Abstract
The continuum model is a key paradigm describing the behavior of electromechanical transients in power systems. In the past two decades, much research work has been done on applying the continuum model to analyze the electromechanical wave in power systems. In this work, the uniform and non-uniform continuum models are first briefly described, and some explanations borrowing concepts and tools from other fields are given. Then, the existing approaches of investigating the resulting wave equations are summarized. An application named the zero reflection controller based on the idea of the wave equations is next presented.
Similar content being viewed by others
Avoid common mistakes on your manuscript.
1 Introduction
The electromechanical wave theory introduces a set of models and analytical tools, which provide explanatory and predicting power on how the electromechanical disturbances propagate in a power system. Unlike the traditional method of studying the electromechanical transient phenomena by differential algebraic equations, the electromechanical wave theory introduces partial differential equations known as wave equations to model the transient process in power networks. Obviously, the solution of the partial differential equations exhibits travelling wave behaviour. By doing this, the concepts and tools in the research field of wave equations can be applied to the analysis of electromechanical transients in power systems. This theory casts a light on the global understanding of power system transient behaviour, and can also explain the wave-like behaviour with velocity greatly less than that of light observed in power systems by phasor measurement units (PMUs) [1].
The propagation of electromechanical disturbances, considered as travelling waves, first appeared in 1974. In [2], the second-order linear hyperbolic wave equation is derived with constant parameters from a swing equation in the context of the idealized continuum limit. Here, Semlyen took the power network as a homogeneous and isotropic system with lossless transmission lines and generators reduced to voltage sources behind a constant reactance. Cresap and Hauer [3] went further in 1981, studying what would emerge from the Western Power System in USA with the continuum model. By comparing observed data of the actual system with the model frequencies obtained from the simple wave equations, they conjectured that the continuum model can provide information about the low frequency modes of the system. In Dersin and Levis [4] the homogeneity and the isotropy constraint are relaxed by dividing the network into cells and averaging the system parameters within each cell. His resulting description is a second-order linear elliptic equation. In Thorp et al. [5] reconstructed the similar model in a simple case consisting of generators and transmission lines with the same per-unit length line impedances. In their following work [6], they employed many assumptions made by Semlyen and Dersin into account. These additional factors appear in the continuum model as nonlinear terms, which is indispensable in discussing the disturbance propagation velocities and their stability. In [7], the derivation of the continuum model is presented, making an analogy between power networks and multi-mass disks. In [8], the approximately analytical solutions of the non-uniform continuum model are obtained by borrowing the method of wave propagation in non-uniform media, the so-called Wentzel-Kramers-Brillouin-Jeffery (WKBJ).
The organization of this paper is as follows: Sect. 2 summarizes the basic concepts and derivation of various versions of continuum models. Sect. 3 is devoted to the analysis tools of continuum equations. Section 4 presents the application of the zero reflection controller based on continuum equations. Some open questions are outlined and future research areas prospected in Sect. 5.
2 Uniform and non-uniform continuum models
2.1 Thorp’s version
2.1.1 The uniform version
In [5], J. S. Thorp et al. discussed how to derive the continuum model. They preceded this using the simplest network depicted in Fig. 1. This network consists of generators interconnected with transmission lines having a series resistance-inductance impedance.
Applying the Kirchoff’s current law at node (x, y), the following equation can be obtained:
where ΔY is the shunt admittance.
Substituting the Taylor series expansions of E(x + Δ, y), E(x − Δ, y), E(x, y + Δ), and E(x, y − Δ) about E(x, y) up to the fourth order into the above, (1) becomes
Now, considering the source voltage as a constant in magnitude and a variable in phase δ, the power injecting into node (x, y) can be expressed as
where G = Re{Y}.
The classical model describing the electromechanical transients in power networks is the so-called swing equation. By introducing a set of units defined relative to a system base power S base , the swing equation takes the following form:
where H is the inertia constant in seconds; ω0 is the rated electrical angular frequency or synchronous speed; D is the rotor damping constant in s2; P a is the accelerating power; P m is the mechanical input power; P e is the electrical output power; and δ is the rotor angle with respect to a synchronously rotating reference frame in electrical radians.
