Background

Previous influenza studies have examined the association between absolute and relative humidity and influenza activity [13]. Absolute humidity (AH) is the water content of air, measured in millibars (mb), independent of barometric pressure and temperature. Relative humidity (RH) is the ratio (expressed as a percent) of the measured water content of air relative to the maximum possible water content of that air, which is dependent on the barometric pressure and temperature. Given these relationships, at a specified AH, the RH of colder air will be higher than that of warmer air. Recent studies indicate that absolute humidity (AH) is associated with the transmission of influenza. Animal experiments show that viral survival and transmissibility are enhanced under conditions of low AH [3]. In temperate climates, seasonal influenza epidemics and waves of the 2009 A/H1N1 influenza pandemic have been associated with decreases in outdoor AH [4, 5]. Despite these findings, the role of AH in viral transmission in indoor environments—where the bulk of influenza transmission in temperate regions likely occurs during winter—has not been examined.

Grade schools are an important setting to study the association between AH and influenza transmission because large numbers of school children are exposed to similar indoor air conditions for many hours during the day and because of the prominent role that viral transmission within schools plays in the spread of influenza in communities [6, 7].

In this study, we examined the variability of indoor AH within and between classrooms during winter in two grade schools in Minnesota, a state with a temperate climate including cold, dry winters. We also examined the association between hourly and daily fluctuations of indoor AH and outdoor AH and the association between indoor AH and indoor temperature, relative humidity (RH), and CO2 levels (as a surrogate for moisture contributions from human respiration). We then determined the effect of in-room humidification on indoor AH in classrooms. Based on these observations, we modeled the potential effects of indoor AH on influenza virus survival in classrooms.

Methods

Schools

The study was conducted in two grade schools in Rochester, Minnesota. These schools are participating in the Integrated Science Education Outreach (InSciEd Out) program, a partnership between the Rochester Public Schools, Mayo Clinic, and Winona State University to enhance science education in schools [8]. The two schools were chosen due to convenience, access, and the interest of school leaders in the study. The Mayo Clinic Institutional Review Board (IRB) determined that the study was not subject to IRB review because it did not involve human subjects. Physical characteristics of the schools are described in Table 1.

Table 1 School descriptions and ventilation capacities

Equipment

Automated data loggers were used to measure temperature, relative humidity and CO2 continuously at 5-minute intervals (HOBO U12-012, Onset: Bourne, MA, temperature accuracy 0.35°C from 0° to 50°C, relative humidity accuracy ±2.5% from 10% to 90% RH; Telaire 7001, CO2 measurement accuracy ±50 ppm). All sensors are calibrated at time of manufacture. No additional validation was done prior to use. Individual home humidifiers (MoistAir MA1201, Essick Air: Little Rock, AR, whole house humidification up to 2,500 sq. ft, humidistat control) were used to raise school humidity levels on weekend days when no students or staff were present.

Sensor placement

Temperature and RH data loggers were placed at a height of 5–7 feet in various locations in School 1 and 2 to assess variability in AH within and between classrooms (Table 1). Thirty loggers were used in School 1 and forty were used in School 2. Standardized locations of loggers for within-classroom measurements were: close to the main doorway from the hallway into the classroom; near exterior facing windows and walls; on interior walls. The standardized location of loggers for between-classroom measurements was close to the main doorway from the hallway into the classroom. CO2 data loggers were placed at three locations in School 1 and four locations in School 2 in both classrooms and common areas.

Humidity modification

Moist-Air MA1201 Essick Humidifiers were placed in 3 individual classrooms on a single weekend day in February 2012, which was chosen for convenience. All manipulations were performed with classroom doors to the hallway closed and building air exchange systems off. Multiple data loggers were present in each room to determine the radius of humidification. Humidifiers were set to target levels of 60% RH and were turned off upon reaching this target. Data loggers continued recording approximately 12 hours after humidifiers were turned off. Data loggers were also present in other classrooms within the school to measure AH changes in non-humidified rooms.

Data management and statistics

Data loggers recorded indoor temperature, RH, and CO2 levels at 5-minute intervals from early January to late March 2011. Data were downloaded from the loggers once a month and exported into Excel using commercial software (HOBOware, Onset: Bourne, MA).

Outdoor AH conditions, measured as vapor pressure, were derived from hourly 2-meter above-ground specific humidity and surface pressure data available from the North American Land Data Assimilation System (NLDAS) project, a joint effort of the National Oceanic and Atmospheric Administration and the National Aeronautics and Space Administration [9]. Specifically, vapor pressure, e, was calculated using known thermodynamic relationships [10] as

e = qp ε + q 1 ε
(1)

where q is specific humidity, p is surface pressure and ε = 0.622.

Indoor AH, again measured as vapor pressure, was calculated from indoor temperature and RH measurements. Saturation vapor pressure, e s (T), was first calculated using the Clausius-Clapeyron equation [10]:

e s T = e s T 0 × exp L T R v 1 T 0 1 T
(2)

where e s (T 0) = 6.11 hPa is a reference saturation vapor pressure at T 0  = 273.15 K, L(T) is the latent heat of vaporization, and R v is the gas constant for water vapor. Once e s (T) is calculated, vapor pressure, e, is then determined as

e = e s T 0 RH 100 %
(3)

Concordance correlation coefficients were used to assess AH variability within classrooms (intra-room), between classrooms (inter-room), and between schools (inter-school).

