1 Introduction

Material deterioration, induced by corrosion, is a significant hazard to the durability of reinforced concrete (RC) structures and increases their vulnerability to seismic events (ASCE 2013). This is especially the case for those either in the marine environment or transport structures expose to de-icing salt (Chiu et al. 2015). Every year, trillions of dollars are spent worldwide on repair and maintenance of corroded RC structure (Schmitt 2009). The structural performance of RC structures could be affected by corrosion through (1) degradation of the mechanical properties of the corroded reinforcing bars, (2) debonding due to the reduced bond strength between the bar and the concrete, (3) damage in concrete caused by volumetric expansion of the corrosion products, and (4) a loss of concrete confinement due to corrosion of the confining reinforcement. As a result, the structural performance of RC structures is significantly affected by corrosion.

At material level, several researchers (Almusallam 2001; Du et al. 2005a, b; Kashani et al. 2013a, b, 2014; Zhu and François 2014; Fernandez et al. 2015; Kashani et al. 2015a, b; Zhang et al. 2015a; Balestra et al. 2016; Fernandez et al. 2016; Ou et al. 2016; Taha and Morsy 2016; Kashani 2017; Lim et al. 2017; Zhu et al. 2017) concluded that corrosion has a significant negative impact on the mechanical properties of reinforcing bars. Experimental material testing indicates that a significant decrease in both the yield and ultimate strengths of corroded rebars can be observed when the corrosion level is over 10% mass loss. As corrosion level increases, the ratio of the ultimate strength to yield strength of corroded bars ascends (Zhang et al. 2015a; Balestra et al. 2016; Ou et al. 2016). It is also observed by some researchers (Ou et al. 2016, Taha and Morsy 2016) that the yield plateau of the corroded bars is shortened or it even disappears when bars are heavily corroded (i.e. a reduction in total elongation of rebars). The nonuniform residual cross-section is more vulnerable to tensile loading compared with the symmetrical residual cross-section (Zhu and François 2014). Non-uniform pitting along the bar is reported as the key factor influencing the stress–strain behaviour of corroded reinforcing bars under both monotonic and cyclic loading (Almusallam 2001; Kashani et al. 2013a, b; Fernandez et al. 2015; Balestra et al. 2016; Fernandez et al. 2016; Zhu et al. 2017). Distribution of pitting also affects the inelastic buckling mechanism of the bars in compression (Kashani 2017). The tensile fracture of corroded bars observed by Kashani et al. (2013a, b) at the maximum pitted section of the corroded bar under cyclic loading, which is due to the combined impact of premature yielding in tension, inelastic buckling, and low-cycle fatigue degradation.

At the structural component level, some studies have been conducted on the structural performance of corroded RC components under static cyclic loading (Mangat and Elgarf 1999; Castel et al. 2000a, b; Webster and Clark 2000; Lee et al. 2003; El Maaddawy et al. 2005; Kallias and Rafiq 2010; Ma et al. 2012; Ou et al. 2012; Meda et al. 2014; Guo et al. 2015a, b; Li et al. 2015; Zhang et al. 2015b; Vu et al. 2016; Yang et al. 2016; Liu et al. 2017; Kashani et al. 2017a; Zhang et al. 2017; Dizaj et al. 2018a, b; Li et al. 2018; Rajput and Sharma 2018). They reported that corroded RC columns demonstrated a significant reduction in the ultimate load capacity and ductility. This degradation is attributed to the combined effect of corrosion-induced damage to both reinforcing bars and concrete. In some studies (Lee et al. 2003; Guo et al. 2015a), the reinforcing bars failed due to severe nonuniform distribution of pitting corrosion. In terms of energy dissipation capacity, Ma et al. (2012) reported that RC columns with mass loss ratios less than 14% have approximately the same cumulative energy dissipation capacity as uncorroded columns. However, Guo et al. (2015a) and Li et al. (2018) reported that RC columns with mass loss ratios around 5–15% have less energy dissipation capacity than uncorroded columns. Mangat and Elgarf (1999) pointed out that the flexural capacity of corroded RC beams is mainly governed by the degradation of the steel–concrete bond strength, while Castel et al. (2000a) found the mass loss of the tensile reinforcement is the primary reason accounting for the bar’s capacity degradation. Several researchers reported that the transverse reinforcement is more vulnerable to corrosion damage than the longitudinal reinforcement since they have less cover than the longitudinal reinforcement. This results in premature buckling of the longitudinal reinforcement and crushing of concrete core under lateral cyclic and/or axial loadings (Ma et al. 2012; Meda et al. 2014; Kashani et al. 2017a).

