1 Introduction

Counter-flow heat exchangers are widely used in food and refinery industry and are an important element of various types of installations.

In a counter-flow heat exchanger, the heat transfer fluids flow in opposite directions. Figure 1 is a diagram of a double-tube counter-flow heat exchanger, illustrating the notation used and the flow directions of both fluids. In this case, the hot fluid flows inside the inner tube, while the heated one inside the outer tube [16].

Fig. 1
figure 1

Counter-flow heat exchanger diagram with the notation used

The temperature profile along the length of the counter-flow heat exchanger under consideration for both fluids is shown in Fig. 2 [16].

Fig. 2
figure 2

Temperature distribution along the length of the counter-flow heat exchanger under consideration

During operation of the counter-flow heat exchanger, variations in temperatures (T h1; T c1) and mass flow rates (\(\dot{m}_{h} ,{\kern 1pt} {\kern 1pt} \dot{m}_{c}\)) at the inlet of the heat exchanger may occur, which affects the heat exchanger performance. Counter-flow heat exchangers are often part of a more complex system, and changes in their performance affect the behaviour of the entire system. Therefore, it is important to know the performance of a counter-flow heat exchanger in off-design conditions. To assess its performance, the first and second law of thermodynamics [5, 79] are utilized. From the first law of thermodynamics and Peclet’s law a concept of effectiveness can be derived. Heat transfer effectiveness is commonly used to describe the heat exchanger performance under off-design conditions, defined as the ratio of the actual to the maximum heat flow rate [15].

$$\varepsilon = \frac{{\dot{Q}}}{{\dot{Q}_{\hbox{max} } }}$$
(1)

Other quantities are also used to assess the exchanger performance, e.g. the heat exchanger efficiency defined as the ratio of the actual to the optimum rate of heat transfer [1012]. To determine the performance of heat exchangers, the required, or obtained, heat transfer units [13] were also proposed. For a counter-flow heat exchanger, the heat transfer effectiveness is a function of two parameters: NTU and C; it has the following form [15]:

$$\varepsilon = \frac{{1 - \exp \left[ {\left( {C - 1} \right) \cdot NTU} \right]}}{{1 - C \cdot \exp \left[ {\left( {C - 1} \right) \cdot NTU} \right]}}$$
(2)

Parameter C is a ratio of heat capacity rates of both fluids: \(C = \frac{{\dot{C}_{2} }}{{\dot{C}_{1} }}\); the numerator is the smaller heat capacity rate of one fluid, while the denominator is the larger heat capacity rate of the other fluid. The fluid heat capacity rate is a product of specific heat at constant pressure and the mass flow rate: \(\dot{C} = c_{p} \dot{m}\). The parameter NTU is equal to a product of an overall heat transfer coefficient and the heat transfer surface area, divided by the smaller fluid heat capacity \(NTU = \frac{UA}{{\dot{C}_{2} }}\).

The analytical solution for the effectiveness of a counterflow heat exchanger in which a uniform, external heat load is applied to one or both sides is presented in [14].

In order to determine the effectiveness of a counter-flow heat exchanger according to relation (2), more equations are needed, e.g. for heat transfer coefficients of both fluids, the overall heat transfer coefficient and the thermodynamic functions, to calculate thermodynamic properties of the fluids, such as specific heat, viscosity, thermal conductivity, and density. All these relations form a set of equations. The thermodynamic properties should be calculated for average fluid temperatures; therefore, the calculations must be carried out iteratively, because the outlet temperatures are not known. Based on the set of equations, simulators of counter-flow heat exchangers have been created [6, 15, 16].

In the literature, approximate relations can also be found that allow to determine the effectiveness of the counter-flow heat exchanger quickly and with good accuracy as a function of the number of transfer units and the ratio of the heat capacity rates [17, 18].

In the article, yet another approach was taken to describe the effectiveness of the counter-flow heat exchanger. It was decided to treat the counter-flow heat exchanger as a ‘black box’ to examine how input variables affect the output variables, and, on this basis, to propose an approximate relation describing the performance of the counter-flow heat exchanger in off-design conditions.

