Introduction

Drinking water sources, particularly surface water, are increasingly subject to contamination risks from various anthropogenic activities including agricultural land use, urban stormwater discharge, wastewater treatment plant outlets and long-distance air pollution. As a result, there is growing concern over the presence of micropollutants in water sources and their potential negative effects on the environment and in drinking water production. Further, the presence of naturally occurring toxicants in raw water, as well as the formation of disinfection by-products (DBPs) during drinking water production, pose potential threats to human health [1,2,3]. Such challenges facing the drinking water sector, thus, call for continued research to not only better understand and predict the removal rates of treatment technologies and support the optimization of water purification strategies, but also to inform more comprehensive water quality frameworks to ultimately safeguard the hygienic quality of drinking water.

Effective water treatment processes are essential to produce safe drinking water under varying source-water quality conditions. Drinking water purification methods commonly utilized at drinking water treatment plants (DWTPs) include different combinations of the following basic physical and chemical processes: coagulation, sedimentation, filtration, and disinfection [chlorination or ultraviolet (UV) irradiation]. These methods, however, do not completely eliminate micropollutants that may remain in the treated drinking water [4] and lead to human exposure to hazardous compounds or mixtures. As such, the choice and combination of treatment methods are important considerations in the design of DWTPs. Chlorination remains a common disinfection method at DWTPs around the world. In the US alone, disinfection using free chlorine continues to be the most widely used disinfectant, as reported by 70% of respondents in a recent survey summarizing common disinfection practices among drinking water utilities [5]. Cost has been reported as the primary factor as to why the utility operators have not considered switching to other disinfection methods such as ozone or UV [5]. Similarly, chlorination is widely used in other countries such as South Africa, Canada, and Australia [6]. However, a major downside of using chlorine is the potential formation of DBPs such as trihalomethanes (THMs) and haloacetic acids (HAAs). Alternative disinfectants such as chloramines, ozone, chlorine dioxide, and UV disinfection are, however, gaining popularity. Ozonation (O3) and activated carbon treatments have been suggested to be more effective treatment methods in managing the removal of organic micropollutants (OMPs) and DBP precursors [7, 8] than other methods such as coagulation, sedimentation, and rapid or slow sand filtration. Certainly, water treatment methods continue to be modernized with the development of advanced treatment alternatives. While each treatment method has its advantages and disadvantages, it is undoubtedly beneficial to pilot-test treatment designs prior to implementation to ensure the designs are appropriately suited for implementation into full-scale capacities or when considering the optimization of existing treatment system processes.

The efficiencies of treatment processes at a DWTP are routinely tracked via drinking water quality monitoring. However, such monitoring is typically only conducted for the limited number of chemical parameters listed in the drinking water regulations, such as metals, pesticides, a few DBPs, and polycyclic aromatic hydrocarbons. Such parameters alone are insufficient in characterizing water quality given that numerous chemicals are likely to be present and potentially at low concentrations. As such, effect-based monitoring using bioanalytical tools (i.e., in vitro bioassays) has been suggested as a promising complement to existing water quality assessments [9,10,11,12,13,14,15,16,17] and can provide valuable information related to treatment efficiencies. Importantly, more studies using bioanalytical tools to assess DWTPs are needed to provide support towards the acceptance and implementation of in vitro bioassays in drinking water quality regulations.

In the current study, a panel of cell-based reporter gene assays assessing effects from multiple toxicity pathways relevant to human health were used to investigate the treatment efficiencies of a pilot-scale drinking water system. Specifically, the study compared the efficacy of pilot-scale GAC filtration as well as the combination of ozonation and GAC filtration vs. full-scale biological activated carbon (BAC) filtration, UV disinfection, and monochloramine dosing at removing/reducing bioactivities. Both treatment systems were fed the same raw water that had undergone primary treatment (coagulation, sedimentation/flotation, sand filtration) in the full-scale. We hypothesized that the ozonation and GAC filtration methods would be more effective at reducing bioactivities. The selected bioassays targeted reactive modes of action such as cytotoxicity and genotoxicity as well as adaptive stress responses and receptor-based effects including oxidative stress, aryl hydrocarbon receptor (AhR) activation, and hormone-mediated modes of action. These particular endpoints, which relate to adaptive stress response, xenobiotic metabolism, and modulation of hormone systems, have been identified as being the most responsive toxicity pathways in the case of drinking water [2, 18, 19]. This study aimed to: (1) provide knowledge on the efficacy of the pilot-scale ozonation and GAC filtration treatments; (2) assess temporal differences in water quality; and (3) report findings regarding bioactivities observed in the raw water and the full-scale treatment process. While the efficacy of the pilot-scale ozone (O3) and GAC had been previously assessed in the context of OMP levels in drinking water production [8], the bioanalytical approach of the current study will provide further useful information regarding the removal efficiencies of the two treatment technologies. This could be of particular relevance as a decision-making tool in the potential implementation of the alternate treatment technologies into full-scale capacities or when considering the optimization of the existing treatment system processes.