Several researchers (Alipour et al. 2010; Ghosh and Padgett 2010; Guo et al. 2015a, b; Ghosh and Sood 2016; Kashani et al. 2016a, b; Ni Choine et al. 2016; Di Carlo et al. 2017; Kashani et al. 2017a) have investigated the nonlinear static and dynamic responses of corroded RC bridges numerically. However, to date, there is no experimental data on the testing of corroded RC components under real dynamic earthquake loading. This is crucial to investigate the nonlinear dynamic response of corroded RC columns, and to validate the aforementioned numerical models.

1.1 Research significance and contribution

Although there have been numerous static experimental testing on corroded columns, there is a significant paucity of experimental data for the nonlinear dynamic behaviour of corroded RC columns in the literature. Accordingly, the aim of this study, and hence the main novelty of this work, is to bridge the gap between previously observed results in static experimental testing, and numerical models, by the experimental investigation of the impact of corrosion on the nonlinear dynamic response of corroded RC columns subject to real-time dynamic earthquake loading. The experimental results of static tests revealed that corrosion affects the ductility and lateral drift capacity of corroded columns. However, there is no experimental data on how this will affect the nonlinear dynamic response and dynamic characteristics of corroded columns. For example, nonuniform corrosion at cross-section levels might result in eccentricities in stiffness and damping that produce complex structural responses that are coupled in/out-of-plane even when subjected to in-plane seismic excitation. The resulting nonlinear stiffness and strength degradation, in this case of dynamic excitation, is impossible to capture using traditional quasi-static experiments.

The experimental programme consists of three lightly confined RC column specimens that represent columns of non-code conforming structures. One of the three columns is used as a control specimen (it is not corroded and is termed: UnCorr) and two columns are corroded with different mass loss ratios. A far-field (FF) long-duration ground motion record (Manjil earthquake) (see Kashani et al. 2017b for details of the ground motion selection procedure), is selected from FEMA (2009) and is used as input ground motion excitation to the shake table. The specimens are tested with ground motion intensity factors of 25%, 300%, and 500% to investigate the dynamic responses of specimens under slight, extensive and complete damage level, respectively. The experimental results show that corrosion changes the failure mode and significantly reduces the strength and drift capacity (plastic deformation capacity) of the corroded RC columns (about 50% mass loss results in about 80% strength reduction).

2 Experimental programme

2.1 Specimen preparation

Three lightly confined RC columns representing non-code conforming [i.e. Eurocode 8 (CEN.EN 2010)], bridge piers are constructed. The specimens are cast in a 1500 mm × 700 mm × 300 mm foundation. The columns have a square cross-section of 250 mm × 250 mm and 2300 mm height. It is worth mentioning that the aspect ratio is relatively large compared with typical bridge piers. This is because (1) the focus of these tests is on flexural dominant RC columns, and hence, large aspect ratio can guarantee the specimens will fail in flexure, and (2) due to the capacity limit of the shaking table, the axial load applied in this work cannot generate sufficient damage to RC columns with low aspect ratios. Eight reinforcing bars with a diameter of 16 mm are used in the vertical reinforcement. The transverse reinforcements are made of 8 mm diameter bars with 200 mm spacing along with the column height (as shown in Fig. 1). The ratio of the transverse bar/tie reinforcement spacing (confining reinforcement) and the diameter of the vertical reinforcement is 12.5, which are more spaced than recommended value of 6 in Eurocode 8 (CEN.EN 2010). The insufficient spacing of tie reinforcement makes the three specimens represent non-code conforming RC columns. The average concrete strength of 40 MPa is derived by compressive tests conducted on three concrete cylinders. All steel reinforcement used in these tests is manufactured under the requirement of the British standard B500 (2005). Three tensile, compressive and cyclic tests are conducted on sample longitudinal bars to characterise their mechanical properties including their stress–strain relationships. The mechanical properties of the longitudinal bars are summarised in Table 1. The identification of the three specimens is given in Table 2.

