1 Introduction

Centrifugal pumps are dynamic work-absorbing turbomachines used to increase the pressure of liquid flows in order to meet specific demands of flow systems. Centrifugal pumps transfer energy to liquids using a rotating impeller that increases the momentum of the fluid. Centrifugal pumps are designed so that the cross-sectional area of flow passages inside the pump increases as the fluid flows from the suction side to the discharge side. Thus, the increase in the fluid momentum is converted to increase in its pressure. Centrifugal pumps are essential components in fluid flow systems; they are widely used in different industrial sectors such as power generation, oil and gas, water distribution networks, process industries and heating, ventilation and air conditioning (HVAC). The average energy consumption of these industrial pumping systems is around 90% of the total life cycle costs of the pumps [1]. Thus, increasing the efficiency of centrifugal pumps reduces the operating costs of fluid pumping system, especially for over-sized low-efficiency pumping systems, which constitute significant percentage of industrial pumping system [2]. Moreover, increasing the efficiency of centrifugal pumps contributes towards meeting national and international targets in reducing carbon footprint [1].

Increasing the efficiency of a pumping system is achieved by examining its energy conversion processes in order to reduce the energy losses in each of these processes. A typical pumping system consists of a prime mover used to supply the required work to rotate the pump impeller. This prime mover could be an electric motor, internal combustion engine or turbine. Increasing the efficiency of energy conversion in the prime mover is not related directly to the pump itself. However, both pump and prime mover should be selected so that their mechanical characteristics—rotational speed and torque—match, which enable them to operate close to their maximum efficiency simultaneously [3]. Moreover, the mechanical coupling between the prime mover and the pump should be selected so that the shaft transmission losses are minimised. Other types of energy losses in a pumping system include the hydraulic losses of the pump, which results from the conversion efficiency of the shaft work to hydraulic energy; and the hydraulic efficiency of the fluid flow system itself, which results from the hydraulic losses in fluid flow conduits such as pipes, valves and fittings.

It is not uncommon for pumping systems to operate at variable loads in order to meet variable flow demands. For example, it has been reported that HVAC pumping systems operate at maximum loads for only 6% of their total operating time [4]. Thus, increasing the pumping system efficiency in partial loading enhances its overall operating efficiency significantly. In order to achieve partial loading of a fluid pumping system, the flow rate could be reduced by either using a throttling control valve, or reducing the rotational speed of the pump using a variable speed drive (VSD) [3, 5], among other mechanisms. Using throttling control valves increases the hydraulic energy losses significantly because the pressure losses increase as the fluid flows across a partially open control valve. Moreover, throttling forces the pump to operate at lower efficiency compared to its best efficiency point (BEP), which is a specific operating point defined by unique values of pressure difference and flow rate for each pump model. On the other hand, achieving the partial loading requirements of a pumping system by reducing the pump rotational speed using VSD eliminates these two losses mechanisms. By reducing the pump rotational speed, the power delivered to the pumping system in not in excess. Thus, there is no need to dissipate the energy in the system. Moreover, one could ensure that the pump operates close to its BEP at each rotational speed corresponding to each partial loading requirement, which also reduces the mechanical loads on the pump components due to the reduction in its rotational speed [6, 7]. Thus, VSD is a natural fit in pumping applications when there is a strong variation in the system load profile with time.

When the load profile of the flow system is nearly constant with time, the pump selection process is rather simple—a fixed speed pump model is selected so that its BEP almost coincides with the system operating point. For systems which operate at variable loads, however, selecting a VSP is not as straightforward in all cases because the overall performance of the pump at different partial loads should be optimised in order achieve maximum efficiency [4, 8]. For systems with low or zero static head, i.e. dynamic head systems, the selection process of VSP is similar to that of fixed speed pumps. This is because the pump characteristics can be chosen so that its best efficiency line (BEL) nearly coincides with the system curve. For static head systems, on the other hand, it is difficult, or nearly impossible, to choose a VSP whose BEL coincides with the system curve [9]. However, some general qualitative recommendations exist in such selection process [9]. Another point to consider in VSP selection is the performance metric—the method used to calculate the overall efficiency of variable speed pumping systems. The overall efficiency of such systems is not a simple averaging of individual efficiencies at each rotational speed. It depends, however, on the efficiencies of the operating points, their time of operation and their power. In order to accurately consider all these factors, a performance metric, referred to as true weighted efficiency (TWE), which is equivalent to the overall system efficiency, has been developed to assist in selecting VSPs [4, 8].

The aim of this paper is to develop a VSP selection method based on generic centrifugal pump models—efficiency, characteristics and similitude—rather than using commercial pump models from manufacturers’ databases, which enables to include VSPs in the conceptual design or planning of fluid networks [6]. The derivation of this method maximises the overall hydraulic efficiency, or the TWE, of the pumping system. This derivation results in a single nonlinear algebraic equation which is solved numerically in order to obtain the pump characteristic curve. Subsequently, all the other relevant information, including speed reduction ratios, are obtained.

