Introduction

In recent days, power systems are growing in size and complexity. Due to technological advancement and the modern lifestyle of society highly increase the consumption of electrical energy. The rapid rise in global energy consumption increases the continuous use of fossil fuels as well as greenhouse gas emissions, which have a significant impact on the power grid. This is a concerning situation in terms of supplying sustainable energy and environmental preservation worldwide. According to this, the Agenda 2030 for Sustainable Development, signed by 193 countries, incorporates worldwide efforts toward 17 goals, with a primary focus on the advancement of renewable energy and the reduction of global warming [1]. As a result, the deployment and integration of renewable energy sources (RESs) into the existing power system have increased [2, 3]. Wind and solar power are familiar sources of clean, renewable energy but are inherently unstable, intermittent, and unpredictable [4, 5]. Power electronics play a crucial role in renewable energy systems like wind, solar PV, hydro, and fuel cell systems. Power electronics are used for power conditioning and control, and converter topologies like modular multilevel-cascaded converters have been adopted for interfacing renewable energy systems to the grid. Thus, the integration of renewable energy into the power grid has been made much easier by the advancement of power electronics [6,7,8].

However, traditional power grids are restricted to some of those essential functions, such as electricity generation, distribution, and control. It is also unreliable, has significant transmission losses, poor power quality like brownouts and blackouts, provides inadequate power supply, and prevents using distributed energy sources. Also, the existing power infrastructure lacks real-time monitoring and control, presenting an opportunity to rebuild it as a smart grid [9,10,11]. The following changes have occurred in recent years as a smart grid: generation resources have been added to the distribution end, one-way power flow has been converted to bidirectional flow, the nature of the load has changed, renewable energy has already met grid power demand in most parts of the world, and electric vehicles can be used as a virtual power plant. Figure 1 shows the various components of a smart grid [12]. Smart grids are built using power-electronic converters, allowing the smooth integration of several energy sources into a power system, including solar PV, wind turbines, batteries, electric vehicles, and diesel engines. A smart grid satisfies the need for electricity and protects the environment by digitising the power infrastructure [13,14,15,16,17,18].

Fig. 1
figure 1

Components of Smart Grid

In contrast, recent advances in power electronics have resulted in several power quality challenges in power systems. Furthermore, the proportion of nonlinear loads in modern power systems is increasing, which also causes power quality issues. As a result, the worst quality of power affects the entire power system network. Furthermore, implementing new technologies of power electronics converters with increased switching frequencies causes a challenge like voltage sag, swell, transients, and waveform distortion, as shown in Fig. 2 [19,20,21].

Fig. 2
figure 2

Various types of Power Quality issues

Novel power system technology and the variety of power electronic devices used by residential, commercial, and industrial users have added to grid concerns by causing waveform distortion. Many waveform distortions occur in the frequency ranging from 0 to 2 kHz [22] Most switching devices and equipment raise harmonic levels in today’s electrical distribution system.

The widespread expansion of wind and solar energy sources and the addition of EV charging to the grid boosts the harmonic level, affecting the smart grid’s operation. Therefore, it is essential to analyse power pollution in today’s electrical power network [23]. In addition to the conventional power quality issues, a new term known as supraharmonics also exists in the modern power system. The frequency range between 2 and 150 kHz is referred to as supraharmonics and is shown in Fig. 3A. McAechern proposed the concept of supraharmonics at IEEE P&E S GM 2013 in Vancouver, which was considered a new significant issue in the reliability of smart grid systems [24, 25]. Supraharmonics are likely to occur at any random frequency [26].

Fig. 3
figure 3

Supraharmonic frequency range

Supraharmonic interference is a serious concern to electrical equipment since it can shorten the lifespan of the equipment. Supraharmonics occupy the same bandwidth as power line communication protocols, which can lead to overheating of the compensation capacitors and transformers, as well as the malfunctioning of the protective devices. In addition, it creates a critical impact on the infrastructure for smart metering, communication, and control. Recent research has shown that supraharmonic emission causes significant inaccuracies in smart energy meters. This causes sensitive loads to be affected, which also has an effect on neighbouring circuits and interacts with the grid [27, 28]. Supraharmonics propagate into the medium-voltage network and generate more resonant frequencies within the supraharmonic range [29]. The effects of supraharmonic emission [30] are illustrated in Fig. 4. As a result, investigating and analysing the solution to this problem is necessary.

