1 Introduction

The island of Hispaniola, shared by the Dominican Republic and Haiti (Fig. 1), is located in a subduction zone between the North America plate and the Caribbean plate. There are 13 geological faults in the interior of the island (Fig. 2), some of which have shown the potential to generate earthquakes of magnitude 7.0 and higher (Delanoy 1995; O’ Reilly et al. 2004). Thus, the whole island is considered to be a high seismic risk region (De León 2005). In the past 100 years, several earthquakes have affected both parts of the island (Table 1). In the case of the Dominican Republic, two earthquakes have occurred in the last decades: a magnitude 8.1 earthquake on August 4, 1946, north of the Samaná Province, which caused a tsunami, soil liquefaction, and the loss of about 100 lives; and a magnitude 6.5 earthquake on September 22, 2003, which occurred around midnight in the city of Puerto Plata, causing great damages in infrastructure (Almeida 2011). Among the observed effects, the partial and total collapse of several school buildings stands out (López and Martínez 2003).

Fig. 1
figure 1

Image adopted from Google Earth

Location of the Hispaniola Island.

Fig. 2
figure 2

Adapted from (COE 2009)

a Tectonic plate locations and b seismic faults in the Hispaniola Island.

Table 1 Seismic records of La Hispaniola Island from 1911 to 2010

Within the affected school buildings can be mentioned La Reforma School which experienced the collapse of the first floor level (Fig. 3a) and the partial collapse of its roof slab (Fig. 3b); José Dubeau High School, with the complete collapse of a two-level annex (Fig. 3c); and the San Marcos School in which several columns were affected by the short column effect.

Fig. 3
figure 3

Affected school buildings after the 6.5 Puerto Plata earthquake: La Reforma School: a collapse of the first floor level, b partial collapse of the roof slab and partial failure of the beam–column joint. José Dubeau High School: c complete collapse of the school annex. And San Marcos School: d several columns were affected by the short column effect

Also, damage in schools not only occurred in the city of Puerto Plata. According to a post-earthquake assessment carried out by the northern region of the Dominican College of Engineers, Architects and Surveyors (aka CODIA, Spanish Acronym), 44 schools experienced structural and non-structural damage in the city of Santiago (CODIA 2003). However, despite of the observed damage, only the death of a person who was staying overnight in a motel that collapsed was recorded (Almeida 2011). If the earthquake had occurred during the day, a great national tragedy could have happened, where the victims would have been counted by thousands.

2 Previous studies

In the Latin American region, school buildings are of great importance since, in addition to teaching, they are used as shelters in the face of natural phenomena such as hurricanes and earthquakes. Such importance has been recognized by international organizations such as the Organization of American States (OAS), United Nations Educational, Scientific and Cultural Organization (UNESCO), and Educational Concerns for Hunger Organization (ECHO) which have financed projects focused on the reduction in vulnerability of school buildings in several Latin American countries such as Mexico (Gómez 1987), Ecuador (Argudo et al. 1992), and through the Program for the Reduction of the Vulnerability of the Education Sector to Natural Hazards (PRVSEPN, Spanish Acronym) (OEA 1992), other countries such El Salvador, Nicaragua, Belize, Costa Rica, Guatemala, Honduras, and Panama (Wong et al. 1997).