The overall heat transfer coefficient U is mainly the function of velocities [mass flow rates (\(\dot{m}_{h} ,{\kern 1pt} {\kern 1pt} \dot{m}_{c}\))] of both fluids and the temperatures (T h1; T c1) at the inlet of the heat exchanger. Assuming that the thermodynamic properties of the fluids are constant (c p  = const), one can define the heat transfer effectiveness as a function of the following parameters at the inlet of the heat exchanger:

$$\varepsilon = f\left( {T_{h1} ,T_{c1} ,\dot{m}_{h} ,\dot{m}_{h} ,type{\kern 1pt} \,of\,heat\,exchanger} \right)$$
(3)

In this paper, an attempt was made to produce a relation for the heat transfer effectiveness as a function of the parameters only at the inlet of the heat exchanger (temperatures and mass flow rates). To this end, the counter-flow heat exchanger was considered as a ‘black box’ (Fig. 3), and the effect of each of the inlet variables on the outlet variables was investigated. The inlet variables were: temperatures (T h1; T c1) and mass flow rates (\(\dot{m}_{h} ,{\kern 1pt} {\kern 1pt} \dot{m}_{c}\)) at the inlet of the heat exchanger. The outlet variables were: the temperatures of the fluids at the outlet of the heat exchanger (T h2; T c2).

Fig. 3
figure 3

Parameters at the inlet and outlet of the counter-flow heat exchanger

2 The mathematical model

2.1 The black box model of the heat exchanger

This model was used to investigate how the inlet parameters (temperatures and mass flow rates of both fluids at the inlet of the heat exchanger) affect the outlet parameters (temperatures of both fluids at the outlet of the heat exchanger).

The outlet temperature of the cold fluid can be written as (Fig. 2)

$$T_{c2} = T_{h1} - \Delta T_{2}$$
(4)

The relation (4) can be converted to a form involving the heat transfer effectiveness:

$$\varepsilon = \frac{{T_{c2} - T_{c1} }}{{T_{h1} - T_{c1} }} = 1 - \frac{{\Delta T_{2} }}{{T_{h1} - T_{c1} }}$$
(5)

The temperature difference (ΔT 2 = T h1 − T c2) and the heat transfer effectiveness depend on the same independent variables:

$$\Delta T_{2} = f\left( {T_{h1} ,T_{c1} ,\dot{m}_{h} ,\dot{m}_{h} ,type\,of\,heat\,exchanger} \right)$$
(6)

The effect of each of the independent variables on the temperature difference (ΔT 2) was analysed. One independent variable was assumed to vary; other independent variables were constant:

$$\Delta T_{2} = f\left( {T_{h1} } \right)$$
(7)
$$\Delta T_{2} = f\left( {T_{c1} } \right)$$
(8)
$$\Delta T_{2} = f\left( {\dot{m}_{c} } \right)$$
(9)
$$\Delta T_{2} = f\left( {\dot{m}_{h} } \right)$$
(10)

Based on the data produced by a counter-flow heat exchanger simulator, linear relations between the temperature difference (ΔT 2) and the temperatures at the inlet of the heat exchanger were obtained.

$$\Delta T_{2} = a_{1} T_{c1} + a_{2}$$
(11)
$$\Delta T_{2} = a_{3} T_{h1} + a_{4}$$
(12)

Taking into account (11, 12), the effect of the change in the inlet temperature (T h1; T c1) on the temperature difference (ΔT 2) can take the form

$$\Delta T_{2} = a_{1} T_{c1} + a_{3} T_{h1} + a_{2} + a_{4}$$
(13)

The relation for the temperature difference (ΔT 2) as a function of the inlet temperatures (T h1; T c1) is linear (13). However, it was difficult to find appropriate functions to describe the relation for the temperature difference (ΔT 2) as a function of mass flow rates (\(\dot{m}_{h} ,{\kern 1pt} {\kern 1pt} \dot{m}_{c}\)). Attempts were made to approximate these relations using various functions but with no satisfactory results. Therefore, the relation for the temperature difference (ΔT 2) as a function of mass flow rates (\(\dot{m}_{h} ,{\kern 1pt} {\kern 1pt} \dot{m}_{c}\)) was shown using logarithmic coordinates. This approach also allowed to obtain, approximately, a linear relation for the temperature difference (ΔT 2) as a function of mass flow rates. Since the arguments of a logarithmic function were required not to be dimensional quantities, the mass flow rates were divided by a reference mass of 1 kg/s, and similarly the temperature differences ΔT 2 were divided by 1 °C.