Fig. 4
figure 4

Effects of Supraharmonics

Based on the data obtained from Scopus using the keywords "supraharmonic" and "supraharmonics" Fig. 5(a) clearly indicates the type of publications over the years 2014 to 2023 and also it shows the increasing importance of studying supraharmonics in recent times. Similarly, Fig. 5(b) depicts details regarding countries actively participating in this field and the number of research papers they have contributed. Therefore, this study provides a comprehensive overview of the current issues concerning supraharmonics in power networks.

Fig. 5
figure 5

a No. of publications and types from 2014 to 2023; b No.of publication vs. countries

This paper gives an overview of the supraharmonic issues in power networks. It is structured into the following sections: Section "Sources of Supraharmonics in Smart Grid" focuses on analysing the sources of supraharmonic emissions in modern smart grids. The details of the measurement techniques and power quality standards are discussed in Section "Measurement and Power Quality Standards", which covers requirements for higher frequency ranges, standards for low-order harmonic distortions, and the problem of specifications for the supraharmonic range of frequency. Finally, "Conclusion" Section gives the conclusions of this study and further research.

Nomenclature

I:

Total emission

J1:

Primary emission

ZD:

Device impedance

Z1:

Grid impedance

V2:

Secondary emission

Sources of Supraharmonics in Smart Grid

The unfamiliar supraharmonics was introduced recently at the IEEE P&E Society General Meeting 2013. The term “supra” refers to beyond, i.e., high-frequency harmonics, high-frequency distortion, or low-frequency EMC [26]. Compared to harmonics and interharmonics, supraharmonics shows different behaviour. Bollen and Ronnberg [23] stated that changes in the generation of electrical energy from other sources and consumption of electrical power by modern loads cause supraharmonics in the network. EPRI started research on supraharmonics emission and the resistance of end-of-use equipment in 2017. Hence, researchers have a large pole of attraction to study the behaviour of supraharmonics in the most recent period [31, 32]. According to the latest research, combining renewable energy with the existing grid and increased use of power electronic converters produces supraharmonics in the power system. Supraharmonics may create electronic device failure, especially in touch technologies, noise generated by mechanical resonance excitation, or increased thermal burden [33]. The biggest issue of high-frequency components in power systems is expanding thermal stress, which shortens electrical equipment’s lifespan [32].

Subhani et al. [34] classify the supraharmonics range into three categories depending on the interruptions in the frequency range.

  1. 1.

    Power line communication is primarily responsible for narrowband signals;

  2. 2.

    Disturbance in the frequency range of broadband signals is due to consumer equipment.

  3. 3.

    Recurrent oscillations in power electronic converters around current zero crossing.

Math H. J. Bollen et al. [35] classify supraharmonic emissions into two types: primary and secondary. Figure 6 illustrates the primary and secondary emissions of supraharmonics, where I is the total emission, J1 is the primary emission, ZD is the device impedance, Z1 is the grid impedance, and V2 is the secondary emission.

Fig. 6
figure 6

Primary and Secondary emissions of supraharmonics

Harmonic distortion caused by the source, i.e., within the device or authority, is referred to as primary emission. However, secondary emission is also a harmonics distortion caused by external devices or sources. The generation of supraharmonics is mainly due to secondary emissions. Some examples of sources of supraharmonic emissions are shown in Fig. 7.

Fig. 7
figure 7

Sources of Supraharmonics

Based on the literature survey [15,16,17,18,19,20,21,22,23], the frequency ranges of SH emission from various sources have been presented in Table 1. According to the early investigations; the frequency ranges from 2 to 9 kHz are considered supraharmonics. Later it can be upgraded to 150 kHz. PC and PLC are the two primary supraharmonic emission sources, irrespective of all other sources [36].