Materials and methods

Conventional full-scale and pilot-scale treatment systems

Görvälnverket is one of three DWTPs operating in the Stockholm region of Sweden. This facility draws untreated raw water from Lake Mälaren and services almost 700,000 consumers in several regional municipalities. Lake Mälaren is the third largest freshwater lake in Sweden and also receives effluent from several wastewater treatment plants located upstream of the DWTP [20]. Görvälnverket was built in 1929 and the facility has undergone several upgrades over the years. To meet the increasing demand for drinking water from the growing municipalities, additional upgrades are currently being considered for the DWTP.

Raw water entering Görvälnverket undergoes several conventional treatment processes consisting of: micro-sieving followed by coagulation treatment using aluminum sulfate, flocculation and sedimentation/flotation, rapid sand filtration, biologically activated carbon (BAC) filtration, UV disinfection, and lastly dosing with monochloramine (NH2Cl) for secondary disinfection and lime for alkalinization and pH adjustment (Table 1, Fig. 1). The BAC filters have a running time of approximately 10–15 years and a short empty bed contact time (EBCT) of approximately 4–6 min.

Table 1 Water sample identifications (IDs) and description of treatment and sampling locations at Görvälnverket DWTP
Fig. 1
figure 1

Treatment steps for the full-scale and the two pilot-scale treatment systems investigated at Görvälnverket (simplified diagram). The sampling points for all sampling events are indicated with symbols

A pilot-scale water treatment system consisting of ozonation pre-treatment and GAC columns (Table 1, Fig. 1) was installed at Görvälnverket in May 2018 to evaluate the efficacy of these two methods in removing, e.g., OMP and DOC removal. This pilot-scale system receives incoming water treated with coagulation, sedimentation, and sand filtration from the full-scale treatment system at a flow rate of 610–720 L/h. In this study, two pilot-scale processes were investigated: (1) pilot-scale A wherein the incoming primary-treated water undergoes ozonation then GAC filtration; and (2) pilot-scale B wherein the incoming primary-treated water undergoes GAC filtration without pre-ozonation. For pilot-scale A, feed water was pH-adjusted to 6.5 prior to ozonation (target residual of 1 mg O3/L after 4.2–4.9 min reaction) while the pilot-scale B GAC column received water at ambient coagulation pH (6.5–6.8). The GAC column in pilot-scale B is used to: (a) directly assess differences in GAC efficacy with and without pre-ozonation; and (b) to investigate the gradual saturation of a GAC filter with longer EBCT and compare it to the full-scale short EBCT BAC treatment. The EBCTs for pilot-scale A and B were 20 min.

Sample collection

Water samples were initially collected at the Görvälnverket DWTP in November 2019. Grab samples (approximately 5 L) of water were collected from multiple points in both the full-scale and pilot-scale treatment systems (Table 1, Fig. 1). The water samples were collected in 12-L stainless steel (Sharpsville) containers and transported immediately back to the laboratory where they were stored at − 20 °C until sample preparation. Procedural controls included ultrapure water (Milli-Q®) sourced from the laboratory.

Based on the results from the November 2019 samples, a follow-up sampling event was carried out in May 2020. The May 2020 sampling event targeted only the full-scale treatment system and one sample from the pilot-scale B system (the pilot-scale A system was no longer operational). An additional follow-up sampling event was conducted in September 2020 to determine if the bioactivities observed in the full-scale DWTP were persisting along the distribution network. As such, the September event focused only on the DWTP outlet as well as two consumer tap water sampling points along the distribution network, located approximately 6 km and 50 km from Görvälnverket. All repeat samples were collected from the same locations at Görvälnverket in all sampling events, then prepared and stored in the same manner.