In the continuum model, the parameters of the swing equation are taken as the functions of the spatial coordinates x and y, which is:
When Δ approaches to zero, the swing equation becomes:
where \( v^{2} \; = \;\frac{{\omega V^{2} \sin \theta }}{2h\left| z \right|};\quad u^{2} \; = \;\frac{{\omega V^{2} \cos \theta }}{2h\left| z \right|};\quad P\; = \;\frac{{\omega \left( {p_{m} \; - \;GV^{2} } \right)}}{2h};\quad \gamma \; = \;\frac{{\omega^{2} d}}{2h}; \)θ is the line impedance angle; V is the voltage magnitude; and G is the line conductance.
This is the so called continuum model. This model represents an alternative approach to analyse the electromechanical transients in power systems. The classical swing equation modelling the dynamics of rotors indirectly reflects the propagation of electromechanical transients in power networks suffering a disturbance. The continuum model assumes that each generator/load in a power system be represented as a continuum. The travelling solutions of this model demonstrate the disturbances of all generators, and directly show the propagation of electromechanical transients. The rationality of this partial differential equation model lies in the fact that the disturbances in realistic power networks propagate with a speed much less than light. Another benefit of this model involves the stability analysis. It is usually difficult to discuss the stability of generators one by one in multi-machine systems, since the number of generators could be very large. The continuum model overcomes this obstacle by the stability analysis of a continuum system.
2.1.2 The non-uniform continuum model
In [5], the per-unit length line impedances of transmission lines are assumed the same, and the orientation of the branches connecting the nodes allows for 0° or 90° with respect to the reference axis. Due to these assumptions the derived continuum model is of the so-called uniform form. In [6], these prerequisites are relaxed to reflect the anisotropy and heterogeneity. In turn, the countable finite branches connecting to the nodes allow for different per-unit length line impedances, and intersect with angle θ i with respect to the reference axis.
Consider a line i connected to a generator. The two parts of this line which are at the left side and the right side of the x-axis are denoted as “−” and “+”, respectively. The per-unit length line impedances of these two parts are Z − i = R − i + jX − i and Z + i = R + i + jX + i , respectively. The angle θ i of the line with respect to the reference axis is nonisotropic. G int − jB int and G s − jB s denote the per-unit length generator internal admittance and shunt admittance, respectively. The unit length of the line is Δ, and r i is a unit vector. The internal and external voltage phase angles of the generator are \( \phi (\overline{x} ) \) and \( \delta (\overline{x} ) \), respectively. When Δ approaches to zero, the discrete system transforms into a so-called continuum system.
The power flow in line i can be obtained as
Given that the incremental unit Δ is small, by applying the Taylor series expansion, the following expressions can be obtained:
and
Using trigonometric equations for a sufficiently small Δ, (6) becomes
The above equation can be rewritten in a more compacted form as
where
Now assuming that there are N lines, then the total power injection into the network takes the following form:
where
The active power Pe supplied by the generator is
Since the difference between the electrical and mechanical power causes the acceleration of the generator’s rotor, the swing equation becomes
The parameters m, d and pm are the generator inertia, damping, and mechanical power, respectively.
Thus, the following equations are obtained:
In practice, the structure of a power network is alike a mesh in the plane while generators and loads locate at discrete node in the network. An alternative is to consider the system parameters are smooth functions of spatial coordinates, which define a partial differential equation while they make the network structure preserved. Thus, the continuum model’s parameters are parted into two groups: line parameters, such as G and B, describing a mesh in spatial coordinates; and nodal parameters, such as m, d, pm, Gint, Bint, describing generator and loads in a power network [6].
Let the distributed real power be \( p(\overline{x} ) \), then \( P^{e} = \Delta p(\overline{x} ) \). So the following expression holds in spatial coordinates:
Since the per-unit length reactance is high with respect to resistance, namely B ≫ G in a lossless network or high voltage networks, the second term in the right hand of (17) can be neglected. Hence (17) reduces to:
This equation embodies the significant insight of the power networks.