Table 1 Frequency ranges of supraharmonics emitted by different sources

Power line communication is an intentional source of supraharmonics. The operation of power line communication with various types of end-user equipment may reduce device performance [37]. Power line communication (PLC) is a preferred communication method for smart grids and also provides reliable communication for Internet-of-things (IoT) [38]. PLC has been classified into ultra-narrowband, narrowband, and broadband PLC. The smart grid requires a frequency range of less than 500 kHz at rates of up to 100 kbps [39]. The narrowband operates at frequencies lower than the required range, making it suitable for applications such as automated metering infrastructure (AMI), power devices sensing/controlling and monitoring, recognition of system malfunction, and control systems for electric vehicles recharging in smart grids. Medium and low-voltage power grid systems, cost-effectiveness, and vast network coverage are achieved [40]. Different frequencies are used for narrowband power line communication in Europe, Japan, and the United States. Table 2 summarises the frequency operating range of PLC [41,42,43,44].

Table 2 PLC operating range of frequency

J. Meyer et al. [45] stated that supraharmonics is produced by grid-connected harmonic sources and smart-meter signals, thus affecting both the consumer and generation sides of equipment. Math Bollen et al. discussed that the functioning of the customer equipment might be negatively impacted in many ways by the voltage distortion created by PLC. For example, modulation of the high-frequency signal on the fundamental frequency causes multiple zero voltage crossings, which leads to equipment failure [37].

Non-intentional disruptions in a frequency ranging from 2–150 kHz are introduced by some of the loads linked to the network in which PLC has been employed [46]. Some of the system components of electric vehicles, onboard battery chargers, laptop chargers, and electronic converters in photovoltaic (PV) and wind energy conversion systems operating in the supraharmonic frequency range are unintentional emitters [30].

The increased penetration of solar energy conversion systems in the modern grid has its issues. Solar PV systems comprise several power stage topologies with transformer or transformer-less choices. DC-DC converters are vital in solar PV energy conversion systems [47, 48]. In solar PV systems, the DC-DC converters act as switching mode regulators and convert uncontrolled DC voltage to a required DC voltage rating. The converters used in solar applications are a buck, boost, buck-boost, Cuk, sepic converter, and isolated DC-DC converter [49,50,51,52,53,54,55,56,57,58,59]. The choice of the DC-DC converter is determined by whether the PV arrays are connected in series or parallel [60]. The operation of DC-DC converters at high switching frequencies of 20 to 500 kHz will result in supraharmonics in the system [61]. Figure 8 shows the emission of supraharmonics from a grid-connected Solar energy conversion system.

Fig. 8
figure 8

Supraharmonics from Solar Energy Conversion System

A grid-connected solar PV system needs an inverter to convert the output of the DC-DC converter into AC, which will also inject supraharmonics into the system [62]. Voltage source inverters, current source inverters, and Z- source inverters are the different types of inverters used in solar energy conversion systems [63, 64]. The supraharmonic emission from the PV inverter is proportional to its output voltage and depends on its operating conditions [65]. PWM technology is commonly employed in single-phase and three-phase inverters, and it exhibits a supraharmonic frequency in the range of 1–20 kHz in PV systems [30].

Gianfranco Chicco et al. [66] employed an inverter with PWM controllers for a solar energy conversion system and analysed it for supraharmonic emission at PCC. From the analysis, the authors concluded that the inverter is the source of supraharmonic, and also supraharmonic emissions vary depending on the inverter configuration. The single-phase linked photovoltaic (PV) inverters with an installed power rating of less than 4.6 kW act as the source of primary supraharmonic emissions at frequencies between 15 and 20 kHz as per the book titled “Power quality aspects of solar power” published by the working group of CIGRE/CIRED JWG C4.29, 2016 [67]. Jalil Yaghoobi et al. [68] examined supraharmonic emission in two sites with varying loads and 3 MW solar energy conversion systems by keeping inverter switching frequencies below 3 kHz. Finally, they discovered that levels of voltage harmonics were seen at frequencies close to or multiples of the switching frequency of the PV inverters in the range of 0-9 kHz.