Estimated 1-hour influenza virus survival (IVS) was calculated using findings derived from laboratory survival experiments [1]:

IVS = exp 4.516 0.0719 e 1
(4)

Predictors of indoor AH were assessed using time-series Auto-Regressive Conditional Heteroskedasticity (ARCH) models to account for daily periodicity [11]. Auto-regression is essential in a time series model as it allows indoor AH at time, t, to be adjusted for prior measurements. In this case, we included in all models the previous two measurements of indoor absolute humidity (t-1 and t-2), as well as the prior 24 hour measurement. Conditional heteroskedasticity utilizes non-constant variance, which accounted for periods of different variance within the data. Indoor AH was predicted by two sets of models. First, using hourly data from January-March 2011, indoor AH was predicted by outdoor AH, adjusted for differences by school location, with and without adjustments for outdoor temperature, and indoor temperature (Models A-C, Table 2). Second, using 5-minute data from January 31- February 4, 2011, indoor AH was predicted by CO2 levels, adjusted for differences by room, with and without adjustment for indoor temperature, and for whether or not school was in session, as a proxy for the presence of students and staff in the environment (Models D-E, Table 3). Robust standard errors were used throughout. We report raw associations between physical measurements of indoor AH and associated variables; also, to assess the degree of sensitivity of indoor AH to these variables, we predicted the change in AH for a one standard deviation (SD) change in each.

Table 2 Daily changes in indoor AH associated with changes in outdoor AH
Table 3 Hourly changes in indoor AH associated with changes in CO 2

Results

Intra- and inter-room and inter-school variability

We explored sensor agreement for indoor AH from January through March using concordance correlation coefficients (CCC) at 3-hour time intervals; details of sensor comparisons are listed in Table 1. There was little variability in indoor AH measurements at different locations within individual classrooms (intra-room concordance correlation coefficients [CCC] >0.90 in both School 1 and 2). Greater variability was observed between classrooms in both School 1 and School 2 (inter-room CCC, 0.81 [CI: 0.76, 0.87] and 0.88 [CI: 0.84, 0.92], respectively) and between School 1 and School 2 as a whole (inter-school CCC, 0.81 [CI: 0.75, 0.88]).

Daily and hourly variability

Outdoor AH, indoor AH, RH, and temperature from a representative sensor in School 1 from January to early March are displayed in Figure 1. The median outdoor AH was 4.62 mb (range: 1.83 mb to 12.50 mb). The median indoor AH was 4.86 mb (range: 2.60 mb to 10.34 mb), with low and high levels that corresponded temporally to those for outdoor AH.

Figure 1
figure 1

Daily changes in winter-time absolute humidity, relative humidity, and temperature. January 19, 2011-March 9, 2011 3 hour time series of indoor temperature, relative humidity and outdoor absolute humidity from representative sensor in School 1.

Adjusting for between school differences, daily periodicity in indoor AH, and auto-regressive lags within the model, outdoor AH was associated with indoor AH over the course of the winter school period (ARCH model regression coefficient 0.51; confidence intervals [CI] 0.48, 0.54; p < 0.001; Table 2: Model A). Further adjustments for outdoor temperature and indoor temperature did not substantially modify the association between outdoor and indoor AH (Models B, C). In the adjusted model (Model C), a one standard deviation (SD) increase in outdoor AH was associated with a 0.90 mb average increase in indoor AH, while a one SD increase in outdoor and indoor temperatures were associated with a −0.24 mb and 0.33 mb average difference in indoor AH, respectively. All three coefficients were highly statistically significant in the adjusted model (p < 0.001).

We assessed 5-minute indoor AH variations during a representative school week in early February 2011. Changes in indoor AH were closely associated with changes in CO2 levels during the school day (Figure 2). In contrast, measures of CO2 and indoor AH on weekends and holidays when staff and students were not present did not demonstrate this relationship (data not shown). We accounted for this difference by adjusting for indoor temperature and school vs. non-school hours (Model E); however, the association between CO2 and indoor AH was nearly identical before and after adjustment (Models D and E). In the adjusted model (Model E), a one SD increase in CO2 corresponded to a 0.27 mb average difference in indoor AH (p < 0.001).

Figure 2
figure 2

Hourly changes in absolute humidity and school-day CO 2 . Time series of average CO2 and indoor absolute humidity during the school day for the week of January 31 to February 4, 2011 in School 1. The dashed line represents mean CO2 levels measured every 5 minutes. The solid line is average indoor absolute humidity for the same week.

Humidity modification

The feasibility of increasing classroom indoor humidity with household humidifiers on weekend days is shown in Figure 3. Mean baseline indoor AH in a single room increased from 4.89 mb to a peak of 8.97 mb in a little over 4 hours. After humidification was discontinued, AH reduced 50% in 2 hours and was reduced to baseline levels in control rooms after 8 hours.