Let
then p is a vector field in the two dimensions plane. Compared with the conventional power flow equations, the vector field can be viewed as the active power flow density. Then, \( p(\overline{x} ) \) measures the active power flow density that flows out of a point \( \overline{x} \) in the network. Bearing the principle of continuity in physics in mind, which states that, in the absence of the creation or destruction of matter, the density within a region of space can change only by making it flow into or away from the region. It holds that if the divergence of p is positive at a point, the point is a source of power. Otherwise, if the divergence of the vector field is negative at the point or region, then the point or region is a sink.
Another interesting characteristic is that, if matrix B and G are assumed to be symmetrical second-order tensors, the anisotropic transmission lines can be analysed by tensor analysis. Reference [6] also demonstrates how these procedures proceed.
2.2 Wang’s version
In [7], Delin Wang developed a similar continuum model in the simplest chain network with the same per-unit length admittance. The difference lies in that the continuum model is obtained through the wave equation of the forced torsional vibration equation of multi-mass disks in continuum. To that end, the electric power transmission through a transmission line is taken as the mechanical power through a shaft in multi-mass disks; a transmission line is treated as a shaft with elasticity but no inertia in a torsional vibration system. Bearing these similarities, the wave equation of electromechanical transients is derived. The correspondence between the variables in power systems and the variables in multi-mass disks is also discussed.
A classical forced torsional vibration system is composed of N disks with different inertia constants aligned in a straight light elastic shaft. For an ideal elastic shaft of length l without inertia and within its elastic limit, the following relationship of torque T and torsional angle θ holds
where k is the torsional rigidity, and \( k\; = \;\frac{1}{2}K\pi r^{4} \) when the elastic shaft is a solid cylinder with radius r and modulus with rigidity K.
Using Ω to represent the angular velocity of the shaft, then
where P m is the shaft power.
Labeling the internal damping coefficient as ε, the internal damping torque T ɛ can be described as
Under some assumptions, the equation set describing the dynamics of the torsional vibration of multi-mass disks is
where θ i is the torsional angle; J i ′is the moment of inertia of theith disk; d ′ i is the damping coefficient; and T iΣ is the total driving torque imposed on theith disk.
If there are infinite disks spread along the finite length shaft, the distance between two disks can be considered as an infinitesimal. Therefore, the continuum model of torsional vibration of multi-mass disks is
Consider the simplest chain system with each bus connected with a generator and a load, and buses connected by transmission lines in series. The length of a transmission line is l, the per-unit length impedance and the per-unit length admittance are r0 + jx0 and g0 − jb0, respectively. Then,
The active power injected into the transmission line connecting theith and (i + 1)th buses is
where \( \hat{V}_{i} \; = \;V_{i} \angle \theta_{i} \) and \( \hat{V}_{i + 1} \; = \;V_{i + 1} \angle \theta_{i + 1} \) are the bus voltages, θi,i+1 = θ i − θi+1 is the voltage angle difference. Under certain assumptions, simplifications can be made:
The line loss can be calculated as
Comparing (21) with (27), and (22) with (28), it is obvious that the electrical power flow in a transmission line has the same mathematical form as the mechanical power through a shaft. Thus, the chain power system is mathematically equivalent to the forced torsional vibration system of multi-mass disks, and the wave equation of the electromechanical disturbance propagation in the power system yields directly from (24) as
The per-unit form of (29) is
where h and d are the distributed inertia and the damping constant, respectively, and ω is the electrical angular velocity.
3 Analysis technique
3.1 Quantitative analysis
In [8], Delin Wang employed the WKBJ to approximate the analytical solutions of a non-uniform continuum model.
The dynamic behaviours describing the generator rotor’s relative angular speed ω and the electrical power p are given by
where m(x) is the per-unit rotor’s inertia, and b(x) is the per-unit length line susceptance. x represents an one-dimension spatial coordinate.