2 Problem formulation

Consider a fluid pumping system that operates at m different states. Each state of this system is defined by an integer index \(i\in \left\{ 1,m\right\} \) and characterised by a given hydraulic operating point—head, \(H_i\), and discharge, \(Q_i\)—and operating time, \(\mathrm {\Delta }t_i\). In order to meet the flow requirements of this system, a variable speed pump (VSP), which operates at an efficiency \({\eta }_i\) corresponding to the system state i, is used. The total work absorbed by this VSP, \(W_T\), is the summation of the work at each state, \(W_i\), which is expressed as

$$\begin{aligned} W_T=\sum ^m_{i=1}{W_i}=\sum ^m_{i=1}{{E_{H,i}}/{{\eta }_i}}=\sum ^m_{i=1}{{\rho gH_iQ_i\mathrm {\Delta }t_i}/{{\eta }_i}}, \end{aligned}$$
(1)

where \(E_{H,i}\) is the hydraulic energy delivered by the pump, \(\rho \) is the fluid density, and g is the acceleration of gravity. The total work of the pump can also be expressed in terms of the total hydraulic energy, \(E_{H,T}\), and the overall hydraulic efficiency, \({\eta }_T\), as

$$\begin{aligned} W_T={E_{H,T}}/{{\eta }_T}={\left( \sum ^m_{i=1}{\rho gH_iQ_i\mathrm {\Delta }t_i}\right) }/{{\eta }_T}, \end{aligned}$$
(2)

Eqs. (1) and (2) are equal,

$$\begin{aligned} {\left( \sum ^m_{i=1}{H_iQ_i\mathrm {\Delta }t_i}\right) }/{{\eta }_T}=\sum ^m_{i=1}{{H_iQ_i\mathrm {\Delta }t_i}/{{\eta }_i}}. \end{aligned}$$
(3)

Thus, the reciprocal of the overall efficiency is

$$\begin{aligned} {1}/{{\eta }_T}=\sum ^m_{i=1}{{{\mathrm {\Psi }}_i}/{{\eta }_i}}, \end{aligned}$$
(4)

where \({\mathrm {\Psi }}_i\) is the work percentage defined as the ratio of the hydraulic energy delivered at each state i with respect to the total hydraulic energy,

$$\begin{aligned} {\mathrm {\Psi }}_i={H_iQ_i\mathrm {\Delta }t_i}/{\left( \sum ^m_{i=1}{H_iQ_i\mathrm {\Delta }t_i}\right) }. \end{aligned}$$
(5)

The aim of this paper is to select a variable speed pump (VSP) that maximises the overall hydraulic efficiency \({\eta }_T\) of this fluid pumping system, which is identical to the TWE [4, 8]. VSP selection means determining its characteristics (HQ curve) at each state i. In the following analysis, it is assumed that the pump suction pressure is well above vapour pressure so that the pump inlet pressure is within its net positive suction head (NPSH), which means that cavitation does not take place.

2.1 Pump hydraulic efficiency

The hydraulic efficiency of a centrifugal pump, \({\eta }_i\), operating at a specific rotational speed can be expressed as a quadratic equation of the flow rate, \(Q_i\), as [1, 10,11,12]

$$\begin{aligned} {\eta }_i={\alpha }_i+{\beta }_iQ_i+{\gamma }_i{Q_i}^2. \end{aligned}$$
(6)

The efficiency is zero at zero flow rate [1, 3, 10,11,12]

$$\begin{aligned} {\eta }_i\left( Q_i=0\right) =0, \end{aligned}$$
(7)

which results in

$$\begin{aligned} {\alpha }_i=0. \end{aligned}$$
(8)

Furthermore, the efficiency is zero at maximum flow rate, \(Q_{i,m}\) because this flow rate corresponds to zero head,

$$\begin{aligned} {\eta }_i\left( Q_i=Q_{i,m}\right) =0, \end{aligned}$$
(9)

which results in

$$\begin{aligned} {\beta }_i=-Q_{i,m}{\gamma }_i. \end{aligned}$$
(10)

Substituting Eqs. (9) and (10) into Eq. (6) results in

$$\begin{aligned} {\eta }_i=-{\gamma }_iQ_{i,m}Q_i+{\gamma }_i{Q_i}^2. \end{aligned}$$
(11)

By definition, the efficiency is maximum at the optimal flow rate, \(Q_{i,0}\). Thus, the first derivative of the efficiency \({\eta }_i\) with respect to the flow rate vanishes at \(Q_{i,0}\), which is expressed mathematically as

$$\begin{aligned} \frac{{d\eta }_i}{dQ_i}\left( Q_i=Q_{i,0}\right) =-{\gamma }_iQ_{i,m}+2{\gamma }_iQ_{i,0}=0, \end{aligned}$$
(12)

where the parameters \({\alpha }_i\), \({\beta }_i\) and \({\gamma }_i\) are constants for a given rotational speed.