Additionally, the evaluation of structural vulnerability of school buildings has focused the attention of researchers worldwide and hundreds of studies have been carried out around the world in terms of earthquake damage reports and vulnerability assessments of school buildings (Rodgers 2012). One of the countries in which more research has been conducted in last decades is Italy, since several earthquakes have strongly affected the school buildings recently and extensive damage has been observed in such structures (L’Aquila 2009: EEFIT 2009; EERI 2009; Molise 2002: Augenti et al. 2004). In the last decade, some of the conducted research has been focused in the assessment of damaged school buildings by means of qualitative method (Formisano 2012); the evaluation of retrofit schemes (Formisano et al. 2017) and the use of detailed advance numerical modeling techniques (Maracchini et al. 2017 and O’ Reilly et al. 2019). Formisano (2012) assessed qualitatively 15 school buildings located in several municipalities of San Pietro, Italy, that were affected by the earthquake occurred on May 20, 2012. The results of the study indicated that all the evaluated structures showed structural schemes and constructive details that did not comply with the current Italian seismic code. It is recommended to retrofit such structures using simple schemes such as the casing of masonry walls with steel plates, as well as the use of tie beams to improve the connection between the walls, among others. Likewise, Formisano et al. (2017) examined the seismic performance of a retrofitted existing reinforced concrete school building, located in Naples, Italy. Such structure was composed by several modules and was designed for gravity load only. One of the modules was retrofitted with different techniques, with the objective of assess the behavior of each technique and select the best one in terms of economic, structural, and environmental point of view. It was found that the best retrofit solution was the buckling-restrained braces. The influence of different modeling choices and material properties uncertainties on the seismic assessment of an existing RC school building was evaluated by Maracchini et al. (2017). The authors found that mechanical properties of concrete and steel strongly affect the seismic risk index. Also, the authors pointed out that the concrete columns’ mechanical properties have large impact on the seismic response of the building. Likewise, O’ Reilly et al. (2019) assessed the behavior of four typical school structures in Italy, applying some of the most up-to-date guidelines for the evaluation of seismic performance of structures. The evaluation included the development of detailed numerical models and the use of sophisticated analysis tools, which included an incremental dynamic analysis. The models were validated and calibrated from the results obtained from the measurement of ambient vibrations. From the results of their evaluation, the authors recommend to practitioners’ engineers take care of their structural models to ensure that such models can represent the entire response of interest.

In the case of the Dominican Republic, the first and most complete seismic vulnerability evaluation project of school structures was carried out by the National Office of Seismic Evaluation and Vulnerability of Infrastructure and Buildings (ONESVIE, Spanish Acronym) (ONESVIE 2014) with the participation of other institutions such as the National Geological Service (SGN, Spanish Acronym), the offices of the Risk Management Program and the Education Regional of the Ministry of Education (MINERD, Spanish Acronym) and was sponsored by the Japan International Cooperating Agency (JICA). The main objective of this project was the qualitative evaluation of the structural vulnerability of schools in the San Cristóbal Province. A total of 320 schools were assessed, using an adaptation of the rapid visual detection method (FEMA 2002a, b) together with other evaluation methodologies (Lew et al. 2002; AGIES 2001). The project also included the classification of the structures according to their vulnerability index (Benedetti and Petrini 1984) which takes into account aspects of structural type, structural configuration, location of the building, foundations and non-structural elements. The results indicated that 290 schools (90.7%) require a detailed structural evaluation. Likewise, the assessment of the vulnerability index showed that 53 schools (16.56%) have a high vulnerability index; 243 schools (75.94%) have an average vulnerability index and 24 schools (7.5%) have a low vulnerability index. The authors recommended a detailed evaluation of the buildings that resulted with a high vulnerability degree.

3 Objectives and scope of the ONESVIE project

Vulnerability studies using qualitative methods constitute a first stage of evaluation when there are a large number of structures to be evaluated and limited resources are available. However, in order to make recommendations for reinforcement, a more detailed analysis is necessary, which was not contemplated within the objectives of the ONESVIE school evaluation project. Therefore, the aforementioned study should be completed in a second stage that includes the quantitative evaluation of each of the schools that resulted with a high degree of vulnerability and that proposes particular solutions based on the results of the analyzes of each one of the assessed schools.

Considering that the current student population in public schools in the Dominican Republic is over 2 million, with the majority attending buildings that were designed with the former 1979 seismic code and which proved to be very vulnerable during the Puerto Plata earthquake, it is deemed vital to take measures that reduce the risk and minimize potential earthquake damage to these structures. In this context, the Technological Institute of Santo Domingo (INTEC) has recently undertaken a project aimed at assessing the seismic vulnerability of 22 schools located in the San Cristóbal Province, in the south of the Dominican Republic. The case study schools were all built prior to the adoption of the current seismic code, which resulted in a higher degree of vulnerability according the study carried out by ONESVIE. The specific objectives established in order to achieve the main objective of this project are: (a) to determine whether the schools are adequate according to the current Dominican seismic code (2011); (b) to update structurally schools that do not comply with the Dominican seismic code and provide the structural solutions if necessary.