Sample preparation

The extraction of the water samples (5 L) was conducted with an automatic solid-phase extraction system (SPE-DEX 4790, Horizon Technology, Salem, NH, USA) using HLB extraction disks (Atlantic HLB-H Disks, diameter 47 mm; Horizon Technology, Salem, NH, USA). Additional information regarding the sample preparations is provided in the Additional file 1: Section S1.

When incubated with the cells, the concentrated water samples were diluted 100-fold with cell medium to get a final plate concentration of 1% ethanol to obtain a relative enrichment factor (REF) of 50 in the bioassays: 5000 (enrichment factor at SPE) × 0.01 (dilution factor at bioassay). REF > 1 denotes an enriched water sample and REF < 1 denotes a diluted water sample. The enrichment and dilution of the samples constitute the REF, as described by Escher et al. [19].

Bioassays

A summary of the bioassays is provided in Table 2 and more detailed descriptions of the bioanalytical methods and positive controls are provided in the Additional file 1: Section S1. The concentrated water samples along with procedural, vehicle, and positive controls were tested for Nrf2, AhR, ER, and AR agonist and antagonist activities in reporter gene assays. Genotoxicity was assessed using the in vitro mammalian cell micronucleus test (MCN) and analyzed with a MicroFlow Kit (Litron Laboratories, USA). Cytotoxicity was initially tested in all cell lines and defined as a cell viability of 0.8 compared to the vehicle control, set at 1. For the MCN test, cytotoxicity was also assessed following the manufacturer’s kit protocol (fourfold EMA-positive event increase over vehicle control). The main purpose of the cell viability testing was to ensure that the bioanalytical assessment of specific parameters was performed under non-cytotoxic conditions. Each sample was analyzed at the highest non-cytotoxic REF value.

Table 2 Summary of the applied bioanalytical methods

As an initial screening, all water samples were analyzed for bioactivity at REF 50 in all bioassays. Each bioassay was conducted at least two times to prove biological reproducibility. This study presents the results from one of the representative experimental runs for each endpoint. In all assays except the MCN, samples showing bioactivity above the respective cut-off levels at REF 50 were then analyzed again in dilution series from REF 50 to REF 1.56 (dilution factor = 2). As it has been suggested that activation of the Nrf2 pathway can also indirectly result in genotoxic effects [21, 22], the MCN test was performed on samples that displayed Nrf2 activity above the cut-off. In all experimental runs, four technical replicates for each sample were tested. In each reporter gene assay, reference compounds (positive controls) were analyzed in parallel with the water samples. The positive controls were analyzed in 6–12 concentrations to obtain standard curves. The compounds used in each assay are listed in Table 2 and described further in the Additional file 1: Section S1.

Data evaluation

Bioactivities observed in the initial screening at REF 50 were expressed as fold change normalized to the vehicle controls, set to 1 in all assays except the MCN. In the MCN assay, the genotoxicity of the water samples was assessed by comparing the micronuclei formation rates (%) to that in the vehicle control. For Nrf2, where no maximum effect can be reached, the standard curve for the reference compound was based on a linear regression of activities normalized to the mean activity of the vehicle control. For AhR, AR, and ER, the standard curves for the reference compounds were obtained by fitting data to a four-parameter sigmoidal curve fit.

For the dilution series, concentration–effect curves (CECs) were obtained from the dilution series for those samples that showed bioactivity above the respective cut-off levels at REF 50. CECs were fit to a four-parameter sigmoidal curve fit for the reference compounds. For all data sets, the mean activity of the vehicle control was first subtracted from all replicates. All adjusted values were then normalized first to the mean activity of the vehicle control, then to the percent of maximum activity of the reference compound. For AhR and ER, linear regression was performed on the normalized data with y-axis intercept fixed at zero and the estimated slope from the regression was used to determine the concentration causing 10% effect (EC10) expressed as REFs, as proposed by Escher et al. [23]. As there is no clear maximum response for Nrf2 activity, fold inductions were normalized to that of the vehicle control then fitted to a linear regression model. The concentration, expressed as REF, causing a 1.5-fold induction (ECIR1.5) was estimated from the model. The EC values for all samples are provided in the Additional file 1: Table S2. All statistical analyses as well as graphical presentations were performed using GraphPad Prism (version 8.3.0).