Solving Eq. (12) results in the following relation between the maximum flow rate and the flow rate at BEP, \(Q_{i,0}\),

$$\begin{aligned} Q_{i,m}=2Q_{i,0}. \end{aligned}$$
(13)

Substituting Eq. (13) into Eq. (11) results in

$$\begin{aligned} {\eta }_i={\gamma }_iQ_i\left( Q_i-2Q_{i,0}\right) . \end{aligned}$$
(14)

Since the efficiency is maximum at BEP, a maximum efficiency coefficient, \({\eta }_{i,m}\), can be defined by setting \(Q_i=Q_{i,0}\) in Eq. (14) as

$$\begin{aligned} {\eta }_{i,m}={-\gamma }_i{Q_{i,0}}^2. \end{aligned}$$
(15)

Thus, for a given rotational speed, it is possible to express the parameter \({\gamma }_i\) in terms of the maximum efficiency \({\eta }_{i,m}\) as

$$\begin{aligned} {\gamma }_i=-\frac{{\eta }_{i,m}}{{Q_{i,0}}^2}. \end{aligned}$$
(16)

Substituting Eq. (16) into Eq. (14) results in the pump efficiency equation as

$$\begin{aligned} {\eta }_i=-\frac{{\eta }_{i,m}Q_i}{{Q_{i,0}}^2}\left( Q_i-2Q_{i,0}\right) . \end{aligned}$$
(17)

Thus, for a given value of \({\eta }_{i,m}\), the hydraulic efficiency at a given rotational speed, \({\eta }_i\), is a function of both the known flow rate, \(Q_i\), and the flow rate at BEP, \(Q_{i,0}\).

Equation (17) can be written as

$$\begin{aligned} {\eta }_i=-{\eta }_{i,m}\frac{Q_i}{Q_{i,0}}\left( \frac{Q_i}{Q_{i,0}}-2\right) . \end{aligned}$$
(18)

Define the ratio of the actual flow rate to that at BEP as

$$\begin{aligned} q_i={Q_i}/{Q_{i,0}}. \end{aligned}$$
(19)

Thus, the pump hydraulic efficiency can be written as

$$\begin{aligned} {\eta }_i=-{\eta }_{i,m}q_i\left( q_i-2\right) . \end{aligned}$$
(20)

2.2 Pump characteristics

In this paper, the pump head, \(H_i\), is expressed as a parabolic relation in the flow rate [1, 12] as

$$\begin{aligned} H_i={\theta }_i-{\epsilon }_i{Q_i}^2, \end{aligned}$$
(21)

where \({\theta }_i\) and \({\epsilon }_i\) are the pump parameters, which should have positive values so that the standard shape of the pump characteristic curve is obtained. At BEP, both the pump head and flow rate are at their optimum values, \(H_{i,0}\) and \(Q_{i,0}\). Thus, the HQ relation at BEP based on Eq. (21) is

$$\begin{aligned} H_{i,0}={\theta }_i-{\epsilon }_i{Q_{i,0}}^2, \end{aligned}$$
(22)

which allows to express \({\theta }_i\) in terms of \({\epsilon }_i\) and \(H_{i,0}\) as

$$\begin{aligned} {\theta }_i=H_{i,0}+{\epsilon }_i{Q_{i,0}}^2. \end{aligned}$$
(23)

Substituting Eq. (23) into Eq. (21) results in

$$\begin{aligned} H_i=H_{i,0}+{\epsilon }_i\left( {{{Q_{i,0}}^2-Q}_i}^2\right) . \end{aligned}$$
(24)

Furthermore, the pump head vanishes at the maximum flow rate, \(Q_{i,m}\), which is twice the optimum flow rate, \(Q_{i,0}\), as given by Eq. (13). Substituting Eq. (13) into Eq. (24) at \(H_i=0\) results in the following expression for \({\epsilon }_i\)

$$\begin{aligned} {\epsilon }_i={H_{i,0}}/{\left( 3{Q_{i,0}}^2\right) }. \end{aligned}$$
(25)

Substituting Eq. (25) into Eq. (24) results in the pump characteristic equation being

$$\begin{aligned} H_i=H_{i,0}\left( 1+{\left( {{{Q_{i,0}}^2-Q}_i}^2\right) }/{\left( 3{Q_{i,0}}^2\right) }\right) . \end{aligned}$$
(26)

Rewrite Eq. (26) in terms of \(q_i\) as given by Eq. (19) as

$$\begin{aligned} H_i={H_{i,0}\left( {{4-q}_i}^2\right) }/{3}. \end{aligned}$$
(27)

The final form of the pump efficiency and characteristics, given by Eqs. (20) and (27), respectively, are expressed in terms of the maximum efficiency, optimum flow and optimum head. These equations will be used to derive a maximum efficiency equation for a VSP operating at different loads for known time intervals.

