation airflow. Report of investigations 9076, US Bureau of Mines
Li Y, Ingason H (2012) The maximum ceiling gas temperature in a large tunnel fire. Fire Saf J 48:38–48
Tanaka F, Takezawa K, Hashimoto Y, Moinuddin KA (2018) Critical velocity and backlayering distance in tunnel fires with longitudinal ventilation taking thermal properties of wall materials into consideration. Tunn Undergr Space Technol 75:36–42
FSV: Tunnel ventilation systems – basic principles. Tech. Rep. RSV 09.02.31, Österreichische Forschungsgesellschaft Straße-Schiene-Verkehr (2014)
McCaffrey BJ (1979) Purely buoyant diffusion flames: Some experimental results. Tech. Rep. MBSIR 79-1910, National Bureau of Standards, Center for Fire Research
Drysdale D (2011) An introduction to fire dynamics, 3rd edn. Wiley, USA
Ingason H, Li Y, Lönnermark A (2015) Runehamar tunnel fire tests. Fire Saf J 71:134–149
Ang CD, Peiro J (2022) TE1D - Throttling Effect 1D Matlab Code (Version 1). Zenodo. https://doi.org/10.5281/zenodo.5831566
McGrattan K, Hostikka S, McDermott R, Floyd J, Weinschenk C, Overholt K. Fire dynamics simulator user’s guide. NIST and VTT Technical Research Centre of Finland, sixth edn. http://dx.doi.org/10.6028/NIST.SP.1019
Gong L, Jiang L, Li S, Shen N, Zhang Y, Sun J (2016) Theoretical and experimental study on longitudinal smoke temperature distribution in tunnel fires. Int J Thermal Sci 102:319–328
Ingason H, Li YZ (2010) Model scale tunnel fire tests with longitudinal ventilation. Fire Saf J 45(6–8):371–384
Li L, Li S, Wang X, Zhang H (2012) Fire-induced flow temperature along tunnels with longitudinal ventilation. Tunnell Underground Space Technol 32:44–52
Li YZ (2019) Study of fire and explosion hazards of alternative fuel vehicles in tunnels. Fire Safety J. https://doi.org/10.1016/j.firesaf.2019.102871
Lin P, Xiong YY, Zuo C, Shi JK (2021) Verification of similarity of scaling laws in tunnel fires with natural ventilation. Fire Technol 57(4):1611–1635. https://doi.org/10.1007/s10694-020-01084-9.
Anderson L (2021) The biggest tunnelling projects around the world in 2021 . https://www.international-construction.com/news/the-biggest-tunnelling-projects-around-the-world-in-2021/8013496.article
Ang CD, Rein G, Peiro J (2020) Unexpected oscillations in fire modelling inside a long tunnel. Fire Technol 56(5):1937–1941. https://doi.org/10.1007/s10694-020-01004-x.
McGrattan K, McDermott R (2021) Response to Unexpected oscillations in fire modelling inside a long tunnel by Ang, et al (2021). Fire Technol
Lin K (2019) 1D assessment of fire throttling effect in tunnel. Final year project report, Department of Aeronautics, Imperial College London
Acknowledgements
Preliminary explorations of the ideas presented in the paper were carried out by Kuan Lin as part of his final year project [35]. His valuable contribution to the work described in this paper is gratefully acknowledged.
Author information
Authors and Affiliations
Corresponding author
Additional information
Publisher's Note
Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.
Rights and permissions
Open Access This article is licensed under a Creative Commons Attribution 4.0 International License, which permits use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons licence, and indicate if changes were made. The images or other third party material in this article are included in the article's Creative Commons licence, unless indicated otherwise in a credit line to the material. If material is not included in the article's Creative Commons licence and your intended use is not permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly from the copyright holder. To view a copy of this licence, visit http://creativecommons.org/licenses/by/4.0/.
About this article
Cite this article
Ang, C.D., Peiró, J., Riess, I. et al. Analysis of Fire Throttling in Longitudinally Ventilated Tunnels With a One-dimensional Model. Fire Technol 58, 2925–2947 (2022). https://doi.org/10.1007/s10694-022-01285-4
Received:
Accepted:
Published:
Issue Date:
DOI: https://doi.org/10.1007/s10694-022-01285-4