For Nrf2 activity, a fold induction of 1.5 compared to the normalized vehicle control was used as the cut-off level for bioactivity, as recommended by Escher et al. [21]. For AhR, AR, and ER, cut-off levels for bioactivity were based on the limit of detection (LOD) for that assay, which was defined as 1 plus 3 times the standard deviation (SD) of the normalized vehicle control [21]. A cut-off level for a positive response was then set for each assay as a value exceeding the LOD value. In instances when the LOD was below 1.5, the cut-off level was set to 1.5, and if the LOD was between 1.5 and 2, the cut-off level was set at 2. For AR antagonist activity, the LOD was calculated as 1 minus 3 times the SD of the normalized vehicle control, and a cut-off level of 0.7 was set. For genotoxicity, statistical significance from the vehicle control was assessed in place of a cut-off level, following the guidance in the OECD’s TG487 acceptability [24]. A summary of the bioassays and concentration ranges of the reference compounds is provided in Table 2.

For the Nrf2, AhR, AR, and ER assays, ECIR1.5 and EC10 values were used to convert the bioactivities measured in the samples into biological equivalent concentrations (BEQs) of the respective positive controls using the following Eq. (1) adapted from Jia et al. [25]:

$${\text{BEQ}}_{{{\text{bio}}}} = \frac{{({\text{EC}}_{10} \;{\text{or}}\;{\text{EC}}_{{{\text{IR}}1.5}} )_{{{\text{positive}}\;{\text{control}}}} }}{{({\text{EC}}_{10} \;{\text{or}}\;{\text{EC}}_{{{\text{IR}}1.5}} )_{{{\text{sample}}}} }}.$$
(1)

To account for differences in sensitivity in the experimental runs between November, May, and September, the BEQ values were calculated to enable comparisons of the data sets between the three sampling events. Based on the BEQ values, the removal efficacies could then be compared to each other.

For the MCN assay, the results in each sampling event were compared to the vehicle control using a one-way ANOVA comparison followed by Dunnett post hoc test. Genotoxicity was defined as a statistically significant increase in the number of micronuclei (% micronuclei events) compared to the vehicle control. P-values less than 0.05 were considered statistically significant. To determine if the results could be compared between the three sampling events, a multiple comparison test of the positive control (Mitomycin C) data was first conducted. No significant differences between the mean % micronuclei events across all three sampling events were detected (Additional file 1: Fig. S7). The statistical analysis and graphical presentations were performed using GraphPad Prism (version 8.3.0).

Results and discussion

Cell viability

All samples were initially tested for cytotoxicity at REF 50 in all assays. In the Nrf2, AhR, ER, and AR assays, none of the water samples exerted cytotoxicity, defined as cell viability below 0.8 compared to vehicle control (Additional file 1: Fig. S1). This demonstrated that the bioassays were conducted under conditions where the cell viability was not compromised. For the MCN assay, no cytotoxicity as defined by the manufacturer’s kit protocol (fourfold EMA-positive event increase over vehicle control) was observed in any of the samples at the highest REF value of 50 (Additional file 1: Fig. S8).

Initial screening of pilot- and full-scale samples

In the samples from November 2019, we observed Nrf2, AhR, and ER activities above cut-off levels at REF 50 and statistically significant genotoxic activities in the incoming raw water (Fig. 2A, D, G; Fig. 3A). Further, the Nrf2, AhR and genotoxic activities increased after the initial coagulation and sand filtration step. In general, the activities were not decreased to below cut-off levels by the coagulation and SF, BAC or UV treatments. The finished drinking water after dosing with monochloramine, on the other hand, was inactive in all four assays. In the pilot-scale systems, both ozonation and GAC filtration considerably reduced the observed bioactivities to below the respective cut-off levels across all assays.