Figure 3
figure 3

Changes in indoor absolute humidity during classroom humidification. Impact of humidifier on classroom indoor absolute humidity on winter weekend day in School 1. Grey lines represent 5-minute individual recordings from 4 different humidity sensors within single room. Mean absolute humidity of these sensors is shown in black. 50% of the humidification effect was gone within 2 hours post humidification.

Virus survival

Using estimates of virus survival from laboratory experiments (Equation 4) [1], maximum projected virus survival of 75% at 1 hour is observed at the lowest measured AH of 2.67 mb (Figure 4A). Conversely, peak wintertime AH values of 9.45 mb correspond to an estimated 1 hour virus survival of 45% (absolute difference: decrease in virus survival of 30%). We estimated projected virus survival changes at indoor humidification target RH levels of 40 and 60% (Figure 4B), values typically reached during non winter-time months and in our humidification experiments (Figure 3). At 60% RH, median virus survival from January through March is predicted to be 34%.

Figure 4
figure 4

A: Calculated daily virus survival at measured absolute humidities. Time series of 1-hour indoor absolute humidity from representative room in School 1 and calculated 1-hour virus survival; Winter 2011. B: Projected virus survival at measured absolute and target relative humidities. Relationship between measured absolute humidity and projected 1-hour virus survival; Relationship between target relative humidities of 40 and 60% and projected 1-hour virus survival with the assumption of no other changes in the environment apart from humidification; Winter 2011, School 1.

Discussion

Indoor absolute humidity in grade schools varies substantially during winter—often to levels that are very low—and these fluctuations are associated primarily with changes in outdoor AH (Figure 1). In addition, during an individual school day, we noted that diurnal changes in indoor AH were associated closely with levels of CO2 (Figure 2). We speculate these diurnal changes in indoor AH are primarily due to the contribution of moisture from human respiration by students, teachers and other staff, although the use of toilets, sinks, and water fountains during weekday hours may account for a portion of these changes. Finally, we showed that classroom humidifiers can increase indoor AH substantially over several hours (Figure 3).

The implications of these findings are important with respect to the potential impact of ambient indoor AH and humidification on survival of influenza virus in the school environment. Modest, achievable changes in indoor AH are likely to have a substantial effect on 1-hour influenza virus survival, as projected from laboratory experiments (Figures 4A, 4B) [1]. For example, mean calculated 1-hour virus survival is projected to decrease from approximately 75% during periods when indoor AH is very low (~3-4 mb) to 35% when indoor AH is raised to 10 mb, a target we demonstrate can be achieved over several hours by a classroom humidifier set to a target RH of 60% on a winter day. During late spring and early fall, indoor school AH often reached 10mb and 60% RH (data not shown). Our estimation of changes in virus survival are limited to models constructed from a single set of animal experiments; however, other experiments have demonstrated similar increases in survival at very low humidity [12, 13]. These data suggest that raising wintertime indoor AH to levels typically experienced indoors during fall and spring offers a strategy to reduce transmission of influenza in schools, and potentially the community, particularly when combined with vaccination and other non-pharmaceutical interventions [1418]. As our measures reflect changes in 1 hour virus survival, humidification over a longer period (4 hours or longer) would afford a greater opportunity to reduce transmission more substantially. Indeed, this intervention may be particularly important when influenza outbreaks (or pandemics) due to novel influenza viruses occur and effective vaccines and antiviral medications are not available. However, the potential effects of wintertime humidification in older buildings need to be evaluated with respect to the potential for building rot or proliferations of mold.

Further research is needed to directly investigate the association of indoor AH with influenza virus survival in the school environment and to evaluate the effect of indoor AH on the incidence of influenza illness and school absence among school children. We also need a better understanding of school Heating Ventilation and Air Condition (HVAC) systems and their capacity for humidification, as well as additional tests of classroom humidification, to better estimate the potential benefit of humidification on decreasing influenza transmission in schools.

Our study is limited by the fact that we measured indoor AH in 2 schools using a single type of sensor in a region with very cold, dry winters. The schools were both older facilities and their HVAC systems had limited capacity for humidification. Measurement of indoor AH in newer facilities with humidification equipment may demonstrate different results. Our tests of classroom humidification were performed under controlled conditions (doors to the classroom closed and HVAC ventilation turned off), and additional study of the feasibility of classroom humidification under routine operating conditions is needed. Finally, our projections of virus survival are limited in that they are calculated using data from previously reported laboratory experiments of influenza virus survival, and we did not include direct measures of infectious virus or virus RNA [1921]. As such, these projections serve only as an estimate of the potential impact of increasing AH in schools on influenza virus survival.

Conclusions

We report here environmental assessments exploring the association of absolute humidity on influenza epidemiology by expanding our understanding of AH in school classrooms. We note the potential for very low indoor AH, a condition that occurs frequently during wintertime months in some regions, to increase the survival and transmission of influenza in this environment. Further investigation is necessary to determine whether increasing humidity in school classrooms is a feasible and effective means of decreasing influenza transmission among school children and in the community.