$$\ln \left( {\Delta T_{2} } \right) = a_{5} \ln \left( {\dot{m}_{h} } \right) + a_{6}$$
(14)
$$\ln \left( {\Delta T_{2} } \right) = a_{7} \ln \left( {\dot{m}_{c} } \right) + a_{8}$$
(15)

Taking into account (14, 15), the effect of the change in the mass flow rates of both fluids (\(\dot{m}_{h} ,{\kern 1pt} {\kern 1pt} \dot{m}_{c}\)) on the temperature difference (ΔT 2) can be written as

$$\ln \left( {\Delta T_{2} } \right) = a_{5} \ln \left( {\dot{m}_{h} } \right) + a_{7} \ln \left( {\dot{m}_{c} } \right) + a_{6} + a_{8}$$
(16)

The relation (16) can be transformed into

$$\Delta T_{2} = C\left( {\frac{{\dot{m}_{c} }}{{\dot{m}_{h} }}} \right)^{{a_{9} }} \left( {\dot{m}_{h} } \right)^{{a_{10} }}$$
(17)

Following the analysis of the relations (13 and 17) one can write:

$$\Delta T_{2} = \left( {A_{1} T_{c1} + A_{2} T_{h1} + A_{3} } \right)\left( {\frac{{\dot{m}_{c} }}{{\dot{m}_{h} }}} \right)^{{A_{4} }} \left( {\dot{m}_{h} } \right)^{{A_{5} }}$$
(18)

The proposed relations (18 and 5) were verified against the data produced by a simulator of a double tube counter-flow heat exchanger. In the simulator, common relations for heat transfer coefficients relevant to a turbulent flow [3, 4, 1921] for both fluids were used. Water was used as heat transfer fluids. The hot fluid was flowing inside the smaller tube, while the cold one inside the larger tube. For the purpose of simplification, the overall heat transfer coefficient (U) was calculated as in the case of a flat wall [3, 4, 22, 23]. The outer diameters were 0.03 m (the inner tube) and 0.043 m (the outer tube). The length of the heat exchanger was 1 m. The inlet parameters varied within the following ranges: the temperature of the hot fluid T h1 <48; 52>°C; the temperature of the cold fluid T c1 <17; 21>°C; the mass flow rate of the hot fluid \(\dot{m}_{h}\) <0.1; 0.5> kg/s; the mass flow rate of the cold fluid \(\dot{m}_{c}\) <0.03; 0.07> kg/s. The cases where heat capacity rates of both fluids were equal were also considered. For equal heat capacity rates, the values were chosen from one or the other range of changes in the mass flow rate. Another example of a double-tube counter-flow heat exchanger simulator along with the ranges of inlet parameter variations can be found in the literature [6].

2.2 Heat exchanger model based on the ratio of the minimum and the actual arithmetic mean temperature difference

The proposed relation (18) is a function of inlet parameters but it contains five constant coefficients which need to be determined based on the real or simulator data. These coefficients vary depending on the counter-flow heat exchanger-specific geometry (inner and outer diameter, length, etc.) and on the fluid (water, air, etc.). Since no general-purpose relation could be produced for the heat transfer effectiveness of a counter-flow heat exchanger as a function of inlet parameters, another approach was chosen, namely to analyse the ratio of the minimum to the actual arithmetic mean temperature difference and to investigate possible solutions (Fig. 2).

$$\frac{{\Delta T_{a\hbox{min} } }}{{\Delta T_{a} }} = \frac{{\Delta T_{1} /2}}{{\left( {\Delta T_{1} + \Delta T_{2} } \right)/2}} = \frac{{\Delta T_{1} }}{{\Delta T_{1} + \Delta T_{2} }}$$
(19)