Fig. 2
figure 2

Nrf2, AhR, and ER relative activities (fold change vs. vehicle control) observed at REF 50 for the full-scale process vs. the pilot-scale A and B treatment processes in November 2019 (A, D, G), in May 2020 (B, E, H), and in September 2020 (C, F, I). Treatment groups (n = 4) were normalized to the vehicle control (n = 8) set to 1. The dotted lines represent the respective cut-off levels. Data presented as mean ± standard deviation. For comparison’s sake, the bioactivities for SF have been repeated for all treatment processes in panels A, B, D, E, G, and H

Fig. 3
figure 3

Micronuclei formation rates at REF 50 from the full-scale process vs. the pilot-scale A and B treatment processes in November 2019 (A), in May 2020 (B), and in September 2020 (C). Treatment groups (n = 4) were compared to the vehicle control (n = 8). Data presented as mean ± standard deviation. * represents significant differences from the vehicle control (*p ≤ 0.05, **p ≤ 0.01, ***p ≤ 0.001, ****p ≤ 0.0001). For comparison’s sake, the micronuclei formation rate for SF has been repeated for all treatment processes in panels A and B

In the follow-up sampling in May 2020, the Nrf2 activities at REF 50 in the incoming raw water were lower than in November. Again, none of the treatment steps in the full-scale system reduced the bioactivities, except the reduction of genotoxic activity after monochloramine dosing. The pilot-scale GAC-B system, on the other hand, reduced all the activities to or below the cut-offs (Fig. 2B, E, H; Fig. 3B). The highest reduction following the GAC treatment was a 2.3-fold decrease in AhR activity. This indicates that, even after being in operation for nearly 2 years, adsorption properties in this filter still remain, as the filter performed better when compared to the full-scale BAC. Alternatively, there may be beneficial effects from the longer EBCT in the pilot filter.

In September 2020, an additional sampling event was carried out to specifically study the outgoing drinking water and two tap locations in the distribution network. AhR activity at REF 50 above cut-off (Fig. 2F) and genotoxicity (Fig. 3C) were observed. However, genotoxicity was not detected in the two samples from the distribution network indicating that removal or transformation of micropollutants may have occurred during distribution.

As an additional step in the data interpretation, to compare differences in bioactivities between each of the treatment steps, results were statistically evaluated using a one-way ANOVA comparison followed by Dunnett post hoc test, performed in GraphPad Prism (version 8.3.0). A table summarizing the statistical analysis is provided in the Additional file 1: Table S1. Neither androgenic nor anti-androgenic activities were observed in any sample across all sampling events. The results are presented in the Additional file 1: Fig. S9.

In summary, the removal efficiencies of the treatment steps in the full-scale system varied between the sampling events and most treatments showed little or no effect on the bioactivities detected in the incoming water. Both ozone and GAC in the pilot-scale systems, on the other hand, effectively reduced observed Nrf2, AhR, and ER activities to or below the cut-off levels and to no statistically significant inductions compared to the vehicle control for genotoxic activities. In general, ozonation treatment is likely to continuously provide a decrease in observed activities. GAC filtration, particularly without pre-ozonation, will likely require regular regeneration to maintain its removal capabilities. However, our results indicate that for an EBCT of 20 min, regeneration may not be needed until after more than 2 years of running time. As the ozonation appeared to remove all activities to levels below the cut-off in the pilot-scale A system, it would suggest that regeneration of the subsequent GAC in the combined treatment would not be needed. However, a biofilter step would still be needed downstream of ozonation to obtain biostability.

Bioactive samples, defined as above the respective cut-off levels at REF 50, were also analyzed in dilution-series (Additional file 1: Figs. S3 to S5) in order to determine effect concentrations (ECs) and bioequivalent concentrations (BEQs). These results are discussed in further detail below.

