1 Introduction

With the continuous expansion of power grid and the increasing of power transmission, low frequency oscillation has become an important problem in power system operation [13]. At the end of 2013, the first 1000 kV ultra-high voltage alternating current (UHVAC) project (Huai-Hu UHVAC Project) in East China Power Grid was put into operation. After this, some other UHVAC and ultra-high voltage direct current (UHVDC) projects, such as Bin-Jin UHVDC project, Zhe-Fu UHVAC project, and Ning-Shao UHVDC project will be put into operation one by one. Due to these ultra-high voltage (UHV) projects, the stability characteristics of East China Power Grid will change greatly and the problem of low frequency oscillation will be prominent. Thus, the research on low frequency oscillation of East China Power Grid is of high engineering value.

Previous researches have been carried out on the theories of low frequency oscillation, including the negative damping theory [4], the forced power oscillation theory [5, 6] and the parametric resonance theory [7], etc.

In recent years, low frequency oscillation caused by negative damping has been monitored in East China Power Grid several times. For example, the oscillation between power grid of Zhejiang and Fujian Provinces, whose frequency is 0.3-0.4 Hz, is shown in Fig. 1. Another example is the negative damping oscillation occurred in 500 kV Shenglong Power Plant with 2×1000 MW units, which is weakly connected to Zhejiang power grid. In early years when the power system stabilizators (PSSs) of Shenglong power units had yet not been put into operation, low frequency oscillation between Shenglong Power Plant and Zhejiang power grid had occurred several times, as shown in Fig. 2. This oscillation mode has been suppressed effectively after commissioning of the PSSs.

Fig. 1
figure 1

Power oscillation curve of connection lines between Zhejiang and Fujian Provinces (wide area measurement system (WAMS) data)

Fig. 2
figure 2

Power oscillation curves of units in Shenglong Power Plant (WAMS data)

The forced power oscillation theory gives a good explanation on the power oscillation of Qinshan nuclear generator occurred in October, 2012. 1 Hz oscillation occurred in a 300 MW nuclear unit in Qinshan Plant several times. The maximum power amplitude is about 20 MW, and the longest oscillation duration is about 37 minutes. It is nearly a zero-attenuation oscillation mode, as shown in Fig. 3. It is concluded that this is a forced oscillation in the end. The reason is that the direct drive valve (DDV) (a device in governor) of a small power unit in 110 kV power grid is not stable at certain load level, thus it excites the load fluctuation of the small unit and finally leads to the forced oscillation around 1 Hz in many power units nearby, including the Qinshan nuclear unit. This problem is now solved by the replacement of the defective DDV of the small unit.

Fig. 3
figure 3

Power oscillation curves of Qinshan nuclear power generating unit and some other units nearby

The parametric resonance theory has not been verified in East China Power Grid, but the parametric resonance due to improper parameter of DC modulators has been observed in China Southern Power Grid in 2007 [8]. Except for these three theories, other theories, such as bifurcation theory and chaotic oscillation theory are also mentioned, yet haven’t been proved in practical engineering so far.

2 Research objects and methods

In this paper, the network of East China Power Grid is studied as the research subjects, and the research time period is during the year 2013–2014. The reason is that during this period, the first UHVAC was put into operation, while the second UHVAC project has not. In the early stages of development of UHV power grid, especially when there was only one UHVAC project, the power grid is relatively weak, and the problem of low frequency oscillation is more prominent. Problems during this period are considered to be more representative, and research results will be more valuable for other power companies who plan to develop UHV.

The Huai-Hu UHVAC project, which is connected to Anhui, Zhejiang and Shanghai Provinces, is the first 1000 kV UHVAC demonstration project in East China Power Grid. It has 2×653 km transmission lines on the same tower. The generators of Pingwei and Yuanzhuang Power Plants were accessed into the UHVAC project gradually. The geographical schematic diagram and the distribution of main generator group of East China Power Grid in 2013–2014 are shown in Fig. 4.

Fig. 4
figure 4

Geographical schematic diagram and distribution of main generator group of East China Power Grid in 2013–2014

The main generators are simulated by the sub-transient model considering the damping windings. Most of the generators connected to the 500 kV system in East China Power Grid use the self-excited static excitation system with the PSS module. The models of the excitation system and the PSS are established based on the actual measurement. The static load models are used, and the frequency effect coefficient of the load is ignored except for the generators in Fujian Province.