4 Code practice in the Dominican Republic

In the Dominican Republic, prior to the implementation of the current seismic design code (MOPC 2019) what existed were some recommendations that governed the seismic design dating back from 1979 (O’ Reilly 2002). That implies the country had the same seismic regulations for 32 years. During these three decades, thousands of structures (including schools) were built throughout the national territory that may be vulnerable to a seismic event. Following sections briefly discuss the main features of both the 1979 Seismic Code Provisional Recommendations and the current Seismic Code implemented in 2011, as well as two important seismic hazards studies carried out in both sides of the Hispaniola Island.

4.1 1979 provisional recommendations for the seismic analysis of structure

The provisional recommendations for the seismic analysis of structures (SEOPC 1979) divide the country into two seismic zones: (1) high seismicity and (2) medium seismicity zone, as shown in Fig. 4. The design spectra, both elastic and inelastic, are shown in the same figure. It is important to mention that the U-, S-, and Rd-coefficients are tabulated values that depend on the importance of the structure, the site in which the structure is located, and the type of structural system, respectively.

Fig. 4
figure 4

Adapted from (SEOPC 1979)

Elastic and inelastic design spectrum according to the 1979 Dominican seismic code.

4.2 Regulations for the seismic analysis and design of structures R-001

The regulation for the seismic analysis and design of structures (MOPC 2011) is basically an adaptation of the ASCE7-05 code (ASCE 2005) of the USA. For the purposes of the regulation, the Dominican Republic is divided into two zones, according to their reference spectral seismic acceleration levels SS, for a return period of 2475 years, with a probability of exceeding 2% in 50 years. Alternatively, for design purposes, the use of spectral iso-acceleration maps is allowed for short periods (SS) and long periods (S1), as shown in Fig. 5. The code also provides accelerations contour maps for both 2% and 10% probabilities of exceedance in 50 years. The expressions that define the elastic design spectrum are shown in Fig. 6. In the figure, Fa and Fv are the site coefficients, which depend on the site classification. Likewise, U represents the use of the structure, means while Rd is the energy dissipation factor that is a function of the structural system. It is important to mention that the current seismic code is not intended for the evaluation of existing structures; thus, the evaluation of the seismic risk of as-built schools may become controversial, especially for the estimation of the hazard levels.

Fig. 5
figure 5

Adapted from MOPC (2011)

Accelerations contour maps for a probability of exceedance of 2% in 50 years, according to the Dominican Republic 2011 seismic provisions. a Short period (SS), b long period (S1), and c seismic zoning.

Fig. 6
figure 6

Adapted from MOPC (2011)

Elastic and inelastic design spectrum expressions as per R-001 seismic code.

The comparison of the design spectra by both the 1979 and 2011 codes for a concrete frame school structure located in the San Cristóbal Province is shown in Fig. 7. Considering that, as first estimate, the fundamental period for a reinforced concrete (RC) frame structure can be evaluated as 0.1 N, where N is the number of levels of the structure, for a typical school building of three levels, the seismic forces obtained from the 1979 code could underestimate such load in 61% (Table 2). Thus, it is necessary that school buildings designed with the former provisional regulations need to be assessed in order to determine the degree of vulnerability that such structures pose.

Fig. 7
figure 7

Design spectrum comparison for the San Cristobal Province

Table 2 Comparison of the 1979 (M-001) and the 2011 (R-001) spectral accelerations

4.3 Seismic hazard maps for Haiti

After the devastating earthquake (magnitude 7.0) of January 12, 2010 that occurred in Haiti, a group of researchers led by the United States Geological Survey (USGS) constructed probabilistic seismic risk maps for Haiti in order that serve as the basis for the development of building codes and standards in that country (Frankel et al. 2011). Although the maps were developed for the entire island of Hispaniola, the authors indicate that they cannot be considered as complete hazard maps for the Dominican Republic since they do not take into account all the sources of earthquake hazard that affect the eastern of the Hispaniola. The proposed maps are depicted in Fig. 8.

Fig. 8
figure 8

Adapted from Frankel et al. (2011)

Seismic hazard map of Hispaniola region with peak ground acceleration (PGA; in %g) a 10% probability of exceedance in 50 years and b 2% probability of exceedance in 50 years.