Seasonal differences in bioactivities between sampling events

We observed seasonal differences in the bioactivities in the raw water samples between the November and May sampling events. For Nrf2, the activity was noticeably higher (8.4 times) in November than May based on the BEQ values (Table 3); while the AhR activity was higher in May than November, albeit by only 1.8 times. Further, the genotoxicity was higher in the raw water in May than in November (Fig. 3). These inconsistent bioactivities across the sampling events can be attributed to the fact that temporal variation in the quality and micropollutant profile of source water is expected to occur. Such factors have been discussed in other DWTP studies which also reported seasonal/temporal variations for similar endpoints such as Nrf2 activity [26, 27], AhR and androgenic activities [28], and genotoxicity [29,30,31,32]. For instance, Hebert et al. [26] measured Nrf2 activities in water samples collected from the outlets of three DWTPs in France across several sampling events (November 2015 and March, May, September 2016). The DWTPS used a combination of clarification, sand filtration, ozonation, GAC filtration, and UV. They reported higher Nrf2 activities in May and September compared to November and March for all three DWTPs, likely due to higher levels of some DBPs in September as a result of warmer temperatures. In our study, the highest Nrf2 activity was detected in November. Based on monitoring data provided by Norrvatten, the temperature of the incoming raw water was slightly higher in November 2019 than in May 2020. Hebert et al. [26] also speculated that the increased effect seen in September may be due to the formation of undetected non-volatile or semi-volatile DBPs or due to other existing micropollutants in the source water. Further, treatment processes could increase effects such as genotoxicity in the water and genotoxic dissolved organic matter might be released or formed during purification processes [32]. Other possible influences may be related to interactions with organic matter [33] and the biostability of the water [34], the presence of natural toxins [35] in the raw water, or the formation of transformation products during a treatment process [36]. In our study, it could thus be hypothesized that the compositions of bioactive compounds present in the samples were different between the sampling events, due to temporal variations in the incoming source water, and that these different causative compounds are not equally responsive to the different treatment technologies used.

Table 3 Summary of bioequivalent concentrations (BEQs) based on the ECIR1.5 for Nrf2 and EC10 values for the AhR, and ER assays

Discussion on pilot-scale treatment technologies

This study highlights the efficacy of ozonation and GAC filtration in removing bioactive and genotoxic compounds compared to the full-scale treatments. For instance, the tBHQEQ was decreased from 0.86 µM (November) and 0.04 µM (May) in the primary-treated (SF) water entering the pilot-scale GAC-B system to below the cut-off for Nrf2 activity following GAC filtration alone in both sampling events. Similarly, the E2EQ in the SF-treated water was reduced to below the cut-off for estrogenic activity from 0.07 pM in November and 0.09 pM in May. For AhR activity, the TCDDEQ in the SF-treated water decreased from 0.08 pM (November) and 0.09 pM (May) to below the cut-off following GAC filtration alone. Similarly, Nrf2, AhR, ER bioactivities and micronuclei formations were all lower at REF 50 in the O3 and GAC-A treated samples collected in November compared to the incoming water following the initial coagulation and rapid sand filtration step. It is worthwhile to mention that the performance of the pilot-scale systems at removing OMPs was previously tested in a 1-year pilot-scale study between May 2018 and July 2019, alongside the full-scale system [8]. The lowest levels of OMPs were observed in GAC effluents from ozonated feed water demonstrating the efficacy of combining ozone with GAC for managing OMP levels [8]. Similar to the observation made in this study regarding the efficiency of the pilot-scale ozonation treatment, Jia et al. [25] reported that ozone technology was able to significantly remove Nrf2 activity (AREc32) with BEQ reduction values between 60 and 80%. While BEQ values for the pilot-scale ozonation were not determined in this study, the fact that Nrf2 activities at REF50 decreased to below cut-off following ozonation suggests high BEQ reduction. In another study, Shi et al. [37] reported higher overall treatment efficiencies in removing genotoxic, mutagenic, dioxin-like and estrogenic pollutants at DWTPs that used primary treatment methods coupled with ozone-activated carbon similar to Görvalnverket vs. those DWTPs that did not include ozone-activated carbon.

Other studies based on chemical profiling of the water samples have reported the efficacy of ozonation and GAC filtration in removing micropollutants [7] as well as NOM and precursors of DBPs products [7, 38,39,40,41,42]. As well, the efficacy of GAC filtration (from a DBP perspective) has been reported elsewhere [43] and at other Swedish DWTPs [4, 15]. Also, ozonation alone has been shown to be an effective treatment for antibiotics [31] and estrogenic chemicals [44,45,46]. The estrogenic activities of 17α-ethinylestradiol and bisphenol A, for instance, dramatically decreased following ozonation treatment in a MCF-7 cell proliferation assay [46]. In the ERα CALUX bioassay, the combination of coagulation, sedimentation, sand filtration and chlorination with ozone-activated carbon adsorption was shown to efficiently remove estrogenic potentials from source water better than coagulation, sedimentation, sand filtration and chlorination alone [37]. GAC filtration alone has also been shown to remove more organic compounds, including pharmaceuticals and steroids, than disinfection with sodium hypochlorite or clarification [47].