Let ω denote the rotor’s relative angular speed, and let
where Ω(x) and P(x) are complex functions. Then,
Assume that b(x) and m(x) are continuous functions of the spatial coordinate x, and the following expressions hold.
Then, equation (32) becomes approximately
where \( \nu (x) = \sqrt {b(x)/m(x)} \) is the propagation speed of the wave crest.
Following the WKBJ approximate method of the classical wave motion theory in the non-uniform media, let
Then, the WKBJ solution in the form of (32) can be obtained as
These are the solutions when d2Ω0(x)/dx2 and d2P0(x)/dx2 are neglected.
It is difficult to integrate the analytical solution of the continuum model because its coefficients are functions of spatial coordinates. But if these coefficients are assumed to be constants, an analytical solution can be obtained, and to some extent explains the behaviour of power networks. However, this method ignores some characteristics of the power network. New tools, such as the Green function [9–11] or other numerical method, need to be employed to solve the partial differential equations. A simplified method to integrate the continuum equations numerically is presented in [12], where the concepts and tools in electromagnetic equations, such as the finite-differencing scenario, are applied to the solution of continuum power networks. By doing this, software designed for electromagnetics can be used for continuum power systems.
This method of using commercial software leads to several advantages, among them increased flexibility and reduced computational time.
3.2 Qualitative analysis
In [13], an analytical approach is proposed to study the propagation mechanism of electro-mechanical disturbances in a chain power system. Applying the Laplace transform to a mulit-segment uniform chain discrete power system can reveal significant characteristics of electromechanical disturbance propagation. Specifically, the analytical expression with respect to time, the reflection and transmission formulations can be carried out.
A mulit-segment uniform chain discrete power system includes two parts, parts I and II. Both parts are composed of the cascades of multiple T-type links. Part I consists of a transmission line with resistance R1/2, reactance X1/2, and a generator with rotor inertia M1 and damping D1. Part II consists of a transmission line with resistance R2/2, reactance X2/2, and a generator with rotor inertia M2 and damping D2.
Provided that there are q buses connected to a generator with rotor inertia constant M1 and damping D1, then the swing equations of Part I at buses k and k + 1 can be expressed as
where 1 ≤ k < k + 1 < m.
Using the Laplace transform yields
where Z1 = R ′1 +sX1, and Z2 = 1/(D1 + sM1).
Similarly, for Part II we have
where Z3 = R ′2 + sX2, Z4 = 1/(D2 + sM2) and m + 1 ≤ k < k + 1 < q.
Let the trial solution of incremental power on the transmission line between buses k and k + 1 be
where A1, A2, A3, v1 and v2 are unknown complex constants.
Thus, the following results can be obtained:
Let n2 and η2 be the reflection coefficient and transmission coefficient of Part I, respectively. According to these equations, we have
where ω I k is the angular velocity at bus k in Part I.
Taking the similar procedures for Part II, we have
where ω II k is the angular velocity at bus k in Part II.
Let the reflection coefficient be a real number. By neglecting the rotor damping coefficient D and the line equivalent loss coefficient and performing the inverse Laplace transform, the following expressions hold:
Equations (45) and (46) reveal a significant characteristic that a linear combination of different orders of the Bessel function can represent the analytical solution to the equations governing electromechanical disturbance propagation in a multi-segment uniform system. Hence, the angle increment of the rotor could be rewritten as
where f is a positive integer function, and {λ k } is a linear base of the Hilbert space.
Considering the properties of the Bessel function, the average velocities of the electromechanical disturbance propagation have the following relationships:
An alternative method of analysing the continuum model is the so-called Lyapunov first method, also known as the small signal analysis method. However, a weakness of this method is that simplification of some nonlinear factors is inevitable.
4 Applications: zero reflection controller
Since electromechanical disturbances propagate as travelling waves, a controller oriented from impedance matching on transmission lines is constructed to quench the caused disturbances. In [14, 15], zero-refection controllers based on an impedance matching constraint at the boundary of the network dramatically suppress the propagation of the electromechanical waves.