Nowadays, low frequency oscillation analytical methods include the time domain method and frequency domain method. These two kinds of methods are used in different cases according to different research targets and characteristics. Implicitly Restarted Arnoldi Algorithm [9] is a widely-used eigenvalue-analytical method with some certain advantages in practical analysis of large-scale power systems and has been integrated into the Power System Department-Bonneville Power Administration (PSD-BPA) business program. Therefore, the research in this paper is carried out based on the method.

3 Results and analysis

3.1 Main oscillation modes of East China Power Grid

After commissioning of Huai-Hu UHVAC Project, the main oscillation modes of East China Power Grid are listed.

3.1.1 Oscillation mode between Fujian Province and East China

In this mode, the generators in Fujian Province oscillate against the main network of East China Power Grid. The oscillation frequency is 0.31 Hz and the damping ratio is 19.37%. The modal distribution is shown in Fig. 5. If the PSS of Fujian generators is out of service, the oscillation frequency will increase to 0.34 Hz, while the damping ratio drop to 5.72%, thus it proves the good inhibitory effect of the PSS of Fujian generators on this oscillation mode.

Fig. 5
figure 5

Modal distribution of low-frequency oscillation mode between Fujian Province and East China

3.1.2 Oscillation mode between Anhui Province and East China

In this mode, the generators in Anhui Province oscillate against the main network of East China Power Grid. The oscillation frequency is 0.63 Hz and the damping ratio is 5.46%, as shown in Fig. 6. The mode is of high risk if the PSS of Anhui units is out of service. In this case, the oscillation frequency increases to 0.65 Hz, while the damping ratio drops to 0.36%, which is very close to zero damping.

Fig. 6
figure 6

Modal distribution of low-frequency oscillation mode between Anhui Province and East China

3.1.3 Oscillation mode between Yangcheng Power Plant and East China

In this mode, the generators in Yangcheng, which is a very large and important power plant in East China, oscillate against the main network of East China Power Grid. The oscillation frequency is 0.72 Hz, and the damping ratio is 10.72%, as shown in Fig. 7. If the PSS of Yangcheng units is out of service, the oscillation will be negatively damped (the damping ratio is −1.84%), which will be a serious threat to the operation of East China Power Grid. Thus it proves the vital role of the PSS of Yangcheng generators in the depression of the oscillation mode.

Fig. 7
figure 7

Modal distribution of low-frequency oscillation mode between Yangcheng Power Plant and East China

3.1.4 Oscillation mode between Zhejiang Province and East China

As the power load in Southern Zhejiang Province increases continuously and no big power plant has been put into operation in Southern Zhejiang Province during recent years, there is less demand for the long-distance power transmission from Southern Zhejiang Province. Therefore, the oscillation mode between Zhejiang Province and East China Power Grid, which used to be weakly damped, is no longer acute. In 2014, the oscillation frequency is 0.93 Hz, and the damping ratio is 9.40%, as shown in Fig. 8. Most of the generators connected to 500 kV systems in Zhejiang Province participate in the oscillation mode. As is seen in Fig. 8, the generators in Northern Zhejiang Province swing against those in Southern Zhejiang Province in the mode. If the PSS of Zhejiang units is out of service, the oscillation frequency will increase to 0.98 Hz, while the damping ratio drops to 7.09%.

Fig. 8
figure 8

Modal distribution map of low-frequency oscillation mode between Zhejiang Province and East China

3.1.5 Oscillation mode between the UHV units and East China

After commissioning of Huai-Hu UHVAC project, the power of Yuanzhuang and Pingwei Power Plants is transmitted to East China via the UHVAC lines, thus forming a point-to-grid oscillation mode. In the mode, the UHV units oscillate relative to the East China Power Grid. The oscillation frequency is 1.07 Hz, and the damping ratio is 18.29%, as shown in Fig. 9. If the PSS of UHV units is out of service, the oscillation frequency will increase to 1.15 Hz, while the damping ratio drops to −2.17%.

Fig. 9
figure 9

Modal distribution of low-frequency oscillation mode between UHV units and East China

The typical oscillation modes before commissioning of Huai-Hu UHVAC project are also calculated for comparison, as shown in Table 1. As is seen, East China power grid is significantly strengthened after commissioning of Huai-Hu UHVAC project. As a result, the frequencies of the main oscillation modes increase in different degrees, and the main East China power grid shows good damping characteristics.