Fig. 1
figure 1

Reinforcement details of experimental test specimens

Table 1 Mechanical properties of the specimens before being corroded
Table 2 The identification of the specimens

2.2 Accelerated corrosion procedure (ACP)

Developing naturally corroded RC structures is a time-consuming process. It usually takes several years to achieve significant corrosion of the metal components of RC structures. To accelerate the corrosion process in the laboratory environment, some artificial techniques have been used by other researchers, including the external current method (El Maaddawy and Soudki 2003), pre-admixed chlorides (El Maaddawy and Soudki 2003) and cyclic wetting and drying (Otieno et al. 2016). In this study, an accelerated corrosion procedure (ACP) using the external current method is employed to corrode the reinforcement inside RC columns. The external current method makes use of electrochemical theory to form an electrolytic cell where a redox reaction can occur when external electrical energy is supplied. Specifically, the reinforcing bars act as an anode, the external metal electrode act as a cathode, and the sodium chloride solution act as an electrolyte.

A polyethene pipe with 500 mm diameter and 1000 mm height was mounted on the top of the foundation to create a bath for the sodium chloride solution. Four 250 mm × 1000 mm stainless plates are connected around the column as the cathode. Reinforcing bars and stainless plates are connected to the power supply by cables respectively. The sodium chloride solution contained 10% sodium chloride (i.e. salt). It is worth clarifying that no additional load (other than its own weight) is applied on the specimens during the procedure. The ACP setup is shown in Fig. 2.

Fig. 2
figure 2

Accelerated corrosion procedure setup

The corrosion process was monitored by measuring the current in the circuit. Faraday’s 2nd Law of Electrolysis illustrates the relation between mass loss and electric charge by Eq. (1). According to Eq. (2), the electric charge is determined by integrating the current over time. This method has been successfully used in other studies (Kashani et al. 2017a; Kashani 2017).

$$ \Delta {\text{m}} = \left( {\frac{\hbox{Q}}{\hbox{F}}} \right)\left( {\frac{\hbox{M}}{\hbox{z}}} \right) $$
(1)
$$ {\text{Q}} = \mathop \smallint \limits_{0}^{\text{T}} I{\text{d}}t $$
(2)

where \( {\text{Q}} \) refers to total electric charge, \( {\text{M}} \) refers to the molar mass of the anode (55.847 g for Fe), \( z \) is the ionic charge (2 electrons per Fe2+ in this case), \( I \) is the measured current of the circuit and \( T \) is the duration of corroding process. The ACP took 3 and 6 months for the Corr1 and the Corr2 specimens, respectively. During this period, the average measured currents are 1.39A (Corr1) and 1.37A (Corr2). Figure 3 shows the corrosion-induced damage to the RC columns after ACP. The horizontal and vertical cracks can be observed. This is because of the volumetric expansion of corrosion product resulting in internal pressure, which subsequently causes the concrete cover to crack along the reinforcement.

Fig. 3
figure 3

Corrosion-induced cracks in Corr1 and Corr2 specimens: a, b front and back of Corr1, and c, d front and back of Corr2

2.3 Shaking table test

The test programme is conducted on the shaking table facility at the University of Bristol. The table is 3 m × 3 m and equipped with eight hydraulic actuators to provide a full six degrees of freedom. In this study, ground motions are applied in one direction, uniaxially. The specimen is fully fixed on the centre of the table with four angles and two channels to prevent the footing from horizontal and vertical movement. In consideration of the capacity limit of the shaking table, three metal mass blocks (1 tonne each) are attached rigidly on top of the column to generate the inertia force as well as axial load due to the mass of the deck on the column. It was expected that the corroded specimens may collapse during the tests. Therefore, a supporting frame was constructed and deployed around the column. To reduce the seismically induced overturning moments of the elevated mass on the table, four metal mass (1 tonne) blocks were attached to the corners of the table surface. Thus, uncontrolled and unwanted rocking motion of the shaking table under uniaxial excitation was avoided. The setup of the experimental rig is shown in Fig. 4. Accelerometers and cable extension position transducers were deployed on the specimen and the shaking table to track the movement during the test. The layout of the instrumentation is shown in Fig. 5. Six accelerometers are attached to the shaking table to track the movement in all 6 degrees of freedom. An accelerometer (ACC1) is mounted on the foundation of the specimen to record the acceleration of input ground motion. Two accelerometers (ACC2&3) are attached at the top of the column to monitor the acceleration response in x and y directions. Two accelerometers (ACC6&7) are fixed on the mass block in positive and negative y-axis respectively to record the acceleration response on x-direction. The difference between the two acceleration time-histories can indicate the rotational movement of the specimen. Another two accelerometers (ACC4&5) are set on the mass block to track the out-of-plane movement of the specimen. An accelerometer is fixed on the supporting frame to validate that the frame is rigid relative to the columns.