Dilini Darmawardana et al. [69] examined three distinct PV energy conversion system topologies and found that the low-frequency single-phase inverter generates supraharmonics up to 8 kHz, the high-frequency inverter emits high frequency at a moderate level or 16 kHz, and the transformer-less inverter emits supraharmonics in the range of 20 kHz. Further, the authors observed that voltage harmonics had been developed near the switching frequency of the PV inverter. Anantaram Varatharajan et al. [70] carried out an extensive investigation of the supraharmonic emission from several three-phase converters with a power rating of 100kVA and single-phase inverters with a rated power of 1- 10kVA after a widespread investigation; the authors concluded that the supraharmonics emission by the inverters is close to its switching frequency.

Gaurav Singh et al. examined the supraharmonic emission from a solar PV plant with a 17 MVA capacity [71]. According to their analyses, the SH emission interacts with traditional telephone service and generates noise in the range of the switching frequency of the solar inverter. Finally, they found that the neutral line of the inverter carried the supraharmonic range of frequency and transmitted it into the telephone line and power distribution system.

Electric vehicle use in transportation infrastructure has a reduced environmental effect, and as EV technology progresses, a considerable quantity of highway charging stations are installed [72]. At a charging station, an electric vehicle receives electricity from both AC and DC sources, thus the charging station is an essential component of the EV charging infrastructure. EV chargers are categorised into several varieties based on source type, station integration, and power level. Wireless and wired chargers are the two main classifications of electric vehicle chargers. In addition, the EV chargers are classified into on-board and off-board chargers based on the charger configuration. While off-board chargers are placed outside the vehicle, on-board chargers are placed inside the vehicle. According to the amount of power the EV chargers deliver, they are divided into four categories: Level 1, Level 2, Level 3, and Level 4. Level 1 is often referred to as normal charging, Level 2 as semi-fast charging, Level 3 as fast charging, and Level 4 as ultra-fast charging. Off-board chargers are usually classified as level 3 of the commercial charging station [73,74,75,76]. Shimi Sudha Letha et al. [77] described three types of charging infrastructure: residential, public, and fast charging, as shown in Fig. 9. Charging modes are subdivided into 2 cases such as unidirectional and Bidirectional. In unidirectional charging mode, the vehicle gets power from the grid alone. In bidirectional charging mode, the power flows in both directions, from vehicle to grid and grid to vehicle [78,79,80,81,82,83].

Fig. 9
figure 9

Types of EV Charging Infrastructure

Using DC level 2 chargers, Gaurav Singh et al. [78] examined the impact of supraharmonic emissions at a charging station on three electric vehicles. In level 2 chargers, a diode rectifier and an active rectifier with a switching frequency of 10 kHz are used to link the charging station at the point of common coupling. The authors found that EV chargers produce supraharmonic emissions in the narrowband and broadband frequency ranges. They concluded that the diode-end converters emit supraharmonics in the 1 to 3 kHz range, and PWM front-end DC chargers emit supraharmonics in the range of 20 kHz. Friedemann Moller et al. [84] tested 8 onboard charging batteries of two electric vehicle models with and without solar energy conversion systems on three-phase and single-phase supplies. The authors found from the test that the distinguishable supraharmonic voltage and current occurred at 10 kHz, 17 kHz, and 20 kHz.

S.Schottke et al. [85] proposed that EV chargers become a source of supraharmonics in the range of 3 kHz to 29 kHz. The author tested type-1 and type-2 chargers of six electric vehicles in the laboratory and found that the supraharmonic emissions occurred due to the switching frequency of the charger. In addition, the emission depends on the charging topology and the charging state. Dilini Darmawardana et al. [86] have proposed an analysis of supraharmonic emission due to DC fast charging and Level 1 onboard charging. Finally, the authors concluded that both types of chargers emit supraharmonic frequency, and it depends upon the characteristics of the charger as well as the charging characteristics of the vehicle.