Table 1 Low frequency oscillation mode of East China power grid before/after commissioning of Huai-Hu UHVAC project

3.2 Analysis on typical oscillation modes in different power operation modes

Low frequency oscillation modes in 6 different power operation modes of East China Power Grid are analyzed, and the detailed results are shown in Table 2. Considering the successive commissioning of UHV units in 2013–2014, the oscillation characteristics of UHV units vary in different stages. Special research on oscillation modes of UHV units in different operation modes is carried out, as shown in Table 3.

Table 2 Low frequency oscillation mode of East China in different typical operation modes of power grid
Table 3 Low frequency oscillation modes between UHV units and East China in the different stages

The main conclusions are as follows:

1) In 6 typical operation modes, the main oscillation modes include the oscillation among Fujian Province and East China, Anhui and East China, Yangcheng Power Plant and East China. As the demand of long-distance and large power transmission from Southern Zhejiang Province decreases in recent years, the weakly damped oscillation between Southern Zhejiang Province and East China is no longer acute. After commissioning of Huai-Hu UHVAC project, the power of Yuanzhuang and Pingwei Power Plants is transmitted via UHVAC to East China. A new oscillation mode between the UHV power plant and East China appears. The damping ratios of these oscillation modes are all above 3% when the PSSs of UHV units are put into service. (In China, it is generally considered that the damping ratio should be above 3% in order to ensure the dynamic stability of power system). If the corresponding PSS is out of service, the damping ratios of all these modes will decrease greatly and some may even drop to negative values. Therefore, it is very important to assure that the PSSs of generators are in service so as to enhance the dynamic stability of the power system.

2) In 2014, a large capacity of generators in Northern Anhui Province are put into operation gradually. When a large amount of power is transmitted from Northern Anhui Province to Southern Anhui Province, the damping ratio of Anhui Province to East China oscillation mode decreases significantly. For example, in intermediate-load operating mode in winter, the damping ratio is 4.31%, which is quite close to 3%. In practical operation, it must pay attention to dynamic stability analysis on the power system when some important equipment is out of service.

3) In 2013 summer, the frequencies of all the oscillation modes are less than those in 2013 winter. The explanation is that the network structure is continually strengthened after commissioning of power system projects including the 1000 kV UHVAC project.

4) The research on the oscillation modes of the UHV units shows that the damping ratio decreases continually while the capacity of UHV units increases. If the PSSs of UHV units are out of service, the damping ratios of the low frequency oscillation in the typical operation modes in 2013 and 2014 will be far below 3%, which means that there will be a high risk of low frequency oscillation in practical operation. When the PSSs of UHV units are in operation, all the damping ratios will be above 5%.

3.3 Influences of important equipment maintenance on low frequency oscillation characteristics

The influences of important equipment maintenance on the low frequency oscillation mode of East China Power Grid are researched. Six important equipment maintenance projects in 2013 winter are selected as the research ones, which include the Huainan-Wuhu 1000 kV UHVAC single line maintenance (Mode 1), the Wuhu-Anji 1000 kV UHVAC single line maintenance (Mode 2), the Wuhu-Anji 1000 kV UHVAC double line maintenance (Mode 3), the Ningshuang-5906 (500 kV inter-provincial contact line of Zhejiang and Fujian Province) single line maintenance (Mode 4), the Jingping-5901 (500 kV inter-provincial contact line of Zhejiang and Anhui Provinces) single line maintenance (Mode 5) and the Qiaoyong-5493 (500 kV important transmission channel across the Qiantang River) single line maintenance (Mode 6). The results are listed in Table 4.

Table 4 Low frequency oscillation mode of East China power grid in important maintenance modes

The main conclusions are as follows:

1) In normal mode, when the PSSs of UHV units are all in service, the oscillation between UHV units and East China can be inhibited efficiently. However, in the UHV line maintenance mode (Modes 1, 2 and 3), the damping ratio cannot meet the requirement. More research on optimizing the PSS parameters of UHV units needs to be done. As the UHV lines are connected to the provincial power grids, the UHV line maintenance has influences not only on the oscillation mode between UHV units and East China, but also on the oscillation mode between provincial power grids.

2) In 2013–2014, there is only one double 500 kV lines connecting Fujian Province to East China. The problem of the low frequency oscillation is acute in the tie-line maintenance mode, which decreases the oscillation frequency greatly (Mode 4). Therefore, the ties between Fujian Province and East China are advised to be further strengthened. Besides, as the network of East China and the network structures between provincial power grids are compact, the influences of maintenance on oscillation mode will not be too large (Modes 5 and 6) in most cases.