According to FEMA 451 (reference), the values of the long-period accelerations (S1) and the short-period accelerations (SS) can be estimated from the PGA. In that regards, S1 can be taken equal to the PGA and SS as 2.5 times the PGA. Thus, it is possible to relate the accelerations proposed in the R-001 seismic code with the ones developed by Frankel et al. (2011). The comparison for the case of the long-period spectral acceleration is shown in Fig. 9. It is observed that the current seismic code has higher accelerations around the northern fault (northwest and northeast of the Dominican Republic). However, outside this region, the acceleration contour proposed by Frankel et al. (2011) shows higher accelerations. The same conclusions apply for the case of the short-period spectral acceleration (Fig. 10).

Fig. 9
figure 9

Comparison between the contour accelerations of the seismic hazard maps developed by Frankel et al. (2011) and the long-period spectral accelerations (S1) indicated in the R-001 seismic code, for the 2% probability of exceedance in 50 years

Fig. 10
figure 10

Comparison between the contour accelerations of the seismic hazard maps developed by Frankel et al. (2011) and the short-period spectral accelerations (Ss) indicated in the R-001 seismic code, for the 2% probability of exceedance in 50 years

4.4 Seismic and windstorm evaluation of existing RC buildings for the Dominican Republic

As part of a reconstruction project funded by the United States Agency for International Development (AID), the National Institute of Standard Technology (NIST) (Lew et al. 2002) developed a manual to evaluate critical reinforced concrete structures (hospitals, emergency response centers, etc.). Such manual was based on the procedures described in two documents published by the Federal Emergency Management Agency FEMA (FEMA 178 1992; FEMA 310 1998). In this document, the seismic load for the evaluation of existing structures (since some level of damage is acceptable in an existing structure) is obtained from recommended PGA values proposed in this study based on an estimate of 10% probability in 50 years (Fig. 11).

Fig. 11
figure 11

Peak ground acceleration (PGA) contours (10% probability of exceedance in 50 years) proposed by Lew et al. (2002)

5 Methodology

The methodology implemented in the study presented in the previous section is summarized as follows:

  • Schools selection;

  • Architectural survey;

  • Structural survey;

  • Structural modeling;

  • Recommendations.

The above framework fulfills the current practice for seismic assessment of existing RC buildings also in the earthquake-prone regions in the south of Europe (e.g., Di Sarno and Manfredi 2010, 2012, among others). The details of each of the above-mentioned steps are presented in the following sections.

5.1 Schools selection

To ensure that the selected schools are the most critical, they must meet the following selection criteria:

  • The structure’s material must be reinforced concrete;

  • Have two or more storeys;

  • Have a medium to high vulnerability index [from the ONESVIE study (ONESVIE 2014)];

  • The year of construction must be before 2011. (It is assumed that the structures built with the current code are not vulnerable.)

5.2 Architectural survey

Due to the low probability that architectural plans are available, it is proposed to perform an architectural survey to identify both the gravity and the lateral load resistance systems as well as to obtain the dimensions of the structural elements.

5.3 Structural survey

In accordance with the requirements for the evaluation of existing buildings (MOPC 2019) established by the Ministry of Public Works of the Dominican Republic (MOPC Spanish acronym), the structural survey for RC structures shall include the assessment of the structural member conditions, the evaluation of concrete strength of the structural components, as well as the evaluation of the reinforcement steel. In this document, the concrete strength shall be evaluated by means of destructive and/or nondestructive test, with the minimum number of sample testing established according to the following criteria:

  1. (a)

    Destructive test

    1. a.

      15% of the vertical earthquake-resistant structural components (walls and columns) in both X- and Y-directions;

    2. b.

      At least one core should be extracted each 15 m3 for beams;

    3. c.

      At least one core should be extracted each 150 m2 for concrete slabs.

  2. (b)

    Nondestructive test

    1. a.

      25% of the structural elements of each level, which must be complemented with core testing of at least 5% of the vertical earthquake-resistant elements; one core each 30 m3 for beams and one core each 300 m2 of concrete slabs.

For the case of the steel reinforcement, the minimum number of structural elements that must be verified is as follows: (a) 70% of the columns and structural walls, (b) 30% of the reinforced concrete beams, and (c) 10% of the reinforced concrete slabs.

The MOPC requirements also establish the evaluation of the foundation system by means of explorations that include: (a) concrete core samples in at least 10% of the foundations but not less than two samples and (b) the geometry of the section (foundation depth, slab thickness, and foundation area).