It was assumed that, with good approximation, the logarithmic mean temperature difference can be replaced by the arithmetic mean temperature difference (Fig. 2) [3, 4, 21, 24, 25].The relation (19) can be transformed into

$$\frac{{\Delta T_{1} }}{{\Delta T_{1} + \Delta T_{2} }} = \frac{{\left( {T_{c2} - T_{c1} } \right)\left( {1 - \frac{{T_{h1} - T_{h2} }}{{T_{c2} - T_{c1} }}} \right)}}{{\frac{{4\left[ {T_{h2} + T_{h1} - (T_{c2} + T_{c1} )} \right]}}{2}}} + \frac{1}{2}$$
(20)

The following stems from the heat exchanger energy balance:

$$C = \frac{{\dot{C}_{2} }}{{\dot{C}_{1} }} = \frac{{T_{h1} - T_{h2} }}{{T_{c2} - T_{c1} }}$$
(21)

According to the Peclet’s law, assuming that, with good approximation, the logarithmic mean temperature difference can be replaced by the arithmetic mean temperature difference, the following can be written:

$$NTU = \frac{UA}{{\dot{C}_{2} }} = \frac{{\left( {T_{c2} - T_{c1} } \right)}}{{\frac{{\left[ {T_{h2} + T_{h1} - (T_{c2} + T_{c1} )} \right]}}{2}}}$$
(22)

Finally, the relation (20), noted as the parameter (α), can be written as

$$\alpha = \frac{{\Delta T_{1} }}{{\Delta T_{1} + \Delta T_{2} }} = \frac{NTU}{4}(1 - C) + \frac{1}{2}$$
(23)

Whereas

$$\frac{{\Delta T_{1} }}{{\Delta T_{1} + \Delta T_{2} }} + \frac{{\Delta T_{2} }}{{\Delta T_{1} + \Delta T_{2} }} = 1$$
(24)

From the relations (24 and 23) it follows that

$$\frac{{\Delta T_{2} }}{{\Delta T_{1} + \Delta T_{2} }} = \frac{1}{2} - \frac{NTU}{4}(1 - C)$$
(25)

By dividing the relation (23) by (25), a relation is obtained between the temperature difference at the front and at the back of the heat exchanger (Fig. 2) and the ratio of heat capacity rates and NTU.

$$\frac{{\Delta T_{1} }}{{\Delta T_{2} }} = \frac{{\frac{NTU}{4}(1 - C) + \frac{1}{2}}}{{\frac{1}{2} - \frac{NTU}{4}(1 - C)}}$$
(26)

The relation (23) can be transformed into

$$\Delta T_{2} = \frac{(C - 1)(1 - \alpha )}{C - \alpha \,C - \alpha }(T_{h1} - T_{c1} )$$
(27)

Taking into account (5, 27), the heat transfer effectiveness of a counter-flow heat exchanger can be approximately written as

$$\varepsilon = \frac{{T_{c2} - T_{c1} }}{{T_{h1} - T_{c1} }} = 1 - \frac{(C - 1)(1 - \alpha )}{C - \alpha \,C - \alpha } = 1 - \frac{(1 - C)(1 - \alpha )}{\alpha + \alpha \,C - C}$$
(28)

The proposed relations for the temperature difference ΔT 2 (27) and the heat transfer effectiveness (28) contain no constant coefficients and are functions of two variables (C; NTU). In order to determine NTU, the overall heat transfer coefficient U needs to be determined.

3 Results

3.1 Results of the black box model

Using the data produced by a simulator of a double-tube counter-flow heat exchanger, the effect of inlet variables (the temperatures at the inlet of the heat exchanger and the mass flow rates of both fluids) on the temperature difference ΔT 2 was analysed.

The effect of the change in the hot fluid temperature (T h1) and the cold fluid temperature (T c1) on the temperature difference (ΔT 2) is shown in Figs. 4 and 5, respectively.