4.1 The principle of zero reflection controllers
In [16], a one-dimension network with homogeneous lossless transmission lines is considered, and the damp of the generator’s rotor is neglected. Under some certain assumptions, which are studied detailedly in [16], the following equations are obtained:
wherez−1 = g − jb. Z is the impedance in per unit length; h is the inertia constant per unit length; d is the damping coefficient per unit length; the voltage magnitude E is constant in space and time.
Comparing (49) and (50) with the standard telegrapher’s equations for electromagnetic waves on a transmission line, it is self-evident that P plays the role of line current and ω plays the role of voltage. Besides, linear undamped wave equations hold:
With regard to a two-dimensional network, a similar derivation lead to the same type of equations, in which the Laplacian operator replaces the second derivative with respect to x. However, the units of the parameters are now different. Fortunately, a realistic power system could be thought of an interconnection of various one-dimensional lines.
Equation (51) is a wave equation, and the characteristic propagation velocity is given in the follow form:
In [14], a string system with 64 identical generators connected to uniform transmission lines is studied to investigate the wave travelling in one-dimension power systems. The forward and reverse propagating waves and their reflections at the open-ended boundaries of the string of generators can be observed. The slow dispersion of the wave attributes to the generator damping and the dissipative component of the line impedance. It can be demonstrated that the theoretical value of the propagating time of the electromechanical waves agrees well with the numerically result [14].
The formulation of calculating wave length λ associated with the wave-like swing motions is given:
where f is the frequency of the swing mode driving the wave-like propagation.
The electromechanical waves are analogous to travelling electromagnetic waves on transmission lines. As for transmission lines, current and voltage are used to describe the travelling waves, and the reflection is characterized in term of reflection coefficients in the light of the characteristic impedance of the lines. Additionally, proper termination can set the refection coefficient to zero, which excludes any refection on the line.
In the case of the power system model, which displays electromechanical wave phenomena, the variables frequency and power flow naturally play a similar part as voltage and current in the electromechanical transmission line case do. To associate the characteristic impedance with P and ω, Let the two variables regarding forward travelling waves be:
where v is the propagation velocity. Substituting these into (50) yields:
Straightforwardly, we have:
This implies that the forward propagating waves in term of power flow and frequency remain in a constant proportion. The characteristic impedance, or proportionality constant, is then defined by
At the termination of the string, the forward and reverse travelling waves must sum in a particular way to satisfy the imposed boundary condition. For example, if one termination is open, power flow is equal to zero, then the sum of the reverse travelling wave and the forward travelling wave must be zero at the boundary which means they are opposite number. This case is equivalent to a negative reflection in power flow and a positive reflection in frequency. If the string of generators is connected to a so-called infinite bus at which the frequency remains constant, then the forward travelling wave in frequency must be a negative reflection of the reverse travelling wave. This is equivalent to a positive reflection for power flow and a negative reflection in frequency.
4.2 The zero reflection control
Based on an approach used in the classical electromagnetic transmission line theory, if assume a time harmonic electromechanical wave excitation, then the time-harmonic telegrapher’s equations is employed, which are ordinary differential equations in x for the ω(x) and P(x). Thus, the solution of this equation can be derived for the frequency and power, respectively. In turn, these results can be used to calculate the reflection coefficient and transmission coefficient easily.
The typical case dealt with in the electromagnetic transmission line theory addressed only one transmission line ended with the load impedance C. Matching this impedance with the characteristic impedance yields zero reflection.
Changing the parameters of C, ω C , and Pc results in various kinds of electromechanical wave controllers. These control laws stem from the aforementioned electromechanical wave theory but will be realized on discrete nonuniform power networks, where the wave behaviour might not exist apparently. The zero-transmission controller aims at quenching the perturbation in [16].
In [14], it is shown that how this impedance matching scheme can be implemented with the nonlinear discrete swing equation of a generator.
The similarity of electric power P and frequency ω to current and voltage in the transmission line theory, respectively, yields:
which is the controlled variable.
