A Comparative study on fire hazards of cables used in nuclear power plants based on small- and large-scale experiments

  • Published:
Journal of Thermal Analysis and Calorimetry Aims and scope Submit manuscript

Abstract

Cables are the most common combustibles in nuclear power plants (NPPs) and cable fires are the one of main threaten to the safety of NPPs. Fire characteristics and fire hazards for two typical cables used in NPPs were comparatively studied based on cone calorimeter and cable tray fire tests. The heat release rate (HRR) curves show different patterns, two-peaks and three-peaks for NPP and conventional flame retardant cables, respectively. This difference is attributed to the fire barrier, which distinguishes the burning of sheath and insulation. Moreover, the maximum value of HRR for conventional flame retardant cable is much higher than NPP flame-retardant cable, and the difference is 108 kW m−2. The time from first peak to second peak for NPP flame-retardant cable is approximately four times as conventional flame retardant cable. Based on cable tray fire, the burning time after burner off is much longer for conventional flame retardant cable and its total mass loss is 0.52 kg, which are three times and five times as much as NPP flame-retardant cable, respectively, and it has a self-sustaining stage during cable burning. The above indicates that the NPP flame-retardant cable has less sustained damage, fire development rate and overall fire hazard. In addition, spacing has little effect on the burning time of sheath, but the burning of insulation layer is promoted, the time from first peak to second peak decreases with the increase in spacing. However, the influence of spacing is non-monotonous in cable tray fire, and the burning of cables with 10 mm spacing has higher fire hazard with a maximum mass loss rate.

This is a preview of subscription content, log in via an institution to check access.

Access this article

Price excludes VAT (USA)
Tax calculation will be finalised during checkout.

Instant access to the full article PDF.

Fig. 1
Fig. 2
Fig. 3
Fig. 4
Fig. 5
Fig. 6
Fig. 7
Fig. 8
Fig. 9
Fig. 10
Fig. 11
Fig. 12
Fig. 13

Similar content being viewed by others

References

  1. Najafi B, Nowlen SP. Fire PRA methodology for nuclear power facilities (NUREG/CR-6850). Washington, DC: U.S. Nuclear Regulatory Commission; 2004.

    Google Scholar 

  2. O’Reilly JP, Moseley NC, Keppler JG, Howard EM, Engelken RH. Cable Fire at Browns Ferry Nuclear Power Station, NRC Bullentin BL-75-04. Washington, DC: U.S. Nuclear Regulatory Commission; 1975.

    Google Scholar 

  3. Organization for Economic Co-operation and Development (OECD), OECD FIRE Database (OECD FIRE DB 2010:1), Nuclear Energy Agency (NEA); 2011.

  4. Barnes MA, Briggs PJ, Hirschler MM, Matheson AF, O’Neill TJ. A comparative study of the fire performance of halogenated and non-halogenated materials for cable applications. Part I tests on materials and insulated wires. Fire Mater. 1996;20:1–16. https://doi.org/10.1002/(SICI)1099-1018(199601)20:1%3c1::AID-FAM553%3e3.0.CO;2-W.

    Article  CAS  Google Scholar 

  5. Barnes MA, Briggs PJ, Hirschler MM, Matheson AF, O’Neill TJ. A comparative study of the fire performance of halogenated and non-halogenated materials for cable applications. Part II tests on cable. Fire Mater. 1996;20:17–37. https://doi.org/10.1002/(SICI)1099-1018(199601)20:1%3c17::AID-FAM554%3e3.0.CO;2-C.

    Article  CAS  Google Scholar 

  6. Zavaleta P, Bascou S, Suard S. Effects of cable tray configuration on fire spread. In: Fifteenth international conference of the fire and materials, San Francisco, USA, 2017, pp. 17–30.

  7. Gallo E, Stöcklein W, Klack P, Schartel B. Assessing the reaction to fire of cables by a new bench-scale method. Fire Mater. 2017;41:768–78. https://doi.org/10.1002/fam.2417.

    Article  CAS  Google Scholar 

  8. Hirschler MM. Comparison of large-and small-scale heat release tests with electrical cables. Fire Mater. 1994;18(2):61–76. https://doi.org/10.1002/fam.810180202.

    Article  CAS  Google Scholar 

  9. Stein AB, Sparrow EM, Gorman JM. Numerical simulation of cables in widespread use in the nuclear power industry subjected to fire. Fire Saf J. 2012;53:28–34. https://doi.org/10.1016/j.firesaf.2012.06.004.

    Article  Google Scholar 

  10. Braun E, Shields JS, Harris RH. Flammability characteristics of electrical cables using the cone calorimeter. NIST Rep NISTIR. 1989;88:4003.

    Google Scholar 

  11. Courty L, Garo JP. External heating of electrical cables and auto-ignition investigation. J Hazard Mater. 2017;321(1):528–36. https://doi.org/10.1016/j.jhazmat.2016.09.042.

    Article  CAS  Google Scholar 

  12. Xie QY, Gong T, Huang XY. Fire zone diagram of flame-retardant cables: ignition and upward flame spread. Fire Technol. 2021;57:2643–59. https://doi.org/10.1007/s10694-021-01133-x.