Fig. 4
figure 4

The effect of the temperature change (T h1) on the temperature difference (ΔT 2)

Fig. 5
figure 5

The effect of the temperature change (T c1) on the temperature difference (ΔT 2)

Based on the data shown in Fig. 4, it can be observed that the change in the hot fluid temperature at the inlet of the heat exchanger has a linear effect on the temperature difference ΔT 2.

The change in the cold fluid temperature at the inlet of the heat exchanger has also a linear effect on the temperature difference ΔT 2 (Fig. 5). The effect of the change in the hot fluid mass flow rate (\(\dot{m}_{h}\)) and the cold fluid mass flow rate (\(\dot{m}_{c}\)) on the temperature difference (ΔT 2) is shown in Figs. 6 and 7, respectively.

Fig. 6
figure 6

The effect of the change in the mass flow rate (\(\dot{m}_{h}\)) on the temperature difference (ΔT 2)

Fig. 7
figure 7

The effect of the change in the mass flow rate (\(\dot{m}_{c}\)) on the temperature difference (ΔT 2)

The change in the hot fluid mass flow rate has no linear effect on the temperature difference (ΔT 2) (Fig. 6).

Similarly, the effect of the change in the cold fluid mass flow rate on the temperature difference (ΔT 2) is not linear (Fig. 7). Attempts were made to approximate the variation path presented in Figs. 6 and 7 using various functions but with no satisfactory results. Therefore, it was decided to show the nature of the variations in these quantities using logarithmic coordinates.

The effect of the change in the mass flow rate (\(\dot{m}_{h}\)) and the mass flow rate (\(\dot{m}_{c}\)) on the temperature difference (ΔT 2) in logarithmic coordinates is shown in Figs. 8 and 9, respectively.

Fig. 8
figure 8

The effect of the change in the mass flow rate (\(\dot{m}_{h}\)) on the temperature difference (ΔT 2) in logarithmic coordinates

Fig. 9
figure 9

The effect of the change in the mass flow rate (\(\dot{m}_{c}\)) on the temperature difference (ΔT 2) in logarithmic coordinates

Based on the data in logarithmic coordinates as shown in Figs. 8 and 9, the effect of mass flow rates on the temperature difference (ΔT 2) can be well approximated using simple functions (14, 15).

The comparison between the temperature difference (ΔT 2) obtained using the data from the simulator and the one calculated from the proposed relation (18) is shown in Fig. 10.

Fig. 10
figure 10

A comparison between the temperature difference (ΔT 2) as obtained using the data from the simulator and as calculated from the proposed relation (18)

The points in Fig. 10 are located along the line (y = x), which indicates that the proposed relation (18) is highly accurate.

Data used in the above analysis are shown in Tables 1 and 2.

Table 1 Data concerning the counter-flow heat exchanger under consideration (different mass flow rates of both fluids)
Table 2 Data concerning the counter-flow heat exchanger under consideration (equal mass flow rates of both fluids)

The inlet and outlet temperatures, mass flow rates, the temperature differences as obtained from the simulator and from the proposed relation (18) and their differences for different mass flow rates of both fluids are presented in Table 1.

An example of inlet and outlet temperatures, mass flow rates, temperature differences obtained from the simulator and from the proposed relation (18), and their differences for equal mass flow rates for both fluids are shown in Table 2.

The difference between ΔT 2 as obtained from the simulator and from the proposed relation (18) corresponds to the difference between T c2 as calculated from the simulator and from the proposed relation (18). These differences are small and their maximum value is equal to 0.44, so the proposed relation (18) can be considered accurate.

3.2 Results of the model involving the parameter α

The relation (27) was verified against the data produced by a simulator of a double-tube heat exchanger. Figure 11 illustrates a comparison between the temperature difference (ΔT 2) obtained using the data from the simulator and the one calculated from the proposed relation (27).

Fig. 11
figure 11

A comparison between the temperature difference (ΔT 2) as obtained using the simulator and as calculated from the proposed relation (27)

In Fig. 11 there are fewer points than in Fig. 10 as the points of equal heat capacity rates of both fluids were not included. For identical heat capacity rates the relation (27) takes an indefinite value of 0/0.

Figure 12 illustrates a comparison between the heat transfer effectiveness as calculated from the definition (1) and from the proposed relation (28).