However, the age of the respective treatment technologies should also be considered when comparing removal performances. In the case of the full-scale BAC vs. the pilot-scale GAC, for instance, it would be worthwhile to compare their effectiveness based on the age range and treated bed volumes of the filter units given that the effectiveness of a filter will likely decrease with time as the filter ages [48]. In an earlier study, Cuthbertson et al. [43] reported that calculated cytotoxicity and genotoxicity were considerably lower following GAC treatment at younger service lives. Further, an increase in GAC run time resulted in an increase of DBPs under simulated distribution system conditions which corresponded to increased calculated cytotoxicity and genotoxicity. The toxicity in their study was determined by the TIC-Tox method. The age and regeneration frequency of a GAC is essential for its function as a chemical barrier. The GAC in the full-scale system has been operating for over 10 years and is currently functioning as a BAC. In comparison, the GAC filters of the pilot-scale systems were installed in May 2018. As such, the dynamics of a GAC filter in its function as either an adsorption filter (GAC) or a biological filter (BAC) can represent two very different removal processes and capabilities. Nevertheless, both ozonation and GAC filtration or GAC filtration alone show great promise as barriers against bioactive compounds in drinking water production [8] and in the overall reduction of DBP formations [43]. Similar observations have been demonstrated elsewhere [15, 49].

Discussion on full-scale treatment technologies

In November, Nrf2, AhR, and genotoxic activities measured in the incoming raw water increased following the initial coagulation and rapid sand filtration steps (Fig. 2; Table 3). The tBHQEQ and TCDDEQ were approximately 2 and 1.3 times higher, respectively, following the conventional coagulation treatment. In the ER assay, the estrogenic activity remained comparable after this initial treatment step. Taken together, the results suggest there was little or no removal effect following this primary treatment step of the full-scale system. Other studies have reported that chemical precipitation processes using coagulants like aluminum sulfate, which is used at Görvälnverket, result in minimal removal of most endocrine-disrupting compounds (EDCs) [45, 50].

Overall, most of the remaining treatments in the full-scale system did not reduce the bioactivities to below cut-off levels across both sampling events, except for BAC in the ER assay and monochloramine dosing in all assays in November. The lack of treatment effects is also reflected in the relatively low BEQ reduction values between these treatment steps, observed for multiple toxicity endpoints. For Nrf2 activity, the highest BEQ reduction value achieved was 20% (SF in May), while the highest BEQ reduction value for AhR activity was 18.2% (SF in May). Rosenmai et al. [16] had previously conducted a bioanalytical study at Görvälnverket and reported findings similar to our observations in May wherein the coagulation treatment, GAC filtration, UV disinfection, and monochloramine dosing of the full-scale system did not decrease Nrf2, AhR, or ER activities. Also consistent with our results of little treatment effect, Lundqvist et al. [17] reported almost similar activities in the inlet (53 ng/L TCDDEQ) and outlet samples (45–52 ng/L TCDDEQ) collected from a DWTP that employed treatments similar to Görvälnverket (e.g., coagulation, sedimentation, rapid then slow sand filtration, UV, NH2Cl dosing) in the AhR reporter gene assay. As well, Macova et al. [51] reported no change in activities in the AhR CAFLUX assay between the inlet and outlet samples from a DWTP that used coagulation, flocculation, sedimentation, filtration, and chlorination.

On the other hand, Escher et al. [21] reported higher Nrf2 activities in AREc32 cells in water samples from the outlet (4.16 × 104 ng/L tBHQEQ) compared to the inlet (1.83 × 104 ng/L tBHQEQ) of a DWTP that utilized treatments similar to at Görvälnverket (e.g., coagulation, flocculation, sedimentation, filtration, chlorination). The authors attributed the increase to the formation of DBPs as a result of chlorination.

As well, in a recent bioanalytical study that investigated multiple DWTPs, Oskarsson et al. [15] reported better treatment effects at two Swedish DWTPs that employed treatment trains similar to that at Görvälnverket (e.g., rapid sand filtration, GAC, UV irradiation, chlorination). At those two DWTPs, AhR activities were reduced from 31 and 34 pM TCDDEQ at the inlets to below cut-off at the outlets.

