1 Introduction

Natural convection processes, since they commonly occur in nature, as well as in industrial applications, have been studied extensively throughout the 20th and twenty-first century. Because of the buoyancy driven convection importance, especially as a means to enhance heat exchange, methods to improve heat transfer even more are often sought. One of the ways to achieve that is by introducing a new buoyancy driven force to the analysed system. In 1991 Braithwaite et al. [1] adopted an external magnetic field to enlarge and supress the convective motion of a paramagnetic fluid. This fact marked the beginning of a new era in convection research, directed to studies of a magnetic field impact on a weak magnetic fluid motion. This research field has been broadly investigated in the past two and a half decades. Tagawa et al. [2] developed a mathematical model equation for thermo-magnetic convection. Bednarz et al. [3,4,5] studied heat transfer and influence of different inclinations of a magnetic field on a paramagnetic fluid in cubical geometry in side-heated configurations. Kenjeres et al. [6, 7] and Pyrda et al. [8] investigated various aspects, e.g. Prandtl number and magnetic susceptibility in transient and turbulent flow regimes in a cubical enclosure. Many other configurations have been studied, e.g. coaxial cylinders [9], thermosiphons [10], porous media [11]. Nowadays, a new field in the area is connected with nanofluids and analysing aspects like a concentration of nanoparticles or their sizes, and their influence on heat transfer in magnetic field [12,13,14].

Despite the considerable number of articles about the influence of different factors on natural convection, in 2012 Turan et al. [15] published research concerning laminar convection in systems with different aspect ratios (AR = height/width). They concluded that AR has a crucial impact on heat transfer in investigated configurations. The field of thermo-magnetic convection lacks this kind of investigation work. To the authors best knowledge, there is no experimental data available in the literature concerning a strong magnetic field’s influence on paramagnetic fluid convection in rectangular systems with different aspect ratios. Therefore, the authors performed experimental research of magnetic field impact on heat transfer and fluid flow behaviour in two different geometries: with AR = 0.5 and AR = 2.0.

2 Theoretical background

In natural convection phenomenon motion of a fluid is a result of a gravitational force acting on a fluid- f g:

$$ {\mathbf{f}}^{\mathbf{g}}=\mathbf{g}\rho $$
(1)

Since the density of a fluid depends on a temperature, the magnitude of a gravitational force acting on a fluid with different temperature varies, creating a gravitational buoyancy force:

$$ {\mathbf{f}}^{\mathbf{G}}=\mathbf{g}\left(\rho -{\rho}_0\right) $$
(2)

Taking into account the Boussinesq model, which states that the density of a fluid can be assumed as a constant for small temperature differences, except in the equation for buoyancy force, fluid density can be expressed as:

$$ \rho \simeq {\rho}_0\left(1-\beta \left(T-{T}_0\right)\right) $$
(3)

Using relation (3) to eq. (2), gravitational buoyancy force takes following form:

$$ {\mathbf{f}}^{\mathbf{G}}=-\mathbf{g}{\rho}_0\beta \left(T-{T}_0\right) $$
(4)

The obvious effect of a gravitational buoyancy force of a fluid in a gravitational field is the downward motion of a cold fluid, while the warm fluid particles are lifted.

Applying external magnetic field to a material causes the magnetic force to act on the material’s electrons. The magnitude of the material’s reaction to a magnetic field can be described by volume magnetic susceptibility:

$$ {\chi}_v=\mathbf{M}/\mathbf{H} $$
(5)

and mass magnetic susceptibility:

$$ \chi ={\chi}_v/\rho $$
(6)

A force acting on a paramagnetic fluid placed in an external magnetic field can be expressed as [16]:

$$ {\mathbf{f}}^{\mathbf{mg}}={\mu}_0\left(\mathbf{M}\cdot \nabla \right)\mathbf{H} $$
(7)

Noting (5) and knowing that magnetic induction b depends on the intensity of a magnetic field and on a magnetic permeability of the material, and also that for a paramagnetic fluid χ <  < 1, eq. (7) can be transformed into:

$$ {\mathbf{f}}^{\mathbf{mg}}=\frac{\chi }{2{\mu}_0}\nabla {\mathbf{b}}^2 $$
(8)