Fig. 4
figure 4

Experimental test setup

Fig. 5
figure 5

Instrumentation layout

In the UnCorr column, a set of Linear Voltage Displacement Transducers (LVDT) were attached to the external face of the column to estimate flexural strains. However, the LVDTs were eliminated in the corroded columns as the extensive corrosion-induced damage to the concrete cover made these results unreliable as strain proxies.

2.4 Excitation ground motion

The ground motion used in this study is selected from a set of ground motions taken from FEMA P695 (2009), which were previously used in a numerical exploration study (Kashani et al. 2017b). The spectrally matched Manjil earthquake (1990) is displayed in Fig. 6a [the ground motion is spectrally matched to mean response spectrum of all FF ground motions listed in FEMA P695 (2009)]. Figure 6b shows the response spectrum of the excitation ground motion together with the fundamental period of the UnCorr test specimen. Since the period of the tests specimen is within the maximum response spectrum of the proposed ground motion, there is no need to time-scale the ground motion (i.e. reducing the ground motion duration).

Fig. 6
figure 6

Spectrally matched Manjil earthquake ground motion record: a acceleration time-series, and b elastic total acceleration response spectrum

The aim is to explore the progressive damage of the corroded RC columns in the case of a cascade of increasing intensity events. This philosophy is also aligned with the pragmatism of extracting the maximum information from each specimen. Therefore, this cascade of earthquakes is represented with a series of increasing amplitude ground motion with scale factors of 25%, 300%, and 500%. These increasing amplitudes excitation time-series qualitatively representing slight, extensive and complete damage limit states respectively. System identification using very low-amplitude white-noise tests was performed on the specimen before the test and after each intensity level experiment.

3 Experimental results and discussion

3.1 Mass loss measurement and spatial variability of corrosion

As mentioned above, the time-dependent corrosion induced mass loss is estimated by Faraday’s second law of electrolysis [see Eq. (1)]. It has been reported that Faraday’s law can give reliable values in lightly corroded specimens (El Maaddawy and Soudki 2003). However, the mass loss derived by Faraday’s law, in this context, estimates the average mass loss of all the steel in the electrical circuit; i.e. both vertical and tie reinforcement. Equation (1) estimates the expected mass loss (i.e. the mean) but does not estimate the spatial variability of corrosion along the height of the columns. Therefore, further investigation of the spatial variability of corrosion is needed. After the shaking table tests were completed, the tested columns were demolished, and corroded bars were carefully taken out from the column. The cleaning procedure adapted by Kashani et al. (2013a, b) was used to remove the corrosion products (rust) and concrete from the corroded bars. The actual mass loss is estimated by calculating the ratio of the mass per unit length of corroded bars to their corresponding original mass per unit length before corrosion. The average mass loss ratios of the vertical bars in Corr1 and Corr2 specimens are 51% and 65% respectively. To quantify the spatial variability of corrosion along with the height of the columns, the vertical bars are cut in 200 mm segments (tie spacing) as shown in Fig. 7. The mass loss ratio of each segment is calculated separately (shown in the “Appendix”). In each segment, the mass loss ratios of the four vertical corner bars (No. 1, No. 3, No. 5 and No. 7) and mid-face bars were calculated separately as shown in Fig. 8. It should be noted that this method cannot reflect the influence of bar necking and elongation during the test. Regarding this point, a novel real-time spatial investigation method on steel bars is needed to improve the shaking table test on corroded RC structures in the future.