In available literature investigating genotoxicity of finished drinking water samples, conflicting results have been reported. For instance, some studies investigating the genotoxicity in drinking water samples observed decreases in micronuclei inductions following various conventional water treatment methods similar to those employed at Görvälnverket [37, 52]. Several other studies using different established cell lines reported no significant differences in the frequency of micronucleus events between control samples and samples representing conventional treatment methods (e.g., pre-disinfection with chlorine dioxide, coagulation, sand- and GAC-filtration, post-chlorination), therefore suggesting no treatment effects [29, 53,54,55].

In November, the full-scale BAC filtration and monochloramine secondary disinfection appeared to reduce estrogenic activities, albeit low estrogen activities were detected overall; however, in May there appeared to be little treatment effect. Neale et al. [27] studied two DWTPs that employ similar treatment sequences: (pre-ozonation), clarification, sand filtration, ozonation, GAC, and then UV treatment followed by chlorination. In their study, estrogenic activity was detected in all source water samples as well; however, the treatment processes reduced the activity to below the limit of detection. As discussed above, ozonation has been shown to reduce estrogenic chemicals.

With respect to the September sampling event focused on the finished drinking water and the distribution network, passage through the distribution network appeared to reduce genotoxic activity. Removal of bioactivities in water samples collected from Görvälnverket’s distribution network had previously been reported [16]. It has been suggested that decreasing bioactivities along a distribution network could be due to the binding of bioactive compounds to the pipe surface or the biofilm, or the degradation/inactivation of the compounds by microorganisms present in the biofilm [56]. As such, the removal of genotoxic activity in the distribution network in the present study may be explained by interactions between genotoxic compounds and the biofilm.

Regarding the lack of AR activity observed in the current study, similar results were reported by Rosenmai et al. [16] from Görvälnverket and in other countries wherein the activation or inhibition of AR was not commonly detected [27, 28, 57,58,59,60,61]. Further, AR antagonistic activity was detected in drinking water from other DWTPs in Sweden [15]. Still, AR agonistic activity has also been reported in treated water [62].

Conclusions

In this study, we observed oxidative stress, genotoxicity, AhR, and ER agonist activities in raw water used for drinking water production over the course of repeated sampling events. In general, most of the full-scale treatment methods were unable to fully remove the compounds causing these activities. On the other hand, pilot-scale treatment with either ozonation or GAC filtration was more efficient in removing the compounds causing oxidative stress, genotoxicity, AhR and ER agonist induction. Both treatment methods appeared to perform better than the conventional full-scale treatment methods utilized at this subject DWTP.

The variability in treatment effects in the full-scale system observed in this study, which has also been reported in other studies on similar treatment technologies, suggests that the treatment process as well as the characteristics of the source water are important factors when assessing the toxic potential of treatment-processed drinking water. Another important consideration is the seasonal variation in the quality of the raw water in that the physico-chemical profile of the incoming water (e.g., temperature, organic matter, micropollutant profile) would differ between sampling events which could be linked to different reactivities during the treatment processes.

Using a panel of cell-based bioassays, this study highlighted that ozonation and GAC filtration methods are effective at reducing bioactivities. The study also demonstrated the usefulness of conducting a pilot-scale assessment combined with bioanalytical methods as a valuable approach to test water treatment techniques before full-scale implementation. As such, the conclusions made in this study regarding both the pilot-scale and full-scale drinking water treatment methods provide important insights into the optimization of existing drinking water treatment designs and support the need for further research into the removal of micropollutants in drinking water. The findings of this study thus suggest that micropollutant removal appears to be dependent on the treatment type, season, and quality of the source water.

Further work with this study could include: chemical analyses and an effect-based analysis (EDA) of the water samples to identify the causative compounds of the observed biological effects; composite sampling over a longer time period in a day; and cost–benefit analysis of the pilot-scale systems. The results of this study will hopefully contribute to the growing body of research supporting more efficient implementation of bioanalytical tools into operational practices at DWTPs, water safety planning, and incorporation into more comprehensive regulatory frameworks for water quality monitoring. Lastly, while the focus of this study was on drinking water treatments, it would be remiss to not also mention environmental implications. Given that source waters of DWTPs are often impacted by human activities, it can be hypothesized that the effects observed in this study are likely attributed to environmental pollutants. Implications such as this draw evidence-based attention towards the need to improve the management and protection of our water resources.