Abstract
We present measurements of the electrical properties of soil using a complex designed for testing of lightning protection systems and for measuring the conductivity of soil, including ground electrodes, at currents close to the lightning discharge current. The working resistance of soil is in the range from 10 to 100 Ω at a discharge current of 50 kA and a pulse energy of approximately 4 MJ. The results of experiments in an open field area at the voltage on a circuit of 2 MV are presented. Based on the data obtained, we plot the time profile of the soil resistance upon passing a current pulse of the amplitude of tens of kiloamperes through the soil. A dynamic change in soil resistance with time, a “degradation” of soil resistance, and the formation of a spark channel along the soil surface are reported.
Similar content being viewed by others
References
Bazelyan, E.M. and Raizer, Yu.P., Fizika molnii i molniezashchity (The Physics of Lightning and Lightning Protection), Moscow: Fizmatlit, 2001.
Mesyats, G.A., Impul’snaya energetika i elektronika (Pulsed Power and Electronics), Moscow: Nauka, 2004.
Petropoulos, G.M., Proc. Inst. Electr. Eng., 1948, vol. 95, no. 2, p. 59.
Mousa, A.M., IEEE Trans. Power Delivery, 1994, vol. 9, no. 3, p. 1669.
Bellaschi, P.L., Armington, R.E., and Snowden, A.E., Trans. Am. Inst. Electr. Eng., 1942, vol. 61, p. 349.
Liew, A. C. and Darveniza, M., Proc. IEEE, 1974, vol. 121, no. 2, p. 123.
Ground Electrode Characteristics from Model Tests, Trans. Am. Inst. Electr. Eng., 1953, vol. 72, p. 1301.
Chisholm, W.A. and Janischewskyj, W., IEEE Trans. Power Delivery, 1989, vol. 4, no. 2, p. 1329.
Geri, A., IEEE Trans. Power Delivery, 1999, vol. 14, no. 3, p. 1008.
Korsuncev, A.V., Application on the theory of similarity to calculation of impulse characteristics of concentrated electrodes, Elektrichestvo, 1958, no. 5, p. 31.
Oettle, E.E., IEEE Trans. Power Delivery, 1988, vol. 3, p. 2020.
Kalyuzhnyi, V.E., Vliyanie vol’tsekundnoi kharakteristiki razryadnikov na parametry generatory impul’snykh napryazhenii (Effect of Time-Voltage Characteristic of Fuses on the Pulse Voltage Generators), Sbornik trudov: Radiatsionnaya apparatura (Collection of Works: Radiation Equipment), Moscow: Energoatomizdat, 1987.
Rahaman, H., Heo, H., Park, S.S., and Nam, S.H., Abstract of Papers, 3rd Euro-Asian Pulsed Power Conf. and 18th Int. Conf. on High Power Particle Beams 2010 (EAPPC/BEAMS 2010), Jeju, Korea, 2010, p. 241.
Author information
Authors and Affiliations
Corresponding author
Additional information
Original Russian Text © V.E. Fortov, V.P. Smirnov, E.E. Son, Yu.A. Bykov, E.V. Grabovskii, A.N. Gribov, G.M. Oleinik, A.S. Savel’ev, 2015, published in Teplofizika Vysokikh Temperatur, 2015, Vol. 53, No. 6, pp. 819–823.
Rights and permissions
About this article
Cite this article
Fortov, V.E., Smirnov, V.P., Son, E.E. et al. Experimental modeling of lightning discharge into soil. High Temp 53, 775–778 (2015). https://doi.org/10.1134/S0018151X15060061
Received:
Published:
Issue Date:
DOI: https://doi.org/10.1134/S0018151X15060061