1 Introduction

High-rise buildings of various structural systems are becoming more and more popular and common in urban cities due to population growth, land prices increase and lack of construction land (Al Agha et al. 2021). Therefore, it has been tried to make high-rise buildings safe and stable under different loads, especially when buildings are built on a site with poor geotechnical conditions in an earthquake-prone area. This is because the effects of horizontal loads on high-rise buildings are not linear but increase rapidly with the increase of the building height. For instance, under horizontal loads, the overturning moment of the structure is proportional to the square of its height, and the lateral deflection at the top of the structure is proportional to the fourth power of its height (Gao et al. 2005). As a result, with the increment of building height, lateral displacement will undoubtedly become the main controlling factor in the structural design. Additionally, the structure can deform in any direction under strong earthquakes, and sometimes the displacement can be large, so the key design problem is to avoid excessive deformation that will lead to building collapse.

In the traditional design method, the superstructure and the substructure are designed separately. On the one hand, the traditional assumption is that the superstructure is fixed at the base and the influence of soil–structure interaction (SSI) is ignored. Besides, the substructure is designed under the vertical load, horizontal load and moment deriving from the superstructure (El Ganainy and El Naggar 2009).

Actually, if the subsoil is stiff enough (e.g., buildings constructed on sound rock), the foundation input motion induced by an earthquake is basically identical to the free field motion and the rigid base assumption can be reasonable. In contrast, if the structure is rested on a soft soil medium, the seismic response can be different. Firstly, the foundation is capable to resist large deformations because of its rigidity. As a result, the foundation fails to conform to the deformations of surrounding soil and thus the input motion is inconsistent with free field motion. Secondly, the seismic response of the superstructure will probably cause deformation of the ground soil, which further modifies the input motion (Wolf and Deeks 2004). Therefore the seismic behaviour of the superstructure is influenced by the interaction between the superstructure and the underneath soil and a feedback loop will exist (Tabatabaiefar et al. 2013, 2017; Tabatabaiefar 2016; Far 2019; Al Agha et al. 2021). This feedback loop, in which the response of the soil affects structural behaviour and vice-versa is termed as SSI (Saleh et al. 2018; Anand and Satish Kumar 2018).

It is widely believed in previous studies that SSI is beneficial to the seismic behaviour of buildings since it elongates the natural period (Seed et al. 1976) and increases the damping of the system (Wolf 1985), which tends to reduce the seismic demand of structures. Therefore, many current structure design codes recommend reducing the overall seismic coefficient when considering SSI or completely ignoring SSI (NZS1170.5 2007; NBCC 2010; GB 50011 2010; IBC 2012). However, observations from a number of earthquake damaged sites proved that this design consideration is quite harmful. Take the 1985 Mexican earthquake as an example, a totally reverse result was noticed, wherein the soft subsoil resulted in a huge increase in the seismic forces (Sharma et al. 2018). In addition, remarkable examples including damage in pile-supported bridge structures and collapse of expressway can be found in Yashinsky (1998) and Mylonakis and Gazetas (2000). Recent studies have also justified this possibility. Although some investigations indicated that the SSI effects may reduce the structural response or seismic demand of structures (Liu et al. 2020; Scarfone et al. 2020; Ayala et al. 2022), more studies have shown the detrimental effects of SSI. Tabatabaiefar et al. (2013) and Hokmabadi et al. (2014; 2015) carried out a series of experimental shaking table tests and fully nonlinear numerical simulations to explore the effects of SSI on mid-rise reinforced concrete (RC) frame structures. Results indicated the SSI increased the lateral deflection and inter-storey drifts in the soil-foundation-structure model. Van Nguyen et al. (2017) established a 15-storey frame structure model to investigate the influence of the size and bearing mechanisms of piles on the seismic response of buildings numerically. The results revealed the maximum lateral displacements increased with the increase of the length of floating piles. Yang et al. (2020) performed a series of large-scale shaking table tests and found that compared with the fixed-base condition, SSI lightened the structural peak acceleration, story shear force, and elastic inter-storey drift. However, it amplified the overall displacement of the superstructure due to the large components of rocking and translational deformation. Nasab et al. (2021) investigated SSI effects on seismic retrofit of soft first-storey buildings. According to the results, SSI increased seismic response and seismic demand of retrofit devices, especially when the structure was founded on soft soils. Forcellini (2021) studied the effects of SSI on the seismic vulnerability of RC buildings with infill masonry walls. The results indicated SSI increased the failure probabilities of the building. Zhang et al. (2022) carried out seismic vulnerability assessments of a 20-storey steel moment-resisting frame building equipped with a tuned mass damper (TMD) considering SSI effects. It is observed that the TMD can significantly reduce the structural demands, while the SSI effects can increase the fragility of structures, especially under strong earthquakes. Kamal et al. (2022) investigated the effects of structure–soil–structure interaction (SSSI) and SSI on seismic behaviour of mid-rise high ductility RC buildings located on soft soil. The authors found that considering SSI increased the displacement demands by up to 15% compared to the fixed-base models.