Fig. 7
figure 7

Physical segments to investigate the spatial variability of corrosion

Fig. 8
figure 8

Spatial variability of corrosion damage at the lowest1m of corroded columns: a vertical bars in Corr1, b vertical bars in Corr2, and c transverse ties in both columns

Figure 8 indicates clearly that the mass loss in the corner bars (bars 1, 3, 5 and 7 in Fig. 7) is larger than mid-face bars (bars 2, 4, 6 and 8 in Fig. 7). This is because the corner bars are exposed to bi-directional chloride diffusion, while the mid-face bars are exposed to unidirectional chloride diffusion. The synergistic effect of two-sided chloride ingress accelerates the corroding process, which leads to more deterioration and even earlier failure of the corner bars. This phenomenon is reported by other researchers (Lee et al. 2003; Khan et al. 2017). Zhang et al. (2011) conducted an experiment on fly ash concrete with two and three-dimensional chloride ingress. This finding is consistent with those summarised by Zhang et al. (2011).

As mentioned before, the designated part of the column to be corroded is 1 m above the foundation. It can be observed that the corrosion level reduces with increasing height up the column in both specimens. In some part, such as segment 1 & 2 in Corr1 and segment 2 in Corr2, the bars have even disconnected after the corroding procedure. The same trend can be found on corroded tie reinforcement in both specimens. The outer face ties/transverse bars (see Fig. 7) appears to have failed during the corroding process. Some of the interface ties/transverse bars remained functional during the corroding process, namely the one in the higher part of the column. Figure 9 displays the ties extracted from the two columns. It is clear from these results that there has been a substantial loss of confinement and a reduction in the lateral restraint against buckling of the main vertical reinforcement. Therefore, the drift capacity and strength of the columns was substantially reduced by the corrosion.

Fig. 9
figure 9

Corrosion damaged transverse ties: a Corr1, and b Corr2

3.2 Influence of corrosion on nonlinear hysteretic force–displacement response

Using the recorded total acceleration and relative displacement (deformation) response time-histories of the tested specimen, the hysteretic cycles of force versus displacement are plotted and shown in Figs. 10, 11 and 12. The base shear is obtained by top block’s mass (3 tonnes) plus the modal mass of the column itself, multiplied by the total acceleration response and normalised by the gravity load on the column. The lateral displacement is normalised to the column height (drift). Figure 10 shows the 25% (slight damage limit state) ground motion amplitude case. The UnCorr column shows almost linear response (Fig. 10a), while both corroded specimens (Fig. 10b, c) exhibited nonlinear responses at the same excitation level. The hysteretic loops in the corroded specimen at this level of excitation are mainly due to the corrosion-induced damage in concrete cover. The peak displacement response of Corr1 and Corr2 columns are 580% and 460% of the peak displacement of the reference column. Figure 10c shows that the force–displacement response of Corr2 column is unsymmetrical. The investigation of the spatial variability of corrosion showed that the vertical bars (bars 1, 2 and 3 in Fig. 7) had more corrosion (see the table in “Appendix”), which resulted in an unsymmetrical hysteretic response. This non-uniform corrosion also resulted in some undesirable out of plane excitation of the corroded columns.

Fig. 10
figure 10

Force-displacement hysteretic response of all three columns at 25% excitation (slight damage): a Corr1, b Corr2, and c UnCorr

Fig. 11
figure 11

Force-displacement hysteretic response and observed damage of all three columns at 300% excitation (extensive damage): a hysteretic response of UnCorr, b hysteretic response of Corr1, c hysteretic response of Corr2, d observed damage in UnCorr, e observed damage in Corr1, and f observed damage in Corr2

Fig. 12
figure 12

Force-displacement hysteretic response and observed damage of UnCorr and Corr2 columns at 500% excitation (complete damage): a hysteretic response of UnCorr, b hysteretic response of Corr2, c observed damage in UnCorr, and d observed damage in Corr2

This is because the additional corrosion in the corner bars results in further corrosion-induced concrete cover cracking (as shown in Fig. 3), and hence, a significant reduction in concrete strength. Therefore, concrete cover crushes earlier on one side of the column, damage the reinforcing bars earlier, and hence, produces larger cyclic force–deformation loops. The corrosion-induced material (concrete cover and reinforcement) degradation also leads to the reduction of stiffness, which accounts for the larger displacement response observed in the two corroded specimens.

Figure 11 shows the force–displacement response of all three columns together with observed visual damage on tests specimen at this 300% excitation level. Figure 11a shows that the Corr1 column collapses completely at the time of 10 s. About 90% of lateral strength reduction is observed compared with the UnCorr control specimen. The Corr2 column (Fig. 11b), despite a slightly higher corrosion level (in terms of mass loss), experiences severe damage without a complete collapse. Note that the mass loss measurements are averaged over 200 mm length of rebar. Therefore, it does not directly reflect the highly localised weakest point of the corroded RC columns. The spatial variability of pitting corrosion in vertical bars and tie reinforcement can greatly influence the failure mechanism of severely corroded RC columns.