Due to budgetary constraints, it was not possible to reach the minimum number of concrete core samples as required by the MOPC. However, to obtain a representative concrete strength for modeling purposes, a minimum number of three sample tests were established by structural elements as suggested by FEMA 356 (2000, 2002). Such elements were selected based on a preliminary structural analysis. At the same time, for the same reasons, it was not possible to carry out the inspection of the foundations.

5.4 Preliminary structural model

To optimize the number of concrete samples, a preliminary structural model was implemented numerically with the main objective to identify those structural elements with the higher load demands that will be selected for a destructive-type test.

5.5 Refined structural model

With the properties of the concrete obtained from the structural assessment and the arrangement of the reinforcing bars in the structural elements determined from the scanning of such elements, a refined analysis model was constructed which includes the seismic loads demands according to the current seismic regulations.

5.6 Recommendations

If the results of the structural analysis indicate that the building system does not comply with the requirements of the R-001 regulations, a structural solution will be proposed. This scheme will be evaluated through a static nonlinear analysis (pushover) and/or by means a time history analysis in order to determine the effectiveness of the proposed solution.

Next section shows the assessment of the Fernando Cabral Ortega School by applying the methodology previously described above. Although only the results of a single RC building are presented, the response of such structure can be considered representative of a portfolio of existing schools in Dominican Republic.

6 Case study: the Fernando Cabral Ortega School

The Fernando Cabral Ortega School is located in the community of La Jeringa, Municipality of San Cristóbal. The structure has a capacity for 400 students and was built in 1996. According to the School Vulnerability Report presented by ONESVIE, the structure resulted with a high vulnerability index. The structure consists of three building modules of two levels each connected by a corridor as shown in Figs. 12 and 13. The structural system is composed by RC frames in both directions enclosed by masonry walls. It can be noticed that the structures satisfy the established selection criteria.

Fig. 12
figure 12

Fernando Cabral Ortega School

Fig. 13
figure 13

Rendered view of the Fernando Ortega School

6.1 Architectural and structural survey

The structural drawings of the sample building were not available; therefore, the cross-sectional dimensions of the elements, the concrete strength, and the reinforcement details were obtained from both the architectural and structural surveys, respectively. The cross sections of beams and columns are depicted in Fig. 14.

Fig. 14
figure 14

Beam and column details

The concrete strength was assessed by means of destructive test. A total of six samples were evaluated (three in beams and three in columns), in structural elements that resulted with higher load demand according to a preliminary structural analysis. The concrete core extraction process is shown in Fig. 15. The concrete test results for the beams and columns are shown in Tables 3 and 4, respectively. It is noteworthy to mention that three samples were extracted for the beams; however, the stress obtained from one of the tests was only 55 kg/cm2 (5 MPa), which is clearly an outlier and thus was discarded.

Fig. 15
figure 15

Concrete core extraction

Table 3 Concrete core test results for beams
Table 4 Concrete core test results for columns

Section 6.3.2.4.1 of FEMA 356 (FEMA 356) states that the minimum number of tests to determine any property is 3 but limited to a coefficient of variation less or equal to 14%.

It can be seen in Table 3 that even though only two tests were evaluated, the coefficient of variation resulted below 14%. For the case of the columns (Table 4), the coefficient of variation exceeded 14%, which implies that more tests are needed. However, it was decided to use in both cases the average of the test results; thus, the concrete strength used in the calculations was set equal to fc  = 39 MPa for the beams and fc  = 18 MPa for the columns. For the case of the reinforcement steel yield strength, a value of fy = 280 MPa was set, as indicated by the MOPC R-033 (MOPC 2012) when no information regarding reinforcement steel is available.

6.2 Structural model

In order to evaluate the behavior of the building structure, a numerical finite element model was created using the ETABS software (Computer and Structures 2005). Such model is shown in Fig. 16. Beams and columns were modeled according to the sections as depicted in Fig. 14. In both elements, the cracking effect as required by the R-001 was considered. To take into account, the effect of the masonry infill walls as an equivalent diagonal as suggested in section 7.5.2.1 of FEMA 356 was used. Both gravitational and seismic loads were estimated as per R-001 regulations. Although in the architectural survey, it was identified that the structures are separated by construction joints, however, the slab was cast in place continuously, which makes it behave as one body instead of four.