Therefore it is noted that there are some contradictory opinions when SSI is considered in the structural design practice (Mylonakis and Gazetas 2000; Far and Flint 2017). It is the complexity of SSI and lack of consensus among researchers with regard to the influence of SSI that lead to very few structure design codes providing provisions related to it. Consequently, considering SSI in the design practice of the most common and worldwide prevalent building typologies has been a rarity (Anand and Satish Kumar 2018). In addition, it should be noted that previous studies have mainly focused on seismic response of mid-rise buildings as well as moment-resisting frame buildings. It should be noted that seismic response of mid-rise buildings are completely different from high-rise buildings In the same way, the seismic response of frame structures and frame-shear wall structures are also different since foundation rotation is significant for the latter (Sharma et al. 2018). Therefore, it is imperative to explore the seismic behaviour of high-rise buildings with different structural systems, superstructure geometry, and various foundation and soil types considering SSI.

In response to the need for critical investigation of SSI impacts, in this study, an enhanced numerical soil–structure model is adopted to investigate the effects of SSI on a typical high-rise building structure system: RC frame-core tube structure. The seismic behaviour of frame-core tube structures with different structure heights, height–width ratios, foundation types and soil types are studied. The results including maximum lateral deflections, foundation rocking, inter-storey drifts and base shears for the rigidly supported and flexibly supported structures are discussed and compared.

2 Overview of the structure–soil model

Three structural heights: 60 m (20 stories), 90 m (30 stories) and 120 m (40 stories) are considered in this study to cover the commonly used height range of high-rise buildings. Besides, the height–width ratios of the superstructure are four, five and six respectively, with three spans in each direction. Two prevalent foundation types: end bearing piled foundation and classical compensated foundation are adopted. The foundation embedment depth is assumed to be 9 m, with three basement stories. The bedrock depth is 30 m since most soil amplification effect occurs in the upper 30 m of the soil profile. For each structure–soil model, two far-field earthquakes and two near-field seismic records are applied. Therefore, a total of 252 cases (36 fixed-base cases and 216 flexible-base cases) were considered. The plan view of standard stories of frame-core tube structures is shown in Fig. 1a, which consists of the outer frame and the inner core tube.

Fig. 1
figure 1

Characteristics of frame-core tube structure a plan view of standard storey b 20-storey frame-core tube structure with end bearing piled foundation (height–width ratio = 6) c 20-storey frame-core tube structure with classical compensated foundation (height–width ratio = 6) d the finite-element model

By referring to AS3600 (2018) and AS1170.4 (2007), the structural sections of buildings with various heights and widths were designed in SAP2000 software. After that, nonlinear time history analyses under four seismic records (Fig. 2) was conducted to ensure inter-storey drifts of fixed-base structures with various parameters were less than 1.5% (life safe level). Grade 40 concrete with characteristic compressive strength (f’c) of 40 MPa, modulus of elasticity (Ec) of 32.8 GPa and unit weight of 24.5 kN/m3 (AS3600 2018) were adopted. In order to facilitate modelling in the subsequent finite element analyses, structures with the same height have the same dimensions of structural sections regardless of the height–width ratio. The dimensions of structural elements are summarised in Table 1.

Fig. 2
figure 2

Seismic records adopted in this study: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Table 1 Summary of dimensions of structural elements (m)

The superstructures are founded on soil deposits with different geotechnical characteristics, which are summarised in Table 2 (Tabatabaiefar and Fatahi 2014). The reason why the maximum shear-wave velocity of ground soil (Vs) adopted in this study is 600 m/s is that generally when the Vs is greater than 600 m/s, the influence of SSI is not significant (Tabatabaiefar et al. 2013).