Fuqiang Chen et al. [87] examined ten chargers with different maximum charging powers in five locations across two countries. The authors found the supraharmonic emissions from the EV chargers and identified that the range of supraharmonic frequency depends upon the switching frequency and type of the EV chargers. S. Cassano et al. [88] proposed an EV charging station model to measure supraharmonic emission in a low-voltage network. From the investigation, the authors reported that the number of devices connected to the grid and the length of the line impact primary emission less. Further to their investigation, grid resistance reduces primary emission while increasing secondary emission. Finally, the authors stated that the maximum supraharmonic emission occurred at 15100 Hz, and concluded there is still a lack of knowledge about the emergence and spread of supraharmonics.

Tim Slangen et al. [79] have tested the propagation of supraharmonic currents in a low-voltage system. The researchers independently evaluated four kinds of electric vehicles linked to the public grid and microgrid. They discovered that EVs generate and absorb the supraharmonics in the range of their switching frequency. The authors concluded that DC fast chargers would be sources of supraharmonic emissions at a high-power level. The supraharmonic currents may be transferred from an LV grid to a medium-voltage (MV) grid via a distribution transformer. Tim Slangen et al. [89] tested fast-charging electric buses at a bus depot and identified that supraharmonics emitted by the EV chargers. The authors stated that converters in EV chargers are the primary source of harmonic and supraharmonics emissions. Further, they specified that there is no specific standard to limit the values of supraharmonic emissions in the EV chargers. Tim Slangen et al. [90] have analysed the supraharmonic from field measurement data of electric vehicle chargers with a rating of 350 kW connected in a different ratio. According to the author’s result, the system’s total supraharmonic current output increases when more chargers are turned on. At the same time, the researchers identified that the emission is not constant over time.

Manav Giri et al. [91] have demonstrated supraharmonics emission from EV rapid chargers with different charging modes at varying charging fields. The researchers concluded that EV chargers cause disruptions in both low-voltage and medium-voltage networks. Finally, they observed various emissions patterns in the power network and concluded that more detailed research is needed to understand the spread of EV emissions. Tim Streubel et al. [92] tested electric vehicles in three different sites and found supraharmonics in a different range of frequencies and interruption of EV charging due to supraharmonics.

Priyanka Mane et al. [93] reviewed the problems with the power quality caused by the solar-powered EV fast charging station. The authors stated in their review that solar and EV fast charging stations are the primary sources of supraharmonics. According to the author, EV emits supraharmonics at frequencies between kHz and 60 kHz in both narrowband and broadband. Also, the SoC of the EV battery influences the emission of supraharmonics from EVs. Bernhard Grasel et al. [94] investigated the impacts of vehicle-to-grid (V2G) chargers connected to the distribution grid. The authors analyzed Austrian electrical low-voltage distribution grids in different scenarios with different topologies. Based on the investigation, they observed that the frequency-dependent grid impedance is influenced by V2G chargers, LCL filters, and DC link capacitors. V2G chargers cause both series and parallel resonance in all conditions, and the number of chargers connected to the grid also affects the frequency range of resonance.

High energy-efficient lighting has recently replaced conventional lighting methods to reduce electrical energy consumption. Nearly 70% of worldwide lighting has been achieved by LED lighting. The use of CFL and LED lights to replace conventional lighting schemes negatively influences the electrical system due to the requirement of drivers [96, 97] is a result of the changeover from an electrical to an electronic load causes harmonic distortion and grid losses in the system [97, 98]. Supraharmonic emissions are observed from the lighting of several types of LED bulbs and high-efficiency fluorescent lighting [23, 99]. Allan Emleh et al. [100] stated that LED lighting produces electrical noise in the DC-DC converter part of the LED driver circuit with a frequency range below 150 kHz and also affects PLC communication. Gaurav Singh et al. [101] highlighted that supraharmonics have been related to the visible flickering of LED lights and produce an audible noise in the range of human audible frequency, i.e., 20 Hz to 20 kHz. Daniel Agudelo-Martinez et al. [102] identified that the buck converter in the LED driver circuit emits a high range of frequencies.