The force–displacement response of the Corr2 column at 300% does not show the typical hysteretic response of RC components such as Lehman et al. (2004) and Kashani et al. (2019). During the test, at 300% excitation, some of the vertical bars fractured (due to a combination of pitting corrosion, tensile strain level, and low-cycle fatigue). Therefore, the response of Corr2 does not show the hysteretic response of a typical RC column. It was observed that the column was pivoting between the edges similar to a rocking column, and hence, resulting in concrete crushing in compression. In the hysteretic rocking response (Fig. 11c), force increases without an increase in displacement until it rocks, and as soon as the joint opens force significantly drops; i.e. negative stiffness (Makris and Vassiliou 2014). A rocking column system is typically characterised by a linear negative slope (negative tangent stiffness) of the force–deflection response (during the rocking phase). This negative tangent stiffness is observed in Fig. 11c in the high amplitude loops (for positive displacements). Furthermore, Fig. 11c shows that the hysteretic response is not symmetrical, which is due to a single-sided opening rocking which contains both in-plane and out-of-plane components. Figure 11d shows the observed damage in the UnCorr column, which is mainly due to inelastic buckling of vertical bars and premature crushing of core concrete. Figure 11e, f shows the observed damage in Corr1 and Corr2 columns. Figure 11e shows that the complete collapse of Corr1 column is due to a severe loss of vertical reinforcement due to corrosion as well as corrosion-induced damage to the surrounding concrete. Figure 11f shows that the damage in Corr2 column is mainly at one side of the column, which justifies the unsymmetrical hysteretic response in Fig. 11c.

Figure 12 shows the force–displacement response of UnCorr and Corr2 columns (the Corr1 column collapsed at 300% excitation) together with observed visual damage on tests specimen at 500% excitation level. Figure 12a shows the force–displacement response of the UnCorr level at the 500% excitation level. The hysteretic response shows severe cyclic degradation, which is due to the inelastic buckling and low-cycle fatigue of vertical reinforcement. Figure 12b shows that at the 500%, the Corr2 column exhibits an erratic force–displacement response, which includes an increasing residual tilting until the complete collapse at a time of 13 s. 80% lateral strength reduction is observed compared with the UnCorr control specimen. This is before it is subjected to the largest-amplitude pulse of the ground motion. Figure 12c shows the observed damage in UnCorr column after the 500% excitation. The visual inspection of damage indicates that severe buckling of vertical bars in lightly confined columns which resulted in the premature crushing of core concrete previously at 300% excitation level results in severe buckling and large residual drift in the UnCorr column after the experiment. This consequently results in severe degradation in the hysteretic response of the column. Figure 12d shows the completely collapsed Corr2 column at 500% excitation, which shows the unsymmetrical failure of the column. This is due to the unsymmetrical corrosion of vertical bars.

A further comparison of the results is provided in Fig. 13. It shows the hysteretic curves of all three columns at 25% excitation amplitude for the strong motion part of the response. It is evident from Fig. 13 that severe corrosion can result in a significant reduction in effective stiffness of RC columns. The severe reduction in stiffness results in an increase in drift, which subsequently results in the premature yielding of the longitudinal reinforcement and crushing of the cover concrete (as shown in Figs. 11, 12). The effective stiffness of the column greatly influences the dynamic properties of the structure as well as the strength and plastic deformation capacity, which all have a significant influence on the energy dissipation capacity of RC columns under earthquake loading. In the following sections of this paper, we will quantitatively investigate the impact of corrosion on the effective stiffness and cumulative damage (energy dispassion) of the test specimens.

Fig. 13
figure 13

Comparative force–displacement responses of all columns at 25% excitation level

3.3 Impact of corrosion and seismic damage on stiffness degradation and modal frequencies

A transfer function estimate (based on both system input and output) is used to identify the current state of the system before and after every test. From this system identification, it is possible to estimate the combined influence of corrosion and structural damage on the system’s natural frequencies and damping ratios. Therefore, a long duration (150 s) low-amplitude white-noise tests are conducted prior to the first experiment and after each excitation level experiment. The amplitude of 0.0043 g of the white-noise signal was chosen to avoid causing any significant concrete crack opening. This amplitude represents approximately 1% of PGA of the Manjil record (in Fig. 6). Therefore, the aim of these white noise tests was to produce a non-destructive system identification.