Fig. 16
figure 16

Structural model

6.3 Results

Based on the averages of the concrete strength obtained from destructive tests, the columns of the structures do not comply with Article 43 of R-033 Regulation (MOPC 2012), which requires that in structural elements, the minimum concrete strength should be 210 kg/cm2 (21 MPa). Also, analysis results indicate that the structure has plan irregularity and thus does not comply with the Article 38 of the R-001 regarding excessive torsion. In addition, columns near the corridors are showing high shear demands due to the partial constraint imposed by the infill masonry walls (Fig. 17). As first solution, it was proposed: (1) separate the structure and model it as four independent structures (Fig. 18) and (2) uncouple masonry walls from the columns using the detail as shown in Fig. 19.

Fig. 17
figure 17

Shear diagram in columns at the corridors

Fig. 18
figure 18

Suggested construction joint

Fig. 19
figure 19

Masonry walls separation details

6.3.1 Pushover analysis

To evaluate the performance of the proposed modified structure, a nonlinear static analysis (pushover) was carried out. The properties of the plastic hinges for the beams and columns were defined according to the recommendations of the standard ASCE7-05 (ASCE 2005). The behavior of the plastic hinges (Fig. 20) was evaluated at the performance point of the structure, in terms of the rotations limits established by the ATC-40 (Applied Technology Council 1996) for buildings with special occupation. To these buildings corresponds an immediate occupancy (IO) level.

Fig. 20
figure 20

Plastic hinge model for flexural member

The pushover analysis results for the case of building I only are shown in Fig. 21 (X-direction) and in Fig. 22 (Y-direction). The results for the other buildings are not shown due to space constraints. It can be seen in these figures that all the columns of the first level reached the life safety limit state and thus do not satisfy the expected performance level for the structure. These results suggest that the structure must be reinforced. As a solution, it is proposed to reinforce the columns and beams of the structure with the detail as shown in Fig. 23.

Fig. 21
figure 21

Plastic hinge behavior for pushover analysis in the X-direction

Fig. 22
figure 22

Plastic hinge behavior for pushover analysis in the Y-direction

Fig. 23
figure 23

Proposed reinforcement detail for beams and columns

In order to validate the behavior of the reinforced structure, a new analysis was performed. The results are shown in Fig. 24 (X-direction) and in Fig. 24 (Y-direction). It is noted that for the performance point, the plastic hinge is kept within the limits of immediate occupation. These results suggest that the proposed reinforcement is adequate.

Fig. 24
figure 24

Plastic hinge behavior for pushover analysis: a x-direction and b y-direction

7 Conclusions

The main conclusions that can be highlighted from this study are the following:

  • The seismic demand expected with the seismic regulation of 1979 could be underestimated between 32 and 61% in school structures from 1 to 3 levels, located in the province of San Cristóbal, when compared with the seismic demand obtained with the current seismic code.

  • Although according to their authors, the seismic hazard maps developed by the USGS cannot be considered complete for the eastern part of Hispaniola, they show that spectral accelerations for a 2% and a 10% probability in 50 years suggested by the current regulation could be underestimating the seismic demand for the entire area of the country located below the northern fault. This implies that more research is needed.

  • It is necessary to develop or implement a code for the evaluation of existing structures in the Dominican Republic, since the current one was not intended for this purpose.

  • The structural configuration of typical schools in the Dominican Republic promotes a poor seismic behavior (short column effect, buildings with irregular plan shapes, etc.) as observed during the Puerto Plata’s earthquake in 2003.

  • For the case of the Fernando Cabral Ortega School, concrete compressive strength obtained by destructive test resulted in a high coefficient of variation in both beam and column elements. This implies that more tests must be performed to obtain a representative resistance for the structural elements. However, it is important to mention that the other assessed schools had concrete strength well below those allowed by the design codes, which suggests that the quality control during the construction process was very deficient.

  • The evaluation of the performance of the structure with the demand estimated according to the current seismic code showed that the expected level of damage exceeds the limit state for a structure with special occupation and, therefore, must be reinforced. The same observations apply for the remaining 21 schools evaluated in this project.

  • When evaluating the proposed scheme reinforcement, the analysis results showed that the level of expected damage is within the limits for a special occupation structure, and therefore, it is demonstrated that this solution is adequate.