Table 2 Parameters of the subsoil

Nowadays, the application of piled foundations for buildings has become increasingly common. The piled foundation generally transmits upper loads through the soft soil to the deep stiff soil or rock. In this study, end bearing piled foundation is adopted and all piles are rigidly connected with the base slab, and pile toes are fixed at the bottom of the soil to simulate the socket end of piles in bedrock (Fig. 1b). The arrangement and characteristics of the pile foundation have shown in Fig. 3 and Table 3. In addition, the classical compensated foundation was selected for comparison with the piled foundation model because the compensated foundation tends to induce larger foundation rotation, and the superstructure can produce more obvious lateral deflection. Therefore, this study employs classical compensated foundation and piled foundation with three basement floors overlying a 1 m-thick RC base slab (Fig. 1b and c). The requirements for bearing capacity and maximum settlement of these two foundation types are satisfied (Bowles 2001).

Fig. 3
figure 3

The pile arrangement used in this study

Table 3 Pile diameters and centre to centre distances

3 Numerical model

This section introduces the modelling method of the structure, foundation, subsoil and contact surface, the setting of boundary conditions and the seismic motion input method in finite element software Abaqus 6.14 (Dassault Systèmes SIMULIA 2012). In the next section, the direct method will be adopted to study the seismic response of high-rise frame-core tube structures with various parameters considering SSI.

3.1 Structural model

In order to improve computing efficiency, shell elements S4R are adopted to model shear walls and slabs and beam elements B31 are adopted to model beams and columns. Three-dimensional eight-node reduced integration element C3D8R are employed to simulate the basement, base slab and piles (Fig. 1d). The damping ratio of RC structures are assumed to be 5% and damping coefficients (α and β) are obtained based on the first and second natural frequencies of the structure (Van Nguyen et al. 2017). In addition, elastic-perfectly plastic behaviour is adopted in structural elements and yield stress is specified. The yield stress, Ec and density of concrete material are equal to the values introduced in Sect. 2.

3.2 Soil model

The soil element is modelled by solid elements C3D8R and the Mohr–Coulomb failure criterion is employed. To achieve this in Abaqus, cohesion and internal friction angle (Table 2) and the tension cut off option are specified.

In order to take into account the nonlinearity of subsoil, the cyclic shear strain (γc) depended shear modulus (G/Gmax) curves (Figs. 4 and 5) and damping ratio (ξ) curves (Figs. 6 and 7) provided by Sun et al. (1998) and Seed et al. (1986) are adopted for cohesive soils (De and Ee soil) and cohesionless soils (Ce soil), respectively. After that, trial and error were employed to calculate the strain-compatible values of soil damping and shear modulus under four seismic records (Fig. 2 and Table 4). The detailed steps of this process can be found in Tabatabaiefar et al. (2013) and Fatahi and Tabatabaiefar (2014). The soil strain-compatible parameters are presented in Table 5.

Fig. 4
figure 4

Shear modulus reduction curve of cohesive soils (after Sun et al. 1998)

Fig. 5
figure 5

Shear modulus reduction curve of cohesionless soils (after Seed et al. 1986)

Fig. 6
figure 6

Damping curve of cohesive soils (after Sun et al. 1998)

Fig. 7
figure 7

Damping curve of cohesionless soils (after Seed et al. 1986)

Table 4 Parameters of seismic records
Table 5 Adopted soil strain-compatible parameters and Rayleigh damping parameters

Rayleigh damping is adopted to consider the energy losses in the ground soil under the action of earthquakes. In this process, it is very important to select soil frequencies because it determines the damping coefficients α and β. In this study, the method introduced by Park and Hashash (2004) that the selection of soil frequencies should partially cover the main frequency range of the seismic record is used. Table 5 provides the Rayleigh damping parameters of subsoil calculated by this method.

3.3 Contact surface

Surface to surface contact (standard) in Abaqus is adopted to simulate the interaction between the foundation and surrounding soil during seismic loading. In this process, the master surface is the foundation surface, and the slave surface is the soil surface. This is because the mesh sizes of these two surfaces are similar, and the material of the foundation is stiffer. Besides, finite sliding formulation and surface-to-surface discretisation method are employed.

The contact interaction property includes two parts: normal direction and tangential direction. In the normal direction, the default relationship between contact pressure and clearance in Abaqus, hard contact, is applied, in which the amount of pressure that can be transmitted between the contact surfaces is not limited; when the contact pressure becomes negative or zero, the two contact surfaces will separate, and contact constraints on the corresponding nodes will be invalid (Van Nguyen et al. 2017). In the tangential direction, penalty friction formulation and contact-pressure-dependent data are adopted to simulate the Mohr–Coulomb failure model between the contact surface of foundation and soil.