Utilizing the above relation and Curie’s law for paramagnetic materials, Tagawa et at. developed an equation to describe the magnetic buoyancy force [2]:

$$ {\mathbf{f}}^{\mathbf{M}}=-\left(1+\frac{1}{\beta {T}_0}\right)\frac{\chi_0{\rho}_0\left(T-{T}_0\right)}{2{\mu}_0}\nabla {\mathbf{b}}^2 $$
(9)

Expression (9) indicates that the paramagnetic fluid particles are attracted to a square of a magnetic field’s gradient if their temperature T is lower than reference temperatureT 0. Taking the above relations into consideration, an experimental enclosure filled with a paramagnetic fluid was placed in an upper half position in the magnet’s working section, where the square of the magnetic field gradient was the highest, so the intensification of the fluid motion could be obtained.

3 Experimental methodology

3.1 Measuring system

The measuring system used in the proposed experimental research is presented in Fig. 1. It consists of two experimental enclosures placed, separately, in the bore of a superconducting magnet, a heater control system, a water thermo-stated bath with a constant temperature and data acquisition system connected to a personal computer. To calculate the magnetic field distribution and its gradient, besides the real dimensions of the system presented on Fig. 1. (right), the current densities in the internal and external coil should be taken into account. They were equal to 140.9∙10−6 A/m2 and 167.3∙10−6 A/m2 respectively at the maximum value (b 0max = 10 T) of the magnetic field inside the centre of the magnet.

Fig. 1
figure 1

Schematic view of the experimental setup (left) and dimensions of the magnet’s coils (right)

Experimental enclosures are shown schematically in Fig. 2. Built from Plexiglass, rectangular vessels, of size 0.032 m × 0.032 m in base and of 0.016 m (Enclosure A) and 0.064 m (Enclosure B) in height, were heated with a constant temperature from the bottom wall and isothermally cooled from the top. Four remaining vertical walls were insulated. The bottom wall consisted of a copper plate heated with nichrome wire connected to a DC power supply. The electric voltage and current were measured with a multi-meter. A top wall was also composed of a copper plate with a built in cooling chamber, which was cooled by cold water running from a thermostat. Because an ambient temperature in the magnet’s working section was 18 °C, in order to minimize the heat losses from the system, the temperature on the cooled wall was set to be the same. The temperature of the heated and cooled walls were measured with six T-type thermocouples inserted into the small holes in each plate. Five (Enclosure no. 1) and six (Enclosure no. 2) thermocouples (Fig. 2) were inserted into small holes in one wall of the experimental enclosure at 6 mm deep and measured the temperature changes of the fluid during the tests.

Fig. 2
figure 2

a Experimental geometries: Enclosure no. 1 with AR = 0.5 and Enclosure no. 2 with AR = 2.0; b thermocouple’s locations in mm

3.2 Working magnetic fluid

An experimental analyses for both geometries were performed about a year apart and because of that the first fluid degraded. Therefore two slightly different fluids were used: fluid 1 (F1) for Enclosure no.1, and fluid 2 (F2) for Enclosure no. 2. The working fluids were 50% volume glycerol aqueous solutions. Since both water and glycerol present diamagnetic properties, an addition of 0.8 mol/(kg of solution) of gadolinium nitrate hexahydrate Gd(NO3)3∙6H2O crystals had to be made to make them paramagnetic. The main goal was to maintain similar magnetic properties of the fluids (mass magnetic susceptibility), which was achieved during the preparation of the second fluid F2, but the viscosity, density and therefore, the thermal expansion coefficient, for fluid F1 are slightly different than for fluid F2.

Fluid properties were measured and are listed in Table 1. The densities of the working fluids were measured with a pycnometer and thermal expansion coefficient was calculated. The magnetic susceptibility of the fluids was gauged with a magnetic susceptibility balance using the Evan’s method. Viscosities were meted using an Ubbelohde viscometer and other properties were taken from [17].