Power Spectral Density (PSD) of structural time-history records can extract structural characteristics in the frequency-domain (Cryer and Chan 2008). The transfer function (based on input and structural response accelerations time-series) are estimated using a MATLAB (1994–2018) toolbox (Vold et al. 1984), which employs Welch’s algorithm (1967). Large peaks of the transfer function estimate modal frequencies. In this study, only the first and second modes are considered as shown in Fig. 14. Since the Corr1 specimen collapsed at 300% excitation, the white-noise tests data are not available at and beyond 300% excitation for this column.

Fig. 14
figure 14

Transfer function estimate of test specimens using the low-amplitude white noise excitation: a Corr1, b Corr2, c all three columns, and d UnCorr and Corr2 after 300% excitation

Table 3 summarises the natural frequencies (mode 1&2) variation of the three specimens. The natural frequency (mode 1) of the UnCorr column is about 10% higher than the natural frequency of the corroded columns before the shaking table experiment. This shows that corrosion damage has some influence on the natural frequency of the corroded RC columns. After slight damage excitation level (25% of PGA), all specimens exhibit further degradation in the frequency of their vibration modes. The natural frequency of the corroded columns reduces more rapidly than the UnCorr column. This is due to severe corrosion-induced damage. In contrast, the UnCorr column remains notionally elastic (see Fig. 10a). As expected, Fig. 14a, b shows a reduction in frequencies of columns after the earthquake excitation. Figure 14c shows the UnCorr column has higher natural frequencies than that of the Corr1 and Corr2 columns. However, Fig. 14d, unexpectedly, shows that after the 300% of PGA excitation test, column Corr2 has a higher frequency than the UnCorr column, which would appear to be counter-intuitive. It is worth noting two points here (1) the force–displacement plots shown in Fig. 11 and post-experimental forensic examination indicate rebar fracture and a change system typology from flexural to a rocking column and (2) the amplitude of the white noise excitation may not have been sufficient to elicit rocking due to additional friction-interlock between aggregate and corrosion products. This resulted in increased stiffness in the case of low amplitude excitations. The non-destructive (low-amplitude) white noise system identification tests characterise the system well for the case of systems with low levels of damage. However, in this case (Corr2 after 300% of PGA) we have a critically damaged column whose system characteristics are very sensitive to response amplitude levels. Therefore, if the aim is to characterise the extent of damage of a highly corroded/damaged system, then in situ ambient (low amplitude) system identification tests can produce ambiguous results that are suggestive of smaller damage then is actually present.

Table 3 Natural frequencies of the specimens obtained by white-noise tests

Stiffness degradation is an important indicator of structural damage under seismic excitation. During earthquakes, RC structures lose their strength and stiffness due to concrete cover spalling, core concrete crushing, reinforcement yielding/fracture in tension (due to large strain and/or low-cycle fatigue degradation), and inelastic buckling in compression. As it is qualitatively shown in Fig. 13, corrosion has a significant negative impact on effective the stiffness of RC columns. Here, we will quantitatively show the stiffness degradation of test specimens during the earthquake excitation.

Given the base shear force and displacement response of column time-histories, a least-square linear fit over a moving window can be used to estimate the time-stiffness and time–frequency relationship during a test. A smoothing low-pass filter is also employed. This is, in effect, an autoregressive moving average (ARMA) type approach, which results in an instantaneous stiffness time-series. As the window length in the ARMA process increases the underline trend becomes smoother. However, this increased noise attenuation comes at a cost of a loss of the resolution in time. A reasonable compromise is obtained for these specimens with a window length between 3 and 9 s. Figure 15 shows the estimated time-varying stiffness and frequency responses for the two corroded columns and the uncorroded control column at 25% excitation amplitude (corresponds to Fig. 13). The ARMA method requires force and deflection response time-histories to obtain predominant time–frequency trendline during the earthquake. The results for the uncorroded column exhibit more noise in the time-series. This is mainly due to epistemic noise in the displacement measurements during the low amplitude vibration parts of the experiment. Note that the uncorroded column displacements (at 25% of PGA) are smaller than those of the corroded columns.