3.4 Boundary conditions

In order to avoid the reflection of outward propagating waves on the boundary and capture the recovery ability of the semi-infinite ground, the viscous-spring boundary is applied on lateral and bottom surfaces of the soil domain. To achieve this goal, independent springs and dampers in one normal and two tangential directions were set on the boundary nodes (Gu et al. 2007), as shown in Fig. 8. The coefficients of the springs KT and KN and coefficients of dampers CT and CN (subscripts T and N indicate tangential and normal directions, respectively) can be calculated by the characteristics of the surrounding soil as follows:

$$ K_{T} = \alpha_{{\text{T}}} G/R,C_{T} = \rho V_{s} $$
(1)
$$ K_{N} = \alpha_{{\text{N}}} G/R,C_{N} = \rho V_{p} $$
(2)
Fig. 8
figure 8

Viscous-spring boundary

where αT, αN are modified coefficients, αT = 0.67, αN = 1.33 (Liu et al. 2006); R is the distance between the wave source and boundary nodes; ρ and G are the density and shear modulus of the subsoil, respectively; Vs and Vp are shear wave velocity and P wave velocity of the subsoil, respectively.

3.5 Seismic motion input method

After the viscous-spring boundary is applied, the artificial boundary node should conform to the free field motion to supply conditions identical to the infinite model. Generally, the one-dimensional free-field grid is set on the periphery of the model, parallel to the main grid, and connected to the main grid nodes through springs and dampers. However, this method will increase the number of elements, and it is difficult to implement in Abaqus due to a large number of boundary nodes. In this study, the free field motion is transformed into the equivalent node force Fb applied on boundary nodes (Ma et al. 2020), and Fb comprises three parts: the first two parts are used to compensate for the influence of springs and dashpots, and the third part is the free field stress on the boundary:

$$ {\varvec{F}}_{{\varvec{b}}} = ({\varvec{K}}_{{\varvec{b}}} {\varvec{u}}_{{\varvec{b}}}^{{\varvec{ff}}} + {\varvec{C}}_{{\varvec{b}}} {\varvec{v}}_{{\varvec{b}}}^{ff} + \sigma_{{\varvec{b}}}^{{\varvec{ff}}} {\varvec{n}})A_{b} $$
(3)

where ubff and vbff are free field displacement and velocity vectors at boundary nodes, respectively; σbff is the free field stress tensor; Kb and Cb are coefficient vectors of springs and dashpots on the boundary, respectively. Ab is the influencing area of boundary nodes and n is the cosine vector of the normal direction outside the boundary. By compiling a simple program in MATLAB software, the amplitudes of Fb in one normal direction and two tangential directions of each boundary node were obtained.

The validity and accuracy of the numerical model have been verified by comparison between experimental shaking table test results and numerical outputs by Zhang and Far (2021). After that, the seismic response of high-rise frame-core tube structures with various parameters considering SSI was numerically studied and the results can be found in Sect. 4.

4 Results and discussions

4.1 Maximum lateral deflection

Figures 9, 10, 11, 12, 13, 14, 15, 16 and 17 show the maximum lateral deflections of 20-, 30- and 40-storey structures with different height–width ratios, foundation types and soil types under the action of four seismic records. Compared with fixed-base counterparts, almost all the maximum lateral deflections of flexible-base structures have been amplified, regardless of the structural height, height–width ratios, foundation and soil types. This is because the degree of freedom of the soil–structure system increases after considering SSI and the natural period is prolonged, and the displacement response spectrum curve generally increases with the increase of the natural period of the system. As a result, the amplification of the displacement response of high-rise buildings was observed.