Table 1 Properties of the working fluid at 25 °C

3.3 The measurement procedure

The first step of the measurement procedure was connected with estimating the heat losses from the system in order to calculate the Nusselt number. Enclosure no. 1 was filled with distilled water and placed in the predestined position in the magnet’s working section, but the vessel was rotated 180 degrees in the reversed Rayleigh- Bénard position. This configuration allowed to reach a temperature stratification – a conduction state without convective fluid motion. After setting the temperature at the bottom and top walls and waiting for the fluid and temperature fields to stabilize, linear temperature distribution was achieved and heating power was measured. Assuming a one-dimensional conductive heat flow, the heat flux can be calculated from Fourier’s law of conduction (see section 4.1.). Therefore, a difference between heat flux calculated from Fourier’s Law and measured heat flux on a heated wall is the heat loss of a measuring system. The same procedure was used to calculate heat losses from Enclosure no. 2. Heat losses from both experimental geometries can be approximated from:

$$ {Q}_{loss\ 1}\propto 0.090\cdot \varDelta T $$
(10)
$$ {Q}_{loss\ 2}\propto 0.083\cdot \varDelta T $$
(11)

The second step of the experimental analysis was connected with natural convection and thermo-magnetic convection measurements. The experimental enclosure was rotated back to the Rayleigh-Bénard configuration and the temperature difference between the thermally active walls was set. Three differences between the thermally active walls were investigated – 3, 5 and 11 °C. After a thermal stabilization was achieved, 15-min recording of temperature took place. Subsequently the magnetic induction was set at the desired value, the experimental system was left to stabilize and then the measurement of temperature took place. Those steps were repeated for the values of magnetic induction b 0max from 0 T up to 10 T.

For both analyzed enclosures, the procedure was the same.

4 Analysis of temperature signals

The temperature signals, recorded during the experimental research, allowed for the investigation of two aspects – the heat transfer in the analysed systems and the behaviour of the paramagnetic fluid’s flow subjected to an external magnetic field.

4.1 Analysis of heat transfer in the system

The heat transfer rate was established by calculation of the Nusselt number, which is a dimensionless criterion displaying heat transfer in the system. From definition, the Nusselt number is a ratio of convective heat flux to conducted heat flux:

$$ \mathrm{Nu}={Q}_{\mathrm{net}\_\mathrm{conv}}/{Q}_{\mathrm{net}\_\mathrm{cond}} $$
(12)

The net conduction (Q net_cond) and net convection (Q net_conv) heat fluxes were computed by Ozoe and Churchill method [18], which is based on the following relations:

$$ {Q}_{\mathrm{net}\_\mathrm{cond}}={Q}_{\mathrm{cond}}-{Q}_{\mathrm{loss}} $$
(13)
$$ {Q}_{\mathrm{net}\_\mathrm{conv}}={Q}_{\mathrm{conv}}-{Q}_{\mathrm{loss}} $$
(14)

As said in section 3.3, it was assumed that the heat losses depend only on the temperature of the heated wall. So as a step one in determining the Nusselt number, the conduction measurements were made and the heat losses were calculated from:

$$ {Q}_{\mathrm{loss}}={Q}_{\mathrm{cond}}-{Q}_{\mathrm{Fourier}\hbox{'}\mathrm{s}\_\mathrm{law}} $$
(15)

where

$$ {Q}_{Fourier\hbox{'}s\_ law}=\frac{{\mathrm{a}}^2\lambda\varDelta T}{d} $$
(16)

The heat flux was computed for a conduction area of 0.032 m × 0.032 m (base wall dimensions in both geometries). So the Nusselt number, with the usage of eqs. (13), (15) and (16) can be expressed as:

$$ \mathrm{Nu}=\frac{Q_{\mathrm{conv}}-{Q}_{\mathrm{loss}}}{\frac{{\mathrm{a}}^2\lambda\varDelta T}{d}} $$
(17)

where the convection heat flux (Qconv) is given by the difference between heat flux measured during experiments and heat losses from the system.

The results of the heat transfer analysis are shown as a function of the thermo-magnetic Rayleigh number, which is defined as follows:

$$ {\mathrm{Ra}}_{\mathrm{T}\mathrm{M}}={\mathrm{Ra}}_{\mathrm{T}}+{\mathrm{Ra}}_{\mathrm{M}} $$
(18)

where RaT is the thermal Rayleigh number, RaM is the magnetic Rayleigh number and γ is the magnetization number:

$$ {\mathrm{Ra}}_{\mathrm{T}}=\frac{\mathbf{g}\beta \left({T}_{\mathrm{h}}-{T}_{\mathrm{c}}\right){d}^3}{\alpha\nu} $$
(19)
$$ {\mathrm{Ra}}_{\mathrm{M}}=\left(1+\frac{1}{\beta {T}_0}\right)\left[\frac{\mathbf{g}\gamma\beta\left({T}_{\mathrm{h}}-{T}_{\mathrm{c}}\right){d}^3}{2\alpha\nu}\right] $$
(20)
$$ \gamma =\frac{\chi {\left|{\mathrm{b}}_0\right|}_{\mathrm{m}\mathrm{ax}}^2}{{\rho\mu}_{\mathrm{m}}\mathbf{g}d} $$
(21)