Fig. 12
figure 12

A comparison between the heat transfer effectiveness as calculated from the definition (1) and from the proposed relation (28)

The points in Figs. 11 and 12 are located along the line (y = x), which indicates that the proposed relations (27, 28) are highly accurate.

The input and output simulator data are the same as presented in Table 1; therefore, in Table 3 only temperature differences (ΔT 2) obtained from the simulator and from the proposed relation (27), and their differences, as well as the values of effectiveness calculated from the definition and from the proposed relation (28) are presented.

Table 3 Comparison of ΔT 2 and the effectiveness calculated from the definition and from the proposed relations (27) and (28)

On the basis of the data presented in Table 3, a high degree of accuracy of the proposed relations (27) and (28) can be seen.

4 Conclusion

In the present paper, the performance of a double-tube counter-flow heat exchanger under off-design conditions was analysed. Water was used as heat transfer fluids. The hot fluid was flowing inside the smaller tube, while the one heated inside the larger tube.

During operation of the counter-flow heat exchanger, the parameters (temperatures and mass flow rates) at its inlet change, which leads to a change in its performance. Heat transfer effectiveness is most often used to describe the heat exchanger performance under off-design conditions. In this paper, an attempt was made to obtain a new relation for the heat transfer effectiveness of the counter-flow heat exchanger as a function of the parameters at its inlet (temperatures of both fluids at the inlet of the heat exchanger and the mass flow rates).

To this end, the counter-flow heat exchanger was considered as a ‘black box’, and the effect of the inlet parameters [the inlet temperature (T h1; T c1) and the mass flow rates (\(\dot{m}_{h} ,{\kern 1pt} {\kern 1pt} \dot{m}_{c}\))] on the heat transfer effectiveness was investigated.

The data obtained from the counter-flow heat exchanger simulator proved that the changes in inlet temperatures (T h1, T c1) cause linear changes in outlet temperatures (Figs. 4, 5) for constant mass flow rates. For constant inlet temperatures, the changes in mass flow rates have a non-linear effect on the outlet temperature changes (Figs. 6, 7). The nature of these changes was approximated by power functions.

Following this analysis, some conclusions were drawn, and a relation for the heat transfer effectiveness as a function of the inlet parameters was obtained. Unfortunately the proposed relation (18 or 5) contains five constant coefficients which need to be determined based on the real or simulator data. The values of these coefficients vary according to the type of counter-flow heat exchanger; they depend on the heat exchanger geometry (inner and outer diameter, length of the heat exchanger) and the properties of heat transfer fluids.

The advantage of the proposed relation (18) is that it is a function of only inlet parameters (two temperatures and mass flow rates). Its disadvantage, however, is quite a large number of constant coefficients that need to be specified for the given type of counter-flow heat exchanger. This equation can be used for both equal and different mass flow rates (fluid heat capacities).

Due to a large number of constant coefficients in the relation, a new approach was chosen, namely to investigate a parameter defined as the ratio of the minimum to the actual arithmetic mean temperature difference. The analysis shown that the parameter (α) defined in this way is a function of two variables: the ratio of heat capacity rates C, and NTU; it contains no constant coefficients. In order to determine NTU, the overall heat transfer coefficient U needs to be determined. This equation can only be used for different mass flow rates (fluid heat capacities), since for equal mass flow rates (fluid heat capacities) the relation takes the indefinite value 0/0.

The proposed relations (5, 18, 27 and 28) were verified against the data produced by a simulator of a double-tube counter-flow heat exchanger. All the proposed equations revealed to be highly accurate (Figs. 10, 11, 12). The difference between the outlet temperature as obtained from the simulator and from the proposed relations (18) and (27) is in the range of ±0.5 °C.

Taking into account the measurement errors of the measured values (temperatures and mass flow rates), it is expected that the accuracy of the proposed equations will be less and in the range of ±2 °C, because temperature measurement is usually implemented with an accuracy of ±1.0 °C. Considering the measurement errors of the temperatures and mass flow rates, the accuracy of the proposed equations should be expected to be in a similar range as in [6].