    Article  Google Scholar 

  13. Zhang BS, Zhang JQ, Li Q, et al. Effects of insulating material ageing on ignition time and heat release rate of the flame retardant cables. Proc Eng. 2018;211:972–8. https://doi.org/10.1016/j.proeng.2017.12.099.

    Article  CAS  Google Scholar 

  14. Wang Z, Wang J. An experimental study on the fire characteristics of new and aged building wires using a cone calorimeter. J Therm Anal Calorim. 2019;135:3115–22. https://doi.org/10.1007/s10973-018-7626-8.

    Article  CAS  Google Scholar 

  15. Beneš M, Milanov N, Matuschek G, et al. Thermal degradation of PVC cable insulation studied by simultaneous TG-FTIR and TG-EGA methods. J Therm Anal Calorim. 2004;78:621–30. https://doi.org/10.1023/B:JTAN.0000046123.59857.ad.

    Article  Google Scholar 

  16. Xie QY, Zhang HP, Tong L. Experimental study on the fire protection properties of PVC sheath for old and new cables. J Hazard Mater. 2010;179(1–3):373–81. https://doi.org/10.1016/j.jhazmat.2010.03.015.

    Article  CAS  Google Scholar 

  17. Gallucci R. Statistical characterization of cable electrical failure temperatures due to fire for nuclear power plant risk applications. Fire Technol. 2017;53:401–12. https://doi.org/10.1007/s10694-016-0616-0.

    Article  Google Scholar 

  18. Zhang Y, Tang KX, Liu ZY, et al. Experimental study on thermal and fire behaviors of energized PE-insulated wires under overload currents. J Therm Anal Calorim. 2021;145:345–51. https://doi.org/10.1007/s10973-020-09745-1.

    Article  CAS  Google Scholar 

  19. Tang KX, Wu S, Zhang HM, Li CW, Yuan BH, Zhang Y. Analysis of heat transfer during flame spread over energized-wire under high currents. Int J Therm Sci. 2022;17:1. https://doi.org/10.1016/j.ijthermalsci.2021.107191.

    Article  CAS  Google Scholar 

  20. Hu LH, Zhang Y, Yoshioka K, Izumo H, Fujita O. Flame spread over electric wire with high thermal conductivity metal core at different inclinations. Proc Combust Inst. 2015;35:2607–14. https://doi.org/10.1016/j.proci.2014.05.059.

    Article  CAS  Google Scholar 

  21. Huang XY, Nakamura Y. A review of fundamental combustion phenomena in wire fires. Fire Technol. 2020;56:315–60. https://doi.org/10.1007/s10694-019-00918-5.

    Article  Google Scholar 

  22. Huang P, Ye SL, Qin L, et al. Experimental study on the maximum excess ceiling gas temperature generated by horizontal cable tray fires in urban utility tunnels. Int J Therm Sci. 2022;172: 107341. https://doi.org/10.1016/j.ijthermalsci.2021.107341.

    Article  Google Scholar 

  23. Audouin L, Prétrel H, Zavaleta P, OECD PRISME 2 fire research project (2011–2016) –Current status and perspectives. In: 13th International seminar on fire safety in nuclear power plants and installations, Columbia, USA, 2013, pp. 69–84

  24. Grayson SJ, Hees PV, Vercellotti U, Breulet H, Green A. Fire performance of electric cables (FIPEC). In: Final report on the European SMT programme sponsored research project SMT 4-CT96-2059. Interscience Communications Limited, Greenwich, UK, 2000.

  25. Hees PV, Axelsson J, Green AM, Grayson SJ. Mathematical modelling of fire development in cable installations. Fire Mater. 2001;25:169–78. https://doi.org/10.1002/fam.767.

    Article  CAS  Google Scholar 

  26. Hees PV, Hirschler MM, Axelsson J, Green AM. Development of a composite pyrolysis model for prediction of the heat release rate from cables by means of material testing in the cone calorimeter. In: Interflam 9th international fire science & engineering conference. 2001; pp. 1107–1116.

  27. Meinier R, Sonnier R, Zavaleta P, et al. Fire behavior of halogen-free flame retardant electrical cables with the cone calorimeter. J Hazard Mater. 2018;342:306–16. https://doi.org/10.1016/j.jhazmat.2017.08.027.

    Article  CAS  Google Scholar 

  28. Elliot PJ, Whiteley RH. Cone calorimeter test for the measurement of flammability properties of insulated wire. Polym Degrad Stabil. 1999;64:577–84. https://doi.org/10.1016/S0141-3910(98)00135-9.

    Article  CAS  Google Scholar 

  29. Hirschler MM. Flame retardants and heat release: review of traditional studies on products and on groups of polymers. Fire Mater. 2015;39:207–31. https://doi.org/10.1002/fam.2243.

    Article  CAS  Google Scholar 

  30. Rao BN, Jothi RA, Srinivasan AR, Sudhindra A. Heat release measurements on FRLS cables using cone calorimeter-CPRI's experience, proceedings of fire mater and conference. 2007.

