Abstract
A portable nuclear magnetic resonance (NMR) sensor with an adjustable ‘clamp’ structure is constructed for the noninvasive measurement of the aging status of silicone rubber insulators used in the high-voltage power transmission. The Carr–Purcell–Meiboom–Gill sequence was employed to record the 1H NMR transverse relaxation curves of silicone rubber insulators with different service times. The decay curves were fitted to mono-exponential and bi-exponential functions. Further data processing of the decay curves was performed with the inverse Laplace transformation for one-dimensional T 2 distribution analysis, focusing on the mean lifetime of the long T 2 component (T 2long mean). The results demonstrate that an increase in the aging level of the insulator clearly results in a decrease of T 2long mean. For comparison, the relative permittivity of the insulator was also measured. It shows the same trend as that of T 2long mean. This indicates that the T 2long mean relaxation time obtained from our portable NMR sensor can reliably be used as an index to reflect the aging status of silicone rubber insulator.
Similar content being viewed by others
References
J.S.T. Looms, Insulators for High Voltages (Peter Peregrinus, London, 1988), pp. 3–15
R. Hackam, IEEE Trans. Dielectr. Electr. Insul. 6(5), 557–585 (1999)
S.M. Rowland, J. Robertson, Y. Xiong, R.J. Day, IEEE Trans. Dielectr. Electr. Insul. 17(2), 375–383 (2010)
Kim Jeong-Ho, Song Woo-Chang, LeeJae-Hyung, Park Yong-Kwan, Cho Han-Goo, Yoo Yeong-Sik, Yang Kea-Joon, IEEE Trans. Dielectr. Electr. Insul. 8(6), 1108–1115 (2001)
A.R. Chughtai, D.M. Smith, L.S. Kumosa, M. Kumosa, IEEE Trans. Dielectr. Electr. Insul. 11(4), 585–596 (2004)
STRl Guide 92/1, Hydrophobicity Classification Guide, 274 K. Kremer, RFP 1, 34–37 (2006)
M. Amin, M. Akbar, M. Salman, Sci. China Ser. E: Technol. Sci. 50(6), 697–713 (2007)
Song Wei, Zhao Linjie, Li Chengrong, Huang Xinquan, Yao Jishan, Zhang Shuqi, Cheng Xiujuan, High Voltage Technology 31(5), 28–30 (2005)
J.P. Reynders, I.R. Jandrell, S.M. Reynders, IEEE Trans. Dielectr. Electr. Insul. 6(5), 620–631 (1999)
A.E. Somers, T.J. Bastow, M.I. Burgar, M. Forsyth, A.J. Hill, Polym. Degrad. Stab. 70, 31–37 (2000)
B. Blümich, A. Buda, K. Kremer, RFP. 1, 34–37 (2006)
B. Blümich, F. Casanova, J. Perlo, S. Anferova, V. Anferov, K. Kremer, N. Goga, K. Kupferschlager, M. Adams, Magn. Reson. Imaging. 23, 197–201 (2005)
B. Blümich, J. Perlo, F. Casanova, Mobile single-sided NMR. Prog. Nucl. Magn. Reson. Spectrosc. 52, 197–269 (2008)
A. Guthausen, G. Zimmer, P. Blümler, B. Blümich, J. Magn. Reson. 130, 1–7 (1998)
J.L. Herberg, S.C. Chinn, A.M. Sawvel, E. Gjersing, R.S. Maxwell, Polym. Degrad. Stab. 91, 1701–1710 (2006)
C. Sarah, Chinn, A. Cook-Tendulkar, R. Maxwell, H. Wheeler, M. Wilson, Z. Harry Xie, Polym. Test. 26, 1015–1024 (2007)
N.O. Goga, D.E. Demco, J. Kolz, R. Ferencz, A. Haber, F. Casanova, B. Blümich, J. Magn. Reson. 192, 1–7 (2008)
V. Herrmann, K. Unseld, H.-B. Fuchs, B. Blümich, Colloid Polym. Sci. 280, 758–764 (2002)
S. Anferova, V. Anferov, M. Adams, R. Fechete, G. Schroeder, B. Blümich, Appl. Magn. Reson. 27, 361–370 (2004)
R.I. Chelcea, R. Fechete, E. Culea, D.E. Demco, B. Blümich, J. Magn. Reson. 196, 178–190 (2009)
S.W. Provencher, Comput. Phys. Commun. 27, 213–227 (1982)
Agilent, 16541B Dielectric Test Fixture Operation and Service Manual. Agilent Part No. 16451-90020
P.C. Hansen, SIAM Rev. 34, 561–580 (1992)
S.H. Kim, E.A. Cherney, R. Hackam, K.G. Rutherford, IEEE Trans. Dielectr. Electr. Insul. 1(1), 106–123 (1994)
F. Casanova, J. Perlo, B. Blümich, Single-Sided NMR (Springer, Berlin, 2011), pp. 203–209
B. Blumich, V. Anferov, S. Anferova, M. Klein, R. Fechete, M. Adams, F. Casanova, Concepts Magn. Reson. 15, 255–261 (2002)
M.D. Hurlimann, D.D. Griffin, J. Magn. Reson. 143, 120–135 (2000)
J. Perlo, F. Casanova, B. Blümich, J. Magn. Reson. 176, 64–70 (2005)
F. Casanova, J. Perlo, B. Blümich, Single-Sided NMR (Springer, Berlin, 2011), pp. 66–67
Acknowledgments
This work was financially supported by the National Natural Science Foundation of China (No. 51107150 and 51377182). We thank Dr. Bryce MacMillan for his help in paper writing. Xu Zheng thanks Mr. Gan Qiang of Jiangsu electric power company for supplying the insulators.
Author information
Authors and Affiliations
Corresponding author
Rights and permissions
About this article
Cite this article
Xu, Z., Zhao, S. & Guo, P. A Portable NMR Sensor Used for Assessing the Aging Status of Silicone Rubber Insulator. Appl Magn Reson 44, 1405–1417 (2013). https://doi.org/10.1007/s00723-013-0489-z
Received:
Revised:
Published:
Issue Date:
DOI: https://doi.org/10.1007/s00723-013-0489-z