2.3 Pump similitude

In order to relate the pump characteristics and efficiency at different rotational speeds, affinity laws must be applied to VSP. There are two types of affinity laws: generic [13], which are based on pump dimensional analysis; and empirical [14], which are based on performance data of a specific pump model. In this paper, generic affinity laws are used in order to derive a generic model for selecting VSP. However, the following analysis approach could be extended to other affinity laws of specific pump models.

Generic affinity laws for VSP state that at two different rotational speeds, the head and flow rate ratios at BEP are related as

$$\begin{aligned} \left( {H_{R,0}}/{H_{i,0}}\right) ={\left( {Q_{R,0}}/{Q_{i,0}}\right) }^2={q_{i,0}}^2, \end{aligned}$$
(28)

where \(H_{R,0}\) and \(Q_{R,0}\) are the BEP head and flow rate at a reference rotational speed of the pump, respectively.

Equation (28) implies that the characteristics (HQ curves) of the pump are parallel at different rotational speeds. This is because the ratio \({H_{i,0}}/{{Q_{i,0}}^2}\), which is constant, is the slope of HQ curves, \(3{\epsilon }_i\), as shown by Eq. (26). This does not necessarily mean that the maximum efficiencies at all rotational speeds, \({\eta }_{i,m}\), are equal. It means, however, that the normalised efficiency, \({{\eta }_i}/{{\eta }_{i,m}}\), as given by Eq. (20), does not vary with the pump rotational speed. This was confirmed for specific pump models [3], whereby all \({{\eta }_i}/{{\eta }_{i,m}}\) curves almost collapse for different rotational speeds.

It is possible to write \(q_i\), which is defined by Eq. (19), as

$$\begin{aligned} q_i=\frac{Q_i}{Q_{i,0}}=\left( \frac{Q_i}{Q_R}\right) \left( \frac{Q_R}{Q_{R,0}}\right) \left( \frac{Q_{R,0}}{Q_{i,0}}\right) , \end{aligned}$$
(29)

where \(Q_R\) is the actual flow rate of a known reference operating condition. Thus, it is possible to set \(Q_R\) equal to any of the known flow rates. In this paper, \(Q_R\) is equal to the flow rate at the pump rated (maximum operating) speed.

Now, define other flow rate ratios as

$$\begin{aligned} \left( \frac{Q_i}{Q_R}\right) =a_i,\ \ \left( \frac{Q_R}{Q_{R,0}}\right) =q_R,\ \ \left( \frac{Q_{R,0}}{Q_{i,0}}\right) =q_{i,0}. \end{aligned}$$
(30)

Thus, Eq. (29) can be written as

$$\begin{aligned} q_i=a_iq_Rq_{i,0}. \end{aligned}$$
(31)

Since \(a_i\) can be computed using the given flow rates at operating conditions (\(Q_i\)), and \(q_i\) is a function of both \(q_R\) and \(q_{i,0}\), the overall efficiency, \({\eta }_T\), defined by Eq. (4), becomes a function of a single independent variable, \(q_R\), if \(q_{i,0}\) could be represented as a function of \(q_R\). Rewrite Eq. (27) as

$$\begin{aligned} H_{i,0}={3H_i}/{\left( {{4-q}_i}^2\right) }. \end{aligned}$$
(32)

Similarly, the reference head at BEP, \(H_{R,0}\), is expressed as

$$\begin{aligned} H_{R,0}={3H_R}/{\left( {{4-q}_R}^2\right) }. \end{aligned}$$
(33)

Divide Eq. (33) by Eq. (32) and substitute into Eq. (28) results in

$$\begin{aligned} \left( \frac{H_{R,0}}{H_{i,0}}\right) =\left( \frac{H_R}{H_i}\right) \left( \frac{{{4-q}_i}^2}{{{4-q}_R}^2}\right) ={q_{i,0}}^2. \end{aligned}$$
(34)

Similar to the definition of \(a_i\) which is given by Eq. (30), the ratio of the reference head, \(H_R\), to the operating head, \(H_i\), is defined as

$$\begin{aligned} b_i={H_R}/{H_i}. \end{aligned}$$
(35)

Substituting Eq. (35) into Eq. (34) gives

$$\begin{aligned} {q_{i,0}}^2=b_i{\left( {{4-q}_i}^2\right) }/{\left( {{4-q}_R}^2\right) }. \end{aligned}$$
(36)