4.2 Flow behaviour analysis

Signals from the thermocouples inserted into the experimental enclosures allowed for the examination of the flow behaviour. This spectral analysis was obtained through the Fast Fourier Transform (FFT), which computes the Discrete Fourier Transform (DFT) of a sequence:

$$ {F}_n=\sum_{i=0}^{N-1}{x}_i{e}^{-\frac{2\pi i}{N} ni} $$
(22)

The spectral functions of a scalar field (e.g. temperature, pressure, density, concentration) are very useful tools in analyzing a turbulent transport mechanism. Thus, assuming that the turbulence is homogenous, power density or spectrum may be calculated with the utilization of FFT:

$$ \mathrm{Power}\ \mathrm{density}\left({e}^{j\omega}\right)=\sum_{m=-\infty}^{\infty }{r}_{xx}(m){e}^{- j\omega m} $$
(23)

and with the use of the Peridogram method, which estimates power as Time-Integral Square Amplitude (TISA) from amplitude obtained with FFT:

$$ \mathrm{Power}\ \mathrm{density}\ \left(\mathrm{TISA}\right)=\frac{\varDelta t\left({\mathrm{Real}}^2+{\mathrm{Imaginary}}^2\right)}{n} $$
(24)

Temperature spectral functions generally depend on energy dissipation, thermal diffusivity, viscosity and temperature. In some ranges of frequency, spectral functions do not depend on the diffusion processes, and hence do not rely on kinematic viscosity and thermal diffusivity. This subrange is called the inertial-convective [19] region and in this range spectral function has an inclination of wave number K with a - 5/3 exponent. In cases where thermal diffusivity becomes more important, the spectral function has an inclination of reverse wave number, and this range is called viscous-diffusive [19].

The attained results, in the form of an amplitude versus frequency and a power spectrum of the fluid flow field, were used to analyse the fluid behaviour in a thermo-magnetic convection.

5 Results

Figure 3 presents the Nusselt number in a function of a thermo-magnetic Rayleigh number [20]. It proves that the aspect ratio of an experimental geometry has a very high impact on heat transfer rate. For Enclosure no. 1, which has an aspect ratio of 0.5, the Nusselt number is significantly lower than for Enclosure no. 2 with an aspect ratio of 2.0. For natural convection cases, where the magnetic Rayleigh number is equal to 0 and therefore RaTM = RaT according to eq. (18), in Enclosure no. 1 Nusselt number values start from 2.95 for ΔT = 5 °C, 3.46 for ΔT = 3 °C and 3.62 for ΔT = 11 °C while in Enclosure no. 2 it is 13.45, 14.50 and 18.82 for ΔT = 3, 5 and 11 °C respectively. After an application of a magnetic field to the system, in both geometries, the Nusselt number increases. For a magnetic field of 10 T, the increase of heat transfer rate in Enclosure no.1 for ΔT = 3 °C is over 250% to Nu = 9.21, while in every other case improvement in the Nusselt number is over 300%. In Enclosure no.1 it reaches values: 11.02 for ΔT = 5 °C and 12.66 for ΔT = 11 °C and in Enclosure no.2 to 40.34, 48.91 and 59.33 for ΔT = 3, 5 and 11 °C, respectively.

Fig. 3
figure 3

Results of Nusselt number calculations for Enclosure no.1 (left) and Enclosure no.2 (right) as a function of a thermo-magnetic Rayleigh number

Figures 4 and 5 represent the changes of fluid temperature during the 15-min period. Parts a,c and e show natural convection cases for ΔT = 3, 5, 11 °C respectively, and parts b,d and f report thermo-magnetic convection cases at a maximal value of a magnetic induction 10 T. Colours of the lines in the presented graphs present thermocouples placed in the experimental enclosure in particular locations, as shown in Fig. 2.