Tatiano Busatto et al. [103] stated that the power circuit’s Active Power Factor Correction (APFC) minimises the lower harmonics. Still, simultaneously, it emits the supraharmonics in the system. Selcuk Sakar et al. [104] mentioned that the supraharmonics from LED causes flickering and affects the sensation of the human eye. According to Marek Wasowski et al. [46] work, the major contributors to PLC transmission disruptions are the CFL light sources (26.54%) and LED light sources (13.46%). Naser Nakhodchi et al. [105] measured supraharmonic emission during lighting installation and found that the emission level increases when the number of lamps increases.

One of the significant sources of renewable energy is the energy acquired from the wind. In recent years, several countries have seen a substantial increase in generation farms tied to sub-transmission and transmission systems. To connect to the grid, wind turbines need power electronic converters [106,107,108,109,110]. Wind power systems and their connections with the grid directly affect the harmonic levels. Therefore, harmonic studies are often a compulsory part of the connection of wind power [111,112,113,114]. Daphne Schwanz et al. [115] stated that wind power plant is the source of primary emission of supraharmonics. A variable-speed wind turbine’s grid interface inverter emits 3.15 kHz.

Ana Maria Blanco et al. [116] investigated the harmonics, inter harmonics, and supraharmonics from wind energy sources and measured the level of harmonics. The supraharmonics in the wind energy conversion system were studied by Javad Behkesh Noshahr [117]. The author proposed that the frequency converter circuit’s switching frequency generates supraharmonics in the 2–3 kHz range. A study on the generation of supraharmonics in power transmission systems caused by wind farms with PMSG technology was presented by Benhur Zolett et al. [118]. The power inverter was shown to be primarily responsible for the emissions from wind farms. The author concluded that the magnitude of supraharmonic voltage is less than that of low-frequency harmonic. Finally, the author stated that there is still no standard limit for this frequency range, so further research is needed to analyse the impact of supraharmonics on PLC.

Jil Sutaria et al. [119] analysed the supraharmonic emission from Data centres. To provide consistent power to the server loads, a data center functions as an essential hub for several converters. An uninterruptible power supply (UPS) regulates the incoming AC power from the utility, providing a backup in the event of a power outage. The UPS output is fed into the server’s input power supply unit (PSU). According to the author, one of the primary sources of supraharmonics in the data center is the UPS. The authors investigated the supraharmonic emission from the UPS and the grid-connected solar energy conversion system in different operating modes. Analysis by the authors indicates that the SH voltage and current depend upon the grid impedance and the solar inverter. Also, in both online and offline operating modes of UPS, it was found that supraharmonics emitted by loads connected to the UPS do not travel to the grid side.

Supraharmonics are also emitted by cell towers and household appliances, including washing machines, compact fluorescent lamps, CRT television, and vacuum cleaner with brush motors [120,121,122]. Thus, the major sources of supraharmonics emissions in a smart grid include power electronic circuits and energy-saving equipment used in domestic applications [23, 24, 26, 27, 30, 31, 33,34,35,36,37,38,39,40,41,42,43, 45,46,47,48, 50,51,52, 54, 56, 57, 60,61,62,63,64,65,66,67,68,69,70, 72,73,74,75,76,77, 80,81,82,83,84,85,86,87,88,89,90,91,92, 95,96,97,98,99,100,101,102,103,104,105,106,107,108,109,110,111,112,113,114,115,116,117,118, 120,121,122]. Table 3 summarises the review of supraharmonic sources identified in the literature.

Table 3 Summary of Supraharmonic Sources

Measurement and Power Quality Standards

Monitoring signals in the 2–150 kHz band has become significant due to emissions on the power grid generated by power converters. Generally, the low-order harmonic content of equipment is measured by connecting the signal analyser and current monitoring device between the source and test equipment [27]. The measuring of harmonics in a system is shown in Fig. 10.