3.4 Time-domain simulation and verification

The time-domain simulation after disturbance is carried out and simulation results are compared with that of the frequency-domain study. The oscillation mode between UHV units and East China has been selected as the research subjects. A three-phase permanent fault occurs in the UHV Huainan station busbar and 0.1 s later the three-phase switch trips. The active power curve of UHV line after this disturbance is shown in Fig. 10.

Fig. 10
figure 10

Active power curve of UHV line after disturbance

The Prony-analysis of the active power curve is carried out based on a “moving-window algorithm” [10]. In this case, the length of each data window is set to 2.5 s, while each data window has a time interval of 1 s, and the analysis region is 0.5–5 s. The Prony-analysis result is shown in Table 5.

Table 5 Prony-analysis results of system signal after disturbance

Based on Table 5, the parameters of the oscillation mode between UHV units and East China Power Grid can be obtained, as shown in Table 6.

Table 6 Results between time domain method and frequency domain method

The results between time and frequency domain shows that the results of this two methods are basically consistent. In the Prony-analysis method, the parameter setting of the data windows has a large influence on the analysis results. Combined engineering experience, we suggest that the best analysis region may be the 2nd to the 5th cycles of the oscillation curve after the disturbance. Similar conclusions can be obtained based on research on other oscillation modes.

3.5 Analysis on the influence of governing system on low frequency oscillation characteristics

In practical engineering nowadays, the research on low frequency oscillation mainly focuses on excitation system, while the influence of governing system is rarely considered. In order to investigate the influence of governing system on low frequency oscillation, the oscillation mode between UHV units and East China power grid is selected as the research object. Figure 11 shows the active power curve of UHV line after the disturbance with/without governing system.

Fig. 11
figure 11

Active power curve of UHV after disturbance with/without governing system

As is seen from Fig. 11, there are some differences between the active power curves of UHV units after the disturbance with or without governing system. In order to illustrate the problem more clearly, the frequency-domain analysis on the low frequency oscillation modes between UHV units and East China are carried out, as shown in Table 7.

Table 7 Low frequency oscillation modes between UHV units and East China under different conditions

As we can see form Table 7, the governing system has some influence on low frequency oscillation characteristic, but not as large as the excitation system (PSS). We can also see from the simulation results that the governing system can improve the system damping to a certain degree. Generally speaking, the response of governing system is much slower than that of the excitation system, thus their responding frequency bands are different. When the oscillation frequency is larger than 1 Hz, the excitation system plays a major role while the effect of governing system is not obvious. However, with the continuous construction of UHV and continued expansion of large-scale power grid, operating conditions of long distance and large capacity power transmission may occur, the oscillations with very low frequencies may be excited, thus the effect of governing system will be more obvious and should not be neglected.

4 Conclusion

The main low frequency oscillation characteristics of East China Power Grid after commissioning of Huai-Hu UHVAC project are researched. The main conclusions are as follows.

1) After commissioning of Huai-Hu UHV project, the typical oscillation modes mainly include the oscillation among Fujian Province and East China, Anhui Province and East China, Yangcheng Power Plant and East China. As the demand of long-distance power transmission from Southern Zhejiang Province drops, the oscillation mode between Zhejiang Province and East China Power Grid, which used to be a weakly damped mode, is improved. A new oscillation mode between UHV units and East China appears. It is very important to ensure the PSS of UHV units to be in service, and the optimization of PSS parameters of UHV units needs to be done continuously.

2) The influences of the important equipment maintenance on low frequency oscillation characteristics of East China Power Grid are researched. It is proved that the maintenance in regional area will not have great influence on power grid stability. But in some regions where the grid structure is not too strong (e.g., the maintenance of UHV tie-lines), the risk of poorly-damped low frequency oscillation may increase. Thematic analysis should be carried out combined with specific work in practical engineering.

3) The time-domain simulation after disturbance is carried out compared with the result of the frequency-domain. Combined with engineering practice, the engineering experiences of parameter setting in time-domain simulation are discussed.

4) The influence of governing system on low frequency oscillation is researched based on the time-domain as well as frequency-domain simulation. It is considered that normally the governing system has some influence on low frequency oscillation characteristic, but not as large as the excitation system (PSS). Their responding frequency bands are quite different. With the continuous expansion of power system scale, oscillations with very low frequencies may occur, which will make the effect of governing system more obvious and non-ignorable.