Fig. 9
figure 9

Maximum lateral deflections of 20-storey structure (height–width ratio = 6) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Fig. 10
figure 10

Maximum lateral deflections of 20-storey structure (height–width ratio = 5) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Fig. 11
figure 11

Maximum lateral deflections of 20-storey structure (height–width ratio = 4) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Fig. 12
figure 12

Maximum lateral deflections of 30-storey structure (height–width ratio = 6) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Fig. 13
figure 13

Maximum lateral deflections of 30-storey structure (height–width ratio = 5) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Fig. 14
figure 14

Maximum lateral deflections of 30-storey structure (height–width ratio = 4) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Fig. 15
figure 15

Maximum lateral deflections of 40-storey structure (height–width ratio = 6) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Fig. 16
figure 16

Maximum lateral deflections of 40-storey structure (height–width ratio = 5) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Fig. 17
figure 17

Maximum lateral deflections of 40-storey structure (height–width ratio = 4) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

It is also can be seen that when the superstructure parameters are the same, the maximum lateral deflections of piled foundation structures only change slightly with the type of soil, but the variation of displacement response of the classical compensated foundation structures is relatively dramatic, especially under the action of far-field earthquakes. This means that the end bearing pile foundation-supported structures is less susceptible to the type of soil.

In addition, the maximum lateral deflections of piled foundation structures are not necessarily smaller than that of classical compensated foundation structures. For example, under the action of far-field earthquakes, the deformation of piled foundation structures (with little difference between each other) is usually smaller than that of classical compensated foundation structures resting on the type Ee soil; however, under the action of near-field earthquakes, the deformation of piled foundation structures does not decrease obviously in comparison to classical compensated foundation structures. It is also worth pointing out that under the action of far-field earthquakes, with the soil type changes from Ce to Ee, the maximum lateral deflections of structures increase gradually, especially for classical compensated foundation structures. In contrast, under the action of near-field earthquakes, the deformation of structures usually decreases with the subsoil modulus decreasing.

The effects of the height–width ratio on the maximum lateral deflection are complex. On one hand, the increase in the width of buildings can increase the stability of structures and decrease the foundation rotation. On the other hand, the increase in the width means the increase in the mass of buildings, which will increase the inertial force and structural distortion in seismic excitations. Therefore, the maximum lateral deflection follows different patterns as the height–width ratio changes.

4.2 Foundation rocking

Different from fixed-base structures, lateral deflections of structures modelled with soil include rocking and distortion components (Kramer 1996). Tables 6, 7 and 8 record the proportion of the foundation rocking induced lateral deflection in the total deflection of the top floor of 20-, 30- and 40-storey structures, respectively. The restriction of structure width on the rotation of the structure is not significant, whereas the soil type can considerably restrain the foundation rocking, and this phenomenon is more obvious in classical compensated foundation-supported models. Similarly, the pile foundation can also effectively restrain the rotation of the foundation. For classical compensated foundation structures founded on Ee soils, the foundation rotation induced displacement accounts for an average of more than 90% of the total displacement, which means buildings are more likely to rotate overall. In contrast, this value is only 17.03% in the case of piled foundation models.

Table 6 The proportion of foundation rocking induced lateral deflection of 20-storey structures (%)
Table 7 The proportion of foundation rocking induced lateral deflection of 30-storey structures (%)
Table 8 The proportion of foundation rocking induced lateral deflection of 40-storey structures (%)

However, as observed in Sect. 4.1, although the end-bearing piled foundation can effectively reduce the foundation rocking, the maximum lateral deflections of piled foundation structures are not always smaller than that of the classical compensated foundation structures.

4.3 Inter-storey drifts

The inter-storey drifts of 20-, 30- and 40-storey structures with different height–width ratios, foundation types and soil types are shown in Figs. 18, 19, 20, 21, 22, 23, 24, 25 and 26. The inter-storey drifts were obtained adopting the method based on AS1170-4 (2007). Similar to lateral deflections, inter-storey drifts of almost all flexible-base cases have increased and the maximum value of many near-field earthquake cases and several far-field earthquake cases have exceeded 1.5%, which means the performance levels were changed from life safe towards near-collapse or collapse level after SSI is taken into account (BSSC 1997). In classical compensated foundation models, the inter-storey drifts usually present an approximately vertical line, indicating that inter-storey drifts only change slightly with the structural height. In other words, the foundation rotation induced lateral deflection accounts for a large part of the total maximum lateral deflection in the classical compensated foundation models. Moreover, compared with classical compensated foundation cases, inter-storey drifts of piled structures with the same height, height–width ratio and seismic record do not change significantly with the soil type. Besides, it is worth noting that a considerable increase of inter-storey drifts is found in structures resting on Ce soil under near-field earthquakes and structures with compensated foundations resting on Ee soil under far-field earthquakes. This is related to the difference between the shape of response spectra of near and far earthquakes.