Fig. 4
figure 4

Changes of a fluid’s temperature during experiments in Enclosure no.1: (a) b 0max = 0 T, ∆T = 3 °C, (b) b 0max = 10 T, ∆T = 3 °C, (c) b 0max = 0 T, ∆T = 5 °C, (d) b 0max = 10 T, ∆T = 5 °C, (e) b 0max = 0 T, ∆T = 11 °C, (f) b 0max = 10 T, ∆T = 11 °C

Fig. 5
figure 5

Changes of a fluid’s temperature during experiments in Enclosure no.2: (a) b 0max = 0 T, ∆T = 3 °C, (b b 0max = 10 T, ∆T = 3 °C, (c) b 0max = 0 T, ∆T = 5 °C, (d) b 0max = 10 T, ∆T = 5 °C, (e) b 0max = 0 T, ∆T = 11 °C, (f) b 0max = 10 T, ∆T = 11 °C

Natural convection measurements for Enclosure no.1 show temperature lines as stable and horizontal (Fig. 4 a, c, d). The thermal Rayleigh number for Enclosure no.1 was 1.84·103, 3.12·103 and 7.64·103 for ΔT = 3, 5, 11 °C respectively. For the geometry with the higher aspect ratio, in cases where the temperature difference was higher than 3 °C (Fig. 5 c, e), the temperature field is not as stable. Temperature lines show a wavy character, which may indicate an existence of flow structures rotating in the enclosure with a low frequency. The thermal Rayleigh numbers for Enclosure no.2 were as follows: RaT = 3.14·104; 4.05·104 and 9.19·104 for ΔT = 3, 5, 11 °C respectively. During the stepwise increase of the magnetic induction up to 10 T, temperature signals from the thermocouples tend to unify temperature values at all thermocouple positions and start to oscillate over time. This suggests an increase in fluid velocity and a change of a fluid flow pattern during this process.

Figures 6 and 7 show the results of the fast Fourier analysis in amplitude versus frequency form. Parts a, c and e represent natural convection cases for ΔT = 3, 5, 11 °C respectively, and parts b, d and f thermo-magnetic convection cases at the maximal value of the magnetic induction - 10 T.

Fig. 6
figure 6

Amplitude of a fluid’s temperature oscillations as a function of frequency in Enclosure no.1: (a) b 0max = 0 T, ∆T = 3 °C, (b) b 0max = 10 T, ∆T = 3 °C, (c) b 0max = 0 T, ∆T = 5 °C, (d) b 0max = 10 T, ∆T = 5 °C, (e) b 0max = 0 T, ∆T = 11 °C, (f) b 0max = 10 T, ∆T = 11 °C

Fig. 7
figure 7

Amplitude of a fluid’s temperature oscillations as a function of frequency in Enclosure no.2: (a) b 0max = 0 T, ∆T = 3 °C, (b) b 0max = 10 T, ∆T = 3 °C, (c) b 0max = 0 T, ∆T = 5 °C, (d) b 0max = 10 T, ∆T = 5 °C, (e) b 0max = 0 T, ∆T = 11 °C, (f) b 0max = 10 T, ∆T = 11 °C

For ΔT = 3,5 and 11 °C in Enclosure no.1 fluid flow is steady and no temperature amplitude peaks can be observed. After applying magnetic induction to the system, the flow becomes faster and temperature oscillations are more frequent. In the thermo-magnetic convection one thermocouple shows behaviour different from the others. This thermocouple ‘tc5’ was placed in the bottom right corner of the enclosure and is represented by cyan colour in the figure. The amplitude of fluctuations is higher than for the other thermocouples. This may indicate an appearance of a small vortical structure which is moving apart from the main flow. In Enclosure no.2, with a higher aspect ratio, high amplitudes appear for small frequencies at natural convection cases (c and e parts in Fig. 7). After applying an external magnetic field to the system, a decrease of higher amplitudes can be observed. The amplitudes of temperature oscillations became less intensive than for the results for the natural convection case but appears in the wider range of the frequency band. This suggests a faster movement of the fluid in the experimental enclosure and confirms the intensification impact of the magnetic field to the paramagnetic fluid flow.

Figures 8 and 9 present the results of the fast Fourier analysis as a power spectrum. Parts a, c and e represent natural convection cases for ΔT = 3, 5, 11 °C respectively, and parts b, d and f thermo-magnetic convection cases at the maximal value of a magnetic induction - 10 T.