By definition, the values of the head and flow rate ought to be positive, which means that the values of both \(q_R\) and \(q_i\) should be between 0 and 2. Thus, the square root of Eq. (36) is its positive root as

$$\begin{aligned} q_{i,0}=\sqrt{b_i}{\left( \frac{{{4-q}_i}^2}{{{4-q}_R}^2}\right) }^{0.5}. \end{aligned}$$
(37)

Substituting Eq. (37) into Eq. (31) gives

$$\begin{aligned} q_i=q_R\left( a_i\sqrt{b_i}\right) {\left( \frac{{{4-q}_i}^2}{{{4-q}_R}^2}\right) }^{0.5}. \end{aligned}$$
(38)

The variables in Eq. (38) are separated using some mathematical manipulation, resulting in \(q_i\) being a function of \(q_R\) as

$$\begin{aligned} q_i=\frac{d_iq_R}{\sqrt{1+e_i{q_R}^2}}, \end{aligned}$$
(39)

where

$$\begin{aligned} c_i= & {} {a_i}^2b_i, \end{aligned}$$
(40)
$$\begin{aligned} e_i= & {} {\left( c_i-1\right) }/{4}, \end{aligned}$$
(41)
$$\begin{aligned} d_i= & {} \sqrt{c_i}. \end{aligned}$$
(42)

2.4 Maximum overall hydraulic efficiency

In order to obtain \(q_R\) which maximises the overall efficiency, \({\eta }_T\), or minimises its reciprocal, \({1}/{{\eta }_T}\), the first derivative of Eq. (4) is set equal to zero, while noting that \({\mathrm {\Psi }}_i\) is constant, which results in the following expression:

$$\begin{aligned} \frac{d\left( {1}/{{\eta }_T}\right) }{dq_R}=\sum ^m_{i=1}{{\mathrm {\Psi }}_i\frac{d\left( {1}/{{\eta }_i}\right) }{dq_R}}=0. \end{aligned}$$
(43)

The right-hand side of Eq. (43) is obtained by using the chain rule as

$$\begin{aligned} \frac{d\left( {1}/{{\eta }_i}\right) }{dq_R}=\frac{\partial \left( {1}/{{\eta }_i}\right) }{\partial q_i} \frac{dq_i}{dq_R}. \end{aligned}$$
(44)

In order to obtain \({\partial \left( {1}/{{\eta }_i}\right) }/{\partial q_i}\) as a function of \({\partial {\eta }_i}/{\partial q_i}\), the following equation is used

$$\begin{aligned} \left( {1}/{{\eta }_i}\right) {\eta }_i=1, \end{aligned}$$
(45)

whose first derivative is

$$\begin{aligned} \frac{\partial }{\partial q_i}\left( \left( {1}/{{\eta }_i}\right) {\eta }_i\right) =0. \end{aligned}$$
(46)

Expanding Eq. (46) results in

$$\begin{aligned} \left( {1}/{{\eta }_i}\right) \frac{\partial {\eta }_i}{\partial q_i}+{\eta }_i\frac{\partial \left( {1}/{{\eta }_i}\right) }{\partial q_i}=0, \end{aligned}$$
(47)

which can be written as

$$\begin{aligned} \frac{\partial \left( {1}/{{\eta }_i}\right) }{\partial q_i}=-\left( {1}/{{{\eta }_i}^2}\right) \frac{\partial {\eta }_i}{\partial q_i}. \end{aligned}$$
(48)

In order to obtain \({\partial {\eta }_i}/{\partial q_i}\), it is assumed that \({\eta }_{i,m}\) is not a function of \(q_i\), i.e. \({\eta }_{i,m}\) is constant for all rotational speeds. It was shown that this assumption is valid for up to 30% reduction of the pump nominal speed [1]. Empirical correlations expressing \({\eta }_{i,m}\) as a function of the pump rotational speed have been reported in the literature [15, 16]. Those correlations were accurate in predicting the variable speed efficiency for small pumps [15, 17]. However, they were not as accurate as assuming constant \({\eta }_{i,m}\) for all rotational speeds up to 30% speed reduction in large pumps [15, 17]. Thus, one cannot reach a universal conclusion on such issue. In this paper, it is assumed that \({\eta }_{i,m}\) is constant for all rotational speeds because such assumption results in a generic model, which is the aim of this paper. However, other empirical correlations for \({\eta }_{i,m}\) could be employed using the following approach with additional mathematical manipulation.