Fig. 10
figure 10

General measurement of low-order Harmonics

The IEEE EMC Society defines low-frequency emission as frequencies less than 150 kHz, but the IEC defines frequencies less than 9 kHz. As a result, there is no normative standard for quantifying supraharmonics. The informative testing and measurement methods for supraharmonic emissions are IEC 61000–4-7, IEC 61000–4-30, IEC 61000–4-19, Digital CISPR 16–1-1, IEEE 519, and CENELEC EN 50065. Time domain measurements are used in IEC standards, whereas frequency domain measurements are used in CISPR 16 standards. Appendix B of IEC 61000–4-7 recommends a measuring technique for equipment with a 2–9 kHz frequency range. This specification relates to CISPR 16–1. This measuring standard suggests a bandpass filter attenuating the fundamental frequency and components over 9 kHz. Figure 11 shows the measurement method of IEC 61000–4-7.

Fig. 11
figure 11

Measurement method as per IEC 6100–4-7

IEC 61000–4-30 suggested the measuring methods for the range of 9-150 kHz of frequency. Annex C of IEC 61,000–4-30 considers the measurement method specified in Annex B of IEC 61,000–4-7 for the frequency range of 9 kHz to 150 kHz. This standard limits the frequency range between 2 and 150 kHz by cascading high-pass and low-pass filters. The measurement method according to the standard is illustrated in Fig. 12. This measurement method is based on a normative standard which is given for below 2 kHz harmonics. It provides the root-mean-square (RMS) values. IEC 61000–4-19 provides the method of testing the equipment under the frequency range of 2-150 kHz and also specifies testing, and verification processes, test setup, and limits, test apparatus, and test waveforms. The CISPR 16–1-1 method specifies the measuring receiver by using different detectors. Quasi-peak detectors and analogue super-heterodyne receivers are suggested in this standard for testing the interference mainly in radio transmission. CISPR 16 is difficult to apply to the Low Voltage grid because it requires a line impedance stabilization network, which is not suited for distortion measurements.

Fig. 12
figure 12

Measurement technique is given by IEC 6100–4-30

CENELEC EN 50065 suggested the standard for electrical equipment using signals in the frequency range of 3 kHz to 1485 kHz to transmit data through PLC. IEEE 519 limits current and voltage harmonics from the customer and utility sides [123,124,125,126,127,128,129,130,131,132]. The summary of measurement range and testing procedure of supraharmonic frequency are given in Table 4 as per IEC and CISPR standards.

Table 4 Measurement and Testing Standards for the supraharmonic frequency

Time–frequency domain, Wavelet approach, Subsampling approach, and Compressive sensing domains are also used to analyse supraharmonics [128] Fig. 13 illustrates the method for measuring supraharmonics from the informative standards.

Fig. 13
figure 13

Steps to measure supraharmonics

Research is ongoing to develop a standard measuring method and techniques for analysing supraharmonic emissions. The researchers have observed that measuring high-frequency harmonics can be challenging. However, several studies investigated the occurrence of supraharmonic emission from numerous sources using different measurement standards, as shown in Table 5 [62, 65, 79, 87,88,89,90,91,92, 126, 133,134,135,136,137,138,139,140,141,142,143,144,145,146, 148,149,150,151,152,153,154,155,156,157,158].

Table 5 Different measurement methods of Supraharmonics

Alexander Gallarreta et al. [159] proposed a new measurement technique to measure the supraharmonic emission in the low voltage distribution grid. The novel method uses the Light Quasi-peak (QP) detection technique, a digital implementation of the CISPR 16 standard. This method reduces the memory requirement and computational process. The light quasi-peak method of measurement is shown in Fig. 14. The same author et al. [160] proposed another new method to measure the supraharmonic emission named as Statistical-QP method shown in Fig. 15. This method obtains an approximate QP value by statistically analyzing the instantaneous RMS values. As compared to CISPR 16, the Statistical-QP requires significantly less computation and memory.

Fig. 14
figure 14

The measurement method according to Light Quasi-peak

Fig. 15
figure 15

Statistical – QP method

These two methods require lower computational complexity and memory than digital CISPR 16 and have been submitted to IEC SC77A WG9 for inclusion in standard IEC 61000–4-30 [161].