Fig. 15
figure 15

Time-varying frequency and stiffness responses of all columns: a timefrequency response, and b time-stiffness response

3.4 Time-cumulative damage analysis

The cumulative energy dissipation is an important quantitative indicator of cyclic degradation of a structure subjected to seismic excitation. Cumulative energy dissipation is defined as the integration of the area inside hysteretic force–displacement loops (Chopra 2007). In this study, the cumulative energy dissipation of two corroded RC columns and the UnCorr control column at slight (25%) and extensive (300%) damage excitation levels are estimated. The results are normalised by the total dissipated energy of the UnCorr control specimen in each round of the test (shown in Figs. 10, 11, 12). Corroded columns Corr1 and Corr2 exhibit 1.53 and 1.75 times the energy dissipation of the UnCorr column at (25% of PGA). At the 300% of PGA level, both corroded columns are highly damaged and appear to dissipate much smaller energy than the UnCorr column. Column Corr1 technically fails at 10 s and would completely collapse if not for the support frame. Column Corr2 as previously discussed has transited from a flexural to a rocking typology and is also very near to collapse. This shows, that corrosion results in premature plastic deformation in the corroded columns and hence higher energy dissipation at low-amplitude excitation (Fig. 16a). However, owing to the corrosion-induced reduction in strength and plastic deformation capacity, there is a severe reduction in energy dissipation capacity at large amplitude excitation (Fig. 16b).

Fig. 16
figure 16

Normalised cumulative energy dissipation of the uncorroded and corroded columns: a slight damage excitation (25%), and b extensive damage excitation (300%)

4 Conclusion

This paper presents a set of shaking table tests on an UnCorr and two corroded RC columns to investigate the impact of corrosion on the nonlinear seismic performance of RC bridge piers. The two specimens are corroded using an accelerated corrosion procedure. They are tested under a far-field ground motion with increasing intensity scale factors until complete collapse. Spatial variability of corrosion, nonlinear hysteretic response, and structural stiffness and strength degradation are evaluated using the test results. Furthermore, time-varying stiffness analysis is conducted on the corroded and UnCorr columns and compared with each other. The experimental results showed a large scatter of data, which is due to the limitation in the number of experuimental test specimens, which requires further experimental testing in the future research. Nevertheless, this study provides a useful benchmarch experimental data that can be used in futur research by other researchers. The main findings of this research can be summarised as follows:

  1. 1.

    The pitting corrosion is spatially nonuniform along with the height and cross-section of the RC columns. In this study, it is observed that the pitting corrosion in the vertical bars varies along with the column height. Furthermore, corner bars have more corrosion due to the two-dimensional diffusion of chloride ions. Some of the vertical rebars have corroded completely resulting in a broken (disconnected) segments of rebar imbedded in the concrete. The exterior tie reinforcement (with some failing) is more significantly corroded than the internal tie reinforcement as they are closer to the concrete surface.

  2. 2.

    The heavily corroded RC columns show significantly larger displacement responses than the UnCorr control column under the same seismic excitation, which is due to the corrosion-induced stiffness degradation. Premature nonlinear response and stiffness degradation can be detected when the seismic intensity is low, while the UnCorr control column with the same design remains elastic. The ultimate strength of the RC columns also significantly reduces by the corrosion damage (about 50% mass loss results in about 85% average reduction in this work).

  3. 3.

    Corrosion has a significant impact on the energy dissipation capacity and cumulative damage of RC columns in an earthquake with moderate intensity. It can be demonstrated that severely corroded RC columns exhibit far less energy dissipation capacity compared with UnCorr RC columns at high-amplitude excitation. This is primarily because at these excitation levels the presence of fractured corroded reinforcement permitted these columns to evolve their structural typology from a flexural inelastic column into a rocking column.

  4. 4.

    At small amplitude excitation levels, the UnCorr columns exhibit linear elastic responses while the corroded columns exhibit inelastic behaviour with unsymmetrical hysteretic force–displacement loops. Consequentially, at these small amplitude levels, the corroded columns exhibit large energy dissipation (a 50% increase in energy dissipation) than the UnCorr column. This shows that even small magnitude earthquakes, which normally do not result in any significant damage in RC bridges, can result in severe damage in corroded RC bridges.