Fig. 18
figure 18

Inter-storey drifts of 20-storey structure (height–width ratio = 6) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Fig. 19
figure 19

Inter-storey drifts of 20-storey structure (height–width ratio = 5) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Fig. 20
figure 20

Inter-storey drifts of 20-storey structure (height–width ratio = 4) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Fig. 21
figure 21

Inter-storey drifts of 30-storey structure (height–width ratio = 6) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Fig. 22
figure 22

Inter-storey drifts of 30-storey structure (height–width ratio = 5) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Fig. 23
figure 23

Inter-storey drifts of 30-storey structure (height–width ratio = 4) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Fig. 24
figure 24

Inter-storey drifts of 40-storey structure (height–width ratio = 6) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Fig. 25
figure 25

Inter-storey drifts of 40-storey structure (height–width ratio = 5) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

Fig. 26
figure 26

Inter-storey drifts of 40-storey structure (height–width ratio = 4) with various foundation types and subsoil types under different seismic records: a El Centro earthquake b Hachinohe earthquake c Kobe earthquake d Northridge earthquake

4.4 Base shear

Tables 9, 10 and 11 compare the base shear of flexible-base cases (\(\tilde{V}\)) and fixed-base cases (V). The ratio \(\tilde{V}\)/V is not always less than 1, which means the base shear of the structure may increase or decrease after considering SSI, depending on the foundation type and the soil type. For example, the base shears of the classical compensated foundation structures constructed on soft soils (type Ee and De) are usually less than that of fixed-base counterparts, while the base shears of the classical compensated foundation models resting on Ce soil and the piled foundation models are generally amplified. That means increasing the stiffness of the foundation and subsoil can absorb more seismic energy, making the traditional assumption that SSI can always reduce the seismic demand of the structure invalid. This result is consistent with Van Nguyen et al. (2017). Therefore, although the piled foundation can reduce the foundation rocking, it will probably increase the seismic shear force and in turn increase the lateral displacement of the structure, which also explains why the deformation of the piled foundation model is not necessarily less than that of the classical compensated foundation model in Sects. 4.1 and 4.3. In addition, although the absolute value of the base shear increases with the increase of the height–width ratio, the change of the height–width ratio will not exert a critical impact on the relative value of the base shear (\(\tilde{V}\)/V).

Table 9 Base shear ratio of 20-storey structures
Table 10 Base shear ratio of 30-storey structures
Table 11 Base shear ratio of 40-storey structures

5 Conclusions

In order to investigate the seismic response of the high rise frame-core tube structure considering SSI, 20-, 30- and 40-storey building models with different height–width ratios, foundation types and soil types were established using Abaqus software. The numerical simulation results including maximum lateral deflections, foundation rocking, inter-storey drifts and base shear of structures with different influencing factors are discussed and compared. The following conclusions can be drawn:

  • Compared to fixed-base cases, the maximum lateral deflections and the inter-storey drifts of almost all structures modelled with subsoil as flexible-base models are amplified to a different extent, regardless of height–width ratios, foundation types and soil types.

  • The maximum inter-storey drifts of many near-field earthquake cases and several far-field earthquake cases have exceeded 1.5%, which means the performance levels of structures have been changed after considering SSI. As a consequence, conventional design procedures excluding SSI may not be adequate to guarantee the structural safety of high-rise frame-core tube structures.

  • The piled foundation can effectively reduce the foundation rocking compared with the classical compensated foundation. However, the maximum lateral deflections of piled foundation models are the largest in many cases, especially under the action of near-field earthquakes. The reason is that the shear forces of piled foundation structures are generally larger than that of compensated foundation structures and fixed-base structures.

  • When the superstructure parameters are the same, the type of soil has minor effects on the deformation of the pile foundation structures, but it has dramatic effects on classical compensated foundation structures, especially under the action of far-field earthquakes. In other words, the seismic performance of piled foundation structures is less susceptible to the type of soil.

  • The stiff soil can considerably restrain the foundation rocking, and this phenomenon is more obvious in classical compensated foundation-supported models. For classical compensated foundation structures constructed on soft soils, the foundation rocking induced lateral deflection accounts for a large proportion of the total lateral deflection.

  • The base shear of the structure may increase or decrease after considering SSI, depending on the foundation type and the soil type. As a result, blindly increasing the stiffness of the foundation and subsoil may absorb more seismic energy, making the structure neither safe nor economical.

  • Although the absolute value of the base shear increases with the increase of the structural height–width ratio, the change of the height–width ratio will not exert a significant impact on the relative value of the base shear (\(\tilde{V}\)/V).