IEC 61000–3-8 limits the supraharmonic maximum emission from power line communication is proposed for the frequency range of 3 to 9 kHz. Hence there is essential to suggest a new standard for supraharmonic emission. Additionally, the standards use different measurement intervals to analyse the supraharmonic emission therefore sudden fluctuations of emission are not able to measure properly. As a result, it is difficult to describe and measure the emissions from various types of equipment [27, 122, 127].

Different techniques are handled by the authors for reducing supraharmonic emissions. Antonio Moreno-Munoz et al. [162], mentioned that power electronics converters are a significant cause of waveform distortion, but at the same time, they may reduce the distortion. Appropriate design and implementation techniques can limit the production of supraharmonics. According to the authors, using multi-level converters can decrease supraharmonic emissions. S.K. Ronnberg et al. [163] proposed that innovative switching patterns in active converters can reduce supraharmonic emissions. The same author presented a pulse width modulation scheme based on random pulse position modulation in solar power plants and concluded this method would reduce supraharmonic emission in the system. The random pulse position modulation approach is complex, time-consuming and produces unreliable results [164]. According to the authors, the fuzzy logic controller is the most precise solution and may quickly eliminate the supraharmonic emissions. No specific method exists from the analysis to mitigate supraharmonic emissions; hence, the evolution of more studies in this area is essential. Table 6 summarises the review.

Table 6 Review Summary

Discussion

In general, there is a lot of research being done on the topic of supraharmonics. The CIGRE C4 working group, the Electric Power Research Institute (EPRI) in the United States, and numerous universities are the few already working on this research issue.

  • Most of the research findings are related to sources of supraharmonics and its emission level.

  • Research work in measurement and analyses of Supraharmonic emission is very few compared to source identification of supraharmonics.

  • Some research on measurement methods is limited to identifying primary and secondary emissions.

  • No generalized measurement methods for supraharmonic emission.

  • There is no normative standard for supraharmonic emission.

  • According to the mitigation methods of supraharmonics, only a limited number of publications exist in the literature review.

Based on the literature review the research gap identified in the field of supraharmonics has been shown in Fig. 16.

Fig. 16
figure 16

Research gap in supraharmonic emission

  • Supraharmonic sources will increase in the future. As a result, to handle this issue, a suitable measurement method and complete analysis are required to minimize the problem and mitigate the supraharmonics to regulate energy utilization.

  • Supraharmonics can potentially be mitigated by employing high-frequency materials, which could be an area of future research.

  • The integration of modern signal processing techniques with machine learning approaches to identify and classify supraharmonic emissions is a promising future scope.

Conclusion

Power quality issues in electrical distribution networks have become severe problems with the rise of many nonlinear loads and the integration of renewable energy. Supraharmonic emission is the source of many disruption issues in the modern electrical network. The most significant proposal for the future electricity system is the smart grid. Supraharmonic emission affects the functioning of the smart grid by creating problems in power line communication. This study provides an overview of the sources of supraharmonic emission in power systems from the power quality view and reviews the supraharmonic measurement methods and related standards. Based on the review reveals that the analysis of supraharmonic emission sources, the amount of emissions produced by these sources, and the effects on power system components are the research areas that researchers most frequently discuss.

Other significant topics addressed include forming new detection algorithms for supraharmonics, comparing various measurement techniques, and the effects of supraharmonics. The well-defined standards for measurement and mitigation are applicable for harmonics ranging in frequency below 2 kHz. However, according to this survey, the previous standards do not apply to supraharmonic emissions ranging between 2 and 150 kHz. Also, several issues have been identified in the measuring techniques. Developing suitable frequency analysis tools is one of the objectives of the expanding supraharmonics research. As a result, new frequency estimation techniques are being researched and recommended. Hence, serious consideration for the standard setting of the supraharmonic frequency range is required. The standards for measurements and mitigation techniques for supraharmonic emissions are in the area of research. Based on this study, further work can proceed to identify the supraharmonic source by different processes and mitigation of supraharmonics and its effects.