Assuming that \({\eta }_{i,m}\) is not a function of \(q_i\), the first derivative of Eq. (20) is

$$\begin{aligned} \frac{\partial {\eta }_i}{\partial q_i}=2{\eta }_{i,m}\left( 1-q_i\right) . \end{aligned}$$
(49)

Thus, the first term on the right-hand side of Eq. (44) is

$$\begin{aligned} \frac{\partial \left( {1}/{{\eta }_i}\right) }{\partial q_i}=\frac{2\left( q_i-1\right) }{{\eta }_{i,m}{q_i}^2{\left( q_i-2\right) }^2}. \end{aligned}$$
(50)

The second term on the right-hand side of Eq. (44) is the first derivative of Eq. (39), as

$$\begin{aligned} \frac{dq_i}{dq_R}=\frac{d_i}{\sqrt{1+e_i{q_R}^2}}\left( 1-\frac{e_i{q_R}^2}{1+e_i{q_R}^2}\right) , \end{aligned}$$
(51)

which, after some mathematical manipulation, is written as

$$\begin{aligned} \frac{dq_i}{dq_R}=d_i{\left( 1+e_i{q_R}^2\right) }^{-3/2}. \end{aligned}$$
(52)

In order to obtain the final form of Eq. (44), substitute Eqs. (50) and (52) into Eq. (44) as

$$\begin{aligned} \frac{d\left( {1}/{{\eta }_i}\right) }{dq_R}=2\left( \frac{d_i}{{\eta }_{i,m}}\right) \left( \frac{\left( q_i-1\right) }{{q_i}^2{\left( q_i-2\right) }^2}\right) {\left( 1+e_i{q_R}^2\right) }^{-3/2}. \end{aligned}$$
(53)

Finally, substitute Eq. (53) into Eq. (43) as

$$\begin{aligned}{} & {} \frac{d\left( {1}/{{\eta }_T}\right) }{dq_R}=\nonumber \\{} & {} \quad \sum ^m_{i=1}{2\left( \frac{d_i{\mathrm {\Psi }}_i}{{\eta }_{i,m}}\right) \frac{\left( q_i-1\right) }{{\left( q_i\left( q_i-2\right) \right) }^2}{\left( 1+e_i{q_R}^2\right) }^{-3/2}=0}, \end{aligned}$$
(54)

which can be written, using Eq. (39), as

$$\begin{aligned}{} & {} \textrm{F}\left( q_R\right) =\frac{d\left( {1}/{{\eta }_T}\right) }{dq_R}=\sum ^m_{i=1}2\left( \frac{{\mathrm {\Psi }}_i}{{\eta }_{i,m}}\right) \nonumber \\{} & {} \quad \left( \frac{q_i-1}{{\left( q_i-2\right) }^2}\right) \left( \frac{{\left( 1+e_i{q_R}^2\right) }^{-{1}/{2}}}{d_i{q_R}^2}\right) =0 \end{aligned}$$
(55)

In order to obtain \(q_R\) which maximises the overall efficiency, \({\eta }_T\), Eq. (55) is solved numerically, with \(q_i\) being a function of \(q_R\) as shown by Eq. (39). Subsequently, Eq. (19) is used to obtain all other flow rates at BEP, \(Q_{i,0}\). Then, the heads at BEP, \(H_{i,0}\) are obtained using the HQ curves given by Eq. (27), which means the VSP has been selected. The efficiency of each state, \({\eta }_i\), is obtained by Eq. (20). Subsequently, the overall hydraulic efficiency of the pumping system, \({\eta }_T\), is obtained by using Eq. (4). Since it has been assumed that the maximum hydraulic efficiency at a given pump speed, \({\eta }_{i,m}\), is constant, which is expressed mathematically as

$$\begin{aligned} {\eta }_{i,m}={\eta }_m; \end{aligned}$$
(56)

therefore, the results for both state and overall efficiency, \({\eta }_i\) and \({\eta }_T\), will be normalised by \({\eta }_m\) in the rest of this paper.

2.5 Numerical solution method

Equation (55) is solved numerically using Newton–Raphson iterative method. The new value of \({q_R}^{n+1}\) at the \(n+1\) iteration is calculated as

$$\begin{aligned} {q_R}^{n+1}={q_{R}}^n-\frac{\textrm{F}\left( {q_R}^n\right) }{{\textrm{F}}^{'}\left( {q_R}^n\right) } \end{aligned}$$
(57)

The first derivative of Eq. (55), \({\textrm{F}}^{'}\left( {q_R}^n\right) \), is obtained numerically using the finite difference method. Because the range of \(q_i\) is between 0 and 2, the solution search is restricted within this range. When \(q_i=1\), the contribution of this specific \(q_i\) in Eq. (55) is zero, i.e. \({\textrm{F}}_i\left( q_R\right) =0\), which means that the operating point coincides with the BEP at this rotational speed. Note that \({\textrm{F}}_i\left( q_R\right) >0\) when \(q_i>0\) and vice versa. Thus, the function \(\textrm{F}\left( q_R\right) \) can be zero in Eq. (55) if all values of \(q_i\) are unity or if they are distributed around unity so that their contributions to \(\textrm{F}\left( q_R\right) \) are equally distributed around zero.