  31. Magalie C, Anne-Sophie C, Rodolphe S, et al. Fire behavior of electrical cables in cone calorimeter: influence of cables structure and layout. Fire Saf J. 2018;99(7):12–21. https://doi.org/10.1016/j.firesaf.2018.05.001.

    Article  Google Scholar 

  32. Nowlen SP. A summary of nuclear power plant fire safety research at Sandia National Laboratories, 1975–1987, NUREG/CR-5384, SAND89*1359. Sandia National Laboratories, Albuqueque, New Mexico, 1989.

  33. U.S. NRC, 2013a. Cable heat release, ignition, and spread in tray installations during fire (CHRISTIFIRE) phase 1: horizontal trays, NUREG/CR-7010, vol. 1. U.S. Nuclear Regulatory Commission, Washington, DC.

  34. U.S. NRC, 2013b. Cable heat release, ignition, and spread in tray installations during fire (CHRISTIFIRE) phase 2: vertical shafts and corridors, NUREG/CR-7010, vol.2. U.S. Nuclear Regulatory Commission, Washington, DC.

  35. Li L, Huang X, Bi K, et al. An enhanced fire hazard assessment model and validation experiments for vertical cable trays. Nucl Eng Des. 2016;301(5):32–8. https://doi.org/10.1016/j.nucengdes.2015.12.034.

    Article  CAS  Google Scholar 

  36. Olaf R, Dietmar H, Marna R. Evaluation of fire models for nuclear power plant applications, benchmark exercise no.5: Flame Spread in Cable Tray Fires, 2006.

  37. Huang X, Wang Y, Zeng W, Peng L, Cheng AC, Chow W. Compartment temperature estimation of a multiple-layer cable tray fire with different cable arrangements in a closed compartment. J Fire Sci. 2019;37:303–19. https://doi.org/10.1177/0734904119860410.

    Article  CAS  Google Scholar 

  38. Huang X, Zhu H, Peng L, Zheng Z, Zeng W, Bi K, et al. Thermal characteristics of vertically spreading cable fires in confined compartments. Fire Technol. 2019;55:1849–75. https://doi.org/10.1007/s10694-019-00833-9.

    Article  Google Scholar 

  39. Huang X, Zhu H, Peng L, Zheng Z, Zeng W, Bi K, et al. Burning behavior of cable tray located on a wall with different cable arrangements. Fire Mater. 2019;43:64–73. https://doi.org/10.1002/fam.2669.

    Article  CAS  Google Scholar 

  40. Huang X, Zhu H, He L, et al. Improved model for estimating sidewall effect on the fire heat release rate of horizontal cable tray. Process Saf Environ Prot. 2021;149(5):831–8. https://doi.org/10.1016/j.psep.2021.03.040.

    Article  CAS  Google Scholar 

  41. ISO 5660, International Standard-Fire Tests-Reaction to Fire-Rate of Heat Release from Building Products (ISO 5660), International Organization for Standardization, Geneva, Switzerland, 1993.

  42. Hugget C. Estimation of rate heat release by means of oxygen consumption measurements. Fire Mater. 1980;4(2):61–5. https://doi.org/10.1002/fam.810040202.

    Article  Google Scholar 

  43. EN 50399: 2011 Common test methods for cable under fire conditions—heat release and smoke production measurement of cables during flame spread test—test apparatus, procedures, results.

  44. Polansky R, Polanská M. Testing of the fire-proof functionality of cable insulation under fire conditions via insulation resistance measurements. Eng Fail Anal. 2015;57:334–49. https://doi.org/10.1016/j.engfailanal.2015.08.001.

    Article  Google Scholar 

Download references

Acknowledgements

The authors gratefully the financial supports from the National Natural Science Foundation of China (Nos. 52074202, 52104211), the Fundamental Research Funds for the Central Universities (WUT: 2021IVA204), and the Natural Science Foundation of Jiangsu Province (No. BK20201030).

Author information

Authors and Affiliations

Authors

Contributions

All authors contributed to the study conception and design. Material preparation, data collection and analysis were performed by KT, YZ and BY. The first draft of the manuscript was written by KT and all authors commented on previous versions of the manuscript. All authors read and approved the final manuscript.

Corresponding author

Correspondence to Bihe Yuan.

Additional information

Publisher's Note

Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Rights and permissions

Springer Nature or its licensor holds exclusive rights to this article under a publishing agreement with the author(s) or other rightsholder(s); author self-archiving of the accepted manuscript version of this article is solely governed by the terms of such publishing agreement and applicable law.

Reprints and permissions

About this article

Check for updates. Verify currency and authenticity via CrossMark

Cite this article

Tang, K., Zhang, Y., Jiang, S. et al. A Comparative study on fire hazards of cables used in nuclear power plants based on small- and large-scale experiments. J Therm Anal Calorim 147, 14659–14671 (2022). https://doi.org/10.1007/s10973-022-11578-z

Download citation

  • Received:

  • Accepted:

  • Published:

  • Issue Date:

  • DOI: https://doi.org/10.1007/s10973-022-11578-z

Keywords

Navigation