Abstract
In order to investigate the eddy current loss of metallic building wall which is penetrated by AC busbar, the 3D finite element model has been created, the eddy current loss in a building wall have been analyzed for different operational condition. Through the comparison between the different simulation results, the most important influencing factors on eddy current loss of building wall are analyzed. The simulation results show that the eddy current loss is directly proportional to bulk conductivity and relative permeability, phase sequence of AC busbar and air gap of building wall have little effects on eddy current loss of building wall. Finally, required shielding of AC busbar, which satisfy the design requirement, is proposed.
Similar content being viewed by others
References
I. Song, J. Thomsen, J. Tao et al., Fault analysis of ITER coil Power supply system. Power Syst. Remote Sens. 32, 153 (2009)
P. Libeyre, B. Bareyt, I. Benfatto et al., Electrical design requirements on the ITER coils. IEEE Trans. Appl. Supercond. 18, 479 (2008)
P. Fu, G. Gao, ZhQ Song, L.W. Xu, L.S. Huang, L. Jiang, J.C. Li, F.W. Zha, L. Dong, M. Wang, Preliminary design of the poloidal field AC/DC converter system for the ITER coil power supply. Fusion Sci. Technol. 64, 4 (2013)
ANSYS software document, version14 (2012)
A.M. Niknejad, R.G. Meyer, Analysis of eddy-current losses over conductive substrates with applications to monolithic inductors and transformers. IEEE Trans. Microw. Theor. Tech. 49, 166 (2001)
P. Reynaud, Building integration, ITER document, France (ITER_D_6LDTHP) (2012)
J. Barranger, Hysteresis and eddy current losses of a transformer lamination viewed as an application of the Poynting theorem. NASA technical Note, USA (1965)
W. Lijian, H. Jinyi, Y. Ruitang et al., Theorem and Design of Huge Current Busbar (Water Resources and electric power press, Beijing, 1983). in Chinese