When the operating point corresponds to the reference operating point, \(q_i=q_R\), Eqs. (30), (35), (40) and (41) show that \(a_i=b_i=c_i=d_i=1\). Furthermore, Eq. (42) shows that \(e_i=0\). Thus, the following relation holds:

$$\begin{aligned} {\textrm{F}}_i\left( q_R\right) =2\left( \frac{{\mathrm {\Psi }}_i}{{\eta }_{i,m}}\right) \left( \frac{q_{R}-1}{{{q_R}^2\left( q_R-2\right) }^2}\right) . \end{aligned}$$
(58)

It is clear from Eqs. (55) and (58) that the two critical values of \(q_R\) are 0 and 2. To study the equation behaviour at these two points, substitute these two values in Eq. (39):

  • If \(q_R=0\) , then \(q_i=0\) and \(\textrm{F}\left( q_R\right) =-\infty \).

  • If \(q_R=2\) , then, using Eqs. (41) and (42), \(q_i=2\) and \(\textrm{F}\left( q_R\right) =\infty \).

Since the range of the function varies between \(-\infty \) and \(\infty \), Eq. (55) should have at least one root—at least one \(q_R\) that maximises the overall efficiency, \({\eta }_T\), between 0 and 2. During the numerical solution of Eq. (55), it was noticed that using different initial guess, \({q_R}^0\), leads to the same solution, confirming that there is one value of \(q_R\) within the valid range which maximises the overall efficiency, \({\eta }_T\).

3 Results and discussion

In this section, the developed VSP selection method is tested using five realistic cases studies [18, 19] which are shown in Table 1. The inputs of the developed selection method are the system states: flow rate \(Q_i\), head \(H_i\) and time of operation \(\mathrm {\Delta }t_i\). Note that the speed reduction for cases S2-S5 is higher than the recommended 30% [3, 15, 17]. Thus, the overall hydraulic efficiency is expected to be lower than that predicted for these case studies. Nevertheless, this does not affect the validity of the findings because the aim of this comparison is to show the effects of work percentage and static head variation on the selected VSPs.

Table 1 Case studies [18, 19]

3.1 VSP selection for maximum overall hydraulic efficiency

In order to show the results of the developed VSP selection method, a system with high static head [18], referred to as S1, is used in this section. The system states are shown in Table 2. The minimum flow rate is 72.5% of the maximum flow rate, whereas the minimum head, corresponding to the minimum flow rate, is around 83% of the maximum head.

Table 2 S1 system states [18]
Fig. 1
figure 1

Pump characteristics curve, operating points and BEL for system S1

Fig. 2
figure 2

Work percentage for different operating points for system S1

Fig. 3
figure 3

Normalised efficiency of different operating points and overall efficiency for system S1

Figure 1 shows the characteristics of the selected VSP, its BEL, and its operating points—flow rate and head—for the system S1. It is clear that the pump is selected so that the system curve starts at the right of the pump BEL for the maximum operating point which corresponds to the highest pump speed. As the pump speed is reduced, the system curve crosses the BEL ending at the left of the BEL for the minimum operating point which corresponds to the lowest pump speed. This behaviour is the recommended selection approach for systems with high static head [9]. It is also clear that the operating point of the lowest pump speed is located far from the BEL compared to those of the higher speed. This is due to the work percentage distribution of the system, which is shown in Fig. 2. The work percentage of the point with the lowest flow rate (state 1 in Table 2) is around 10%. Thus, the pump is selected so that its characteristics are biased against that point, as shown in the definition of TWE in Eqs. (4) and (5). Thus, the overall normalised efficiency of the pumping system is closer to the efficiencies of states 2–5 as shown in Fig. 3.

3.2 Effect of work percentage

This section presents a comparison between the selected VSPs for two systems with high static head, S2 and S3 [18]. The operating states of S2 and S3 are shown in Table 3 and Table 4, respectively. For S2, the minimum flow rate is 35% of the maximum flow rate, whereas the minimum head is around 96% of the maximum head. For S3, on the other hand, the minimum flow rate is 59% of the maximum flow rate, whereas the minimum head is around 91% of the maximum head.