Fig. 8
figure 8

Power density as a function of a frequency in Enclosure no.1: (a) b 0max = 0 T, ∆T = 3 °C, (b) b 0max = 10 T, ∆T = 3 °C, (c) b 0max = 0 T, ∆T = 5 °C, (d) b 0max = 10 T, ∆T = 5 °C, (e) b 0max = 0 T, ∆T = 11 °C, (f) b 0max = 10 T, ∆T = 11 °C

Fig. 9
figure 9

Power density as a function of a frequency in Enclosure no.2: (a) b 0max = 0 T, ∆T = 3 °C, (b) b 0max = 10 T, ∆T = 3 °C, (c) b 0max = 0 T, ∆T = 5 °C, (d) b 0max = 10 T, ∆T = 5 °C, (e) b 0max = 0 T, ∆T = 11 °C, (f) b 0max = 10 T, ∆T = 11 °C

Taking into account the theory of turbulent energy flow, as well as the Kolmogorov theorem, certain frequency regions can be distinguished for inertial and viscous-diffusive regimes (see section 4.2). Fluctuations of physical quantities observed as a function of time at a fixed point of space (thermocouples placed in experimental enclosures) are caused by turbulent vortex flowing through this point. These whirls are constantly changing from the largest scales, close to the average scales, to the smallest structures in which turbulent kinetic energy dissipation occurs. With each whirl size, a specific frequency of fluctuations can be observed in a given flow. The largest whirls exhibit the lowest frequency, while the smaller whirls participate in higher frequencies. Therefore, fluctuations occur continuously throughout the frequency band. Internal energy transport plays an important role in the distribution of energy in individual frequency sub-regions. Information about turbulence macroscale can be obtained by analysing the corresponding spectral functions. Colloquially, on the power spectrum, one can distinguish certain frequency regions for which there are inertia and viscous-diffusive subspaces of the wave number. The given patterns show the powers that speak precisely of these ranges.

Spectral analysis in natural convection cases for geometry with a small aspect ratio represents the flat character of the spectrum, which is specific for stable, regular and laminar flows. For ΔT = 5 °C a match to a viscous-diffusive regime for small frequencies can be observed. For the highest temperature difference ΔT = 11 °C a partial match to an inertial-convective regime can be found for low frequencies. Applying magnetic induction to the system significantly changed the flow pattern. The spectral function became more inclined, suggesting that the flow field was destabilized. Partial matches to the inertial-convective regime were observed for all temperature differences.

In geometry with a high aspect ratio a flat power spectrum is characteristic only for the smallest temperature difference, in the case without the magnetic field applied. For temperature differences of 5 and 11 °C the spectrum of temperature variation in natural convection cases present slopes sharper than wave number to −5/3 exponent, indicating that the flow is in a transitional regime. After magnetic induction is applied, destabilization occurs and the power spectrum shows character similar to the inertial-convective regime. The conclusion for now is that a strong magnetic field breaks down irregular vortex structures in the fluid. Numerical simulations and visualization experiments must be performed to confirm this theory.

6 Summary

An experimental analysis of a magnetic field impact on a heat transfer and the behaviour of a fluid was conducted. Two geometries of experimental enclosures were investigated: Enclosure no. 1 with an aspect ratio of 0.5 and Enclosure no.2 with a higher aspect ratio equal 2.0. Various magnetic field inductions were analysed and representative parts of the obtained results were shown in this paper.

The obtained results showed that the aspect ratio of the measurement vessel and the application of an external magnetic field to a magnetic fluid flow have an immense impact on heat transfer rate. While for Enclosure no.1 the Nusselt number starts from 2.95 to 3.61, for Enclosure no.2 heat transfer is almost at least four times greater for the natural convection cases. The performed analyses also demonstrated that magnetic field application to a magnetic fluid flow strongly enhances heat transfer. For every aspect ratio and all temperature differences, the magnetic induction increase from 0 T to 10 T caused an enhancement in heat transfer for at least 250%. The performed spectral analysis allowed a conclusion that an external magnetic field applied to the system causes significant changes in the character of the flow. Introducing an additional new force – magnetic buoyancy one – to a convective motion causes intensification of fluid velocity. Large structures moving with low frequencies, under a strong magnetic field, transform to lower scales where energy dissipation occurs. Further studies, planned by the authors, will concentrate on numerical simulations for these cases and a thorough energy transport investigation.