Table 3 S2 system states [18]
Table 4 S3 system states [18]
Fig. 4
figure 4

Pump characteristics curve, operating points and BEL a S2, b S3

Fig. 5
figure 5

Work percentage for different operating points, S2 and S3

Fig. 6
figure 6

Normalised efficiency of different operating points and overall efficiency. a S2, b S3

Figure 4 shows the characteristics curves of the selected VSP, its BEL, and the system operating points for S2 (a) and S3 (b). Similar to Fig. 1, the pump is selected so that the maximum operating point, corresponding to the highest pump speed, starts, for both S2 and S3, at the right of BEL, then goes to the left as the pump speed is reduced, crossing the BEL in between. For S2, the operating point of the highest pump speed is located far from the BEL compared to that of the lowest speed. This is due to the work percentage distribution of the system, which is shown in Fig. 5. The operating point of S2 whose flow rate is 0.063 \(m^3/s\), i.e. state 2 in Table 3, has the highest share of the total work—around 60%. This is because its operating time is very high compared to other states, although it is not the point of the highest power. On the contrary, the operating point of the lowest pump speed for S3 is located far from the BEL compared to that of the highest speed. This is because the last four points account for around 80% of the total work, as shown in Fig. 5. It is thus shown in Fig. 6 that the VSP is selected, for each system, so that it has the highest normalised efficiency at the states of the highest work percentage. Again, this confirms that this selection method is biased towards the operating states which require higher work percentage, as shown in the definition of TWE in Eqs. (4) and (5).

3.3 Effect of static and dynamic head

Here, a comparison between the selected VSPs of two systems, S4 and S5 [19], whose operating states are shown in Table 5, is presented. In the work of Salmasi et al. [19], the system head is defined by a quadratic equation which is a function of its operating flow rate. The intercept of this equation, A, is the value of the system static head. In this paper, the system S4 is defined using the same equation, whereas the system S5 is defined by setting \(A=0\) so that the system includes dynamic head only. This is done in order to investigate the effect of static head variation on the selected VSPs. For S4, the minimum flow rate is 50% of the maximum flow rate, whereas the minimum head is around 88% of the maximum head. For S5, on the other hand, the minimum flow rate is 50% of the maximum flow rate, whereas the minimum head is around 33% of the maximum head.

Table 5 S4 (\(A=45.296\)) and S5 (\(A=0\)) system states [19]
Fig. 7
figure 7

Pump characteristics curve, operating points and BEL. a S4, b S5

Fig. 8
figure 8

Work percentage for different operating points, S4 and S5

Fig. 9
figure 9

Normalised efficiency of different operating points and overall efficiency. (a) S4, (b) S5

Figure 7 shows the characteristics curves of the selected VSP, its BEL, and the system operating points for S4 and S5. Because S4 is dominated by static head, its behaviour is similar to S1, S2 and S3. For the system S5, which includes dynamic head only, its BEL almost passes through all the operating points because the intercept of the HQ equation is zero. Thus, the parabolic relation of the selected pump shown in Eq. (18) can almost be fitted with the quadratic relation of the system equation shown in Table 5 with \(A=0\).

Figure 8 shows the work percentage of both systems S4 and S5. For both systems, it is clear that the distributions of the work percentage have similar trends, though the distribution is quantitatively different between the two systems S4 and S5. This is because the system equation of S5 is the same as S4 but without its vertical axis intercept, i.e. its static head. The normalised efficiency distribution is thus qualitatively similar as shown in Fig. 9. The efficiency of S5 is indeed higher than that of S4 because its operating points almost coincide with the BEL of the selected pump.

4 Conclusions

This paper presented a VSPs selection method based on generic mathematical models of centrifugal pumps. The equations describing the pump efficiency, characteristics and similitude were combined resulting in, after appropriate mathematical manipulation, a single nonlinear algebraic equation that maximises the pumping system overall hydraulic efficiency. This equation is a function of a reference flow rate and is solved numerically using Newton–Raphson method. This reference flow rate is subsequently used to obtain the pump characteristic curves at all operating pump speeds. The overall hydraulic efficiency equation used in this paper takes into account the efficiencies of the operating points, their time of operation and their power. The selection method presented in this paper could be extended to other models of centrifugal pumps using different equations describing the pump efficiency, characteristics and similitude as well as other types of turbomachines.

Five case studies of real pumping systems obtained from the literature [18, 19] were investigated in order to assess the developed method. It is shown that:

  1. 1.

    The developed method selects a VSP whose characteristics are biased towards the system states with the highest work percentage, which is significant for systems with high static head.

  2. 2.

    The behaviour of the selected VSPs for systems with high static head is similar to the qualitative recommendations in the literature [9].

  3. 3.

    It is possible to select VSPs for systems with dynamic head only whose BEL almost coincides with the system curve, on the contrary to systems with high static head.

The results show that this method is fast because it requires the numerical solution of a single equation; accurate because it results in VSPs with high efficiency; and reliable because it is capable of operating with different flow curves and head profiles. Since this method uses generic pump models rather than specific models from manufacturers’ databases, its enables the integration of VSP selection in early engineering design phases of pumping systems.