The control law
is proposed to design the zero-reflection control. Here, K is a gain, P g is the deviation of P from its nominal value. This controller can be implemented if the parameters C and D need be estimated properly, and P and ω be measured accurately.
Simulation results show that this control law achieves to some extent the eradication of the reflection observed in the string system. In fact, the controller does not completely exclude reflections. One of the explanations is attributed to the difference between the wave equation model used to derive the controller and the simulation model. The former is continuum, linear, and neglects damping; the latter is discrete and of nonlinearities. Besides, the implementation of the controller is to feedback the control signal to an input into a generator, not achieved directly.
It is also possible to design a zero-reflection controller by manipulating the power flowing into the terminal load in a string of generators, and a method for this objective is proposed in [17].
4.3 Estimating the generation trip event
Since an electromechanical disturbance is propagating as a wave, a generation trip event can be estimated by synchronized phasor measurements [20].
Let the location of a frequency measurement unit and the detection time be (x i , y i ) and t i , respectively. The index i (i = 1,2,…,N) denotes theith frequency measurement unit deployed in the monitoring area. Let (xe, ye) and te represent the location and time of an event, respectively. Now the values of (xe, ye) and te need to be estimated so as to obtain the information corresponding to the event. Let the distance between the event and theith measurement unit take the following form:
Denoting the average speed of the electromechanical wave as V, Li can be expressed as
Substituting (62) into (61), then there will be three unknown variables. If the number of the frequency measurement units is more than four, then the above two equations can be solved in light of the linear square method. The value of (xe, ye) and te can be obtained next.
5 Concluding remarks
In recent years, electromechanical wave propagation in power systems has received more and more concerns. In this paper, a brief description on the major versions of continuum models is first given. One of the principal goals is to demonstrate the applicability of the relevant concepts and approaches developed in other fields. For this purpose, some representative examples like adopting tensor analysis to explain the equation describing the structure of the network equation are investigated in detail, and the derivation of the continuum model from the multi-mass disks, the numerical solution of a continuum model by the method in electromagnetic equations, and the analytical solution of the continuum model in the WKBJ approximation. It is also discussed on how to employ traditional tools, such as small signal analysis to address the continuum model. Finally, some applications of the zero reflection controller based on continuum model are investigated to mitigate the electromechanical disturbances.
Unfortunately, the well-established small signal stability analysis method cannot accommodate the nonlinear term in the continuum model, which is of importance for describing the behaviour of power networks. Extending the research work towards the qualitative analysis of continuum models is highly expected.
One of the most striking applications of the continuum model in power networks is the electromechanical wave controllers aiming at reducing electromechanical disturbances, such as the zero reflection controllers. However, the influence of those controllers on power systems remains unclear. In [17], the stability of power networks with electromechanical wave controllers installed is discussed. In [19], the power system stabilizer is employed to mitigate the electromechanical wave. It is hoped that future efforts will reveal the relationship between the stability and these controllers from the perspective of control theory.
The issue that to what extent the continuum model accurately describes the behaviour of electromechanical transients in power systems is still an open question. In addition, it is possible that, through comparisons with other fields, the continuum model can be understood from various points of view. Recently, Nutaro and Protopoopescu [18] and his co-workers discovered a phenomenon that the delay of phase and frequency in power systems can be explained by the classical swing equation and Kirchhoff equation. It is expected that a further investigation on this issue could provide some insight on the continuum model.
References
Faulk D, Murphy RJ (1994) Comanche peak unit No. 2 100% load rejection test-underfrequency and system phasors measured across TU electric power system. In: Proceedings of the 47th annual conference for protective relay engineers, College Station, 21–23 Mar 1994
Semlyen A (1974) Analysis of disturbance propagation in power systems based on a homogeneous dynamic model. IEEE Trans Power Appl Syst 93(2):676–684
Cresap PL, Hauer JF (1981) Emergence of a new swing mode in the western power system. IEEE Trans Power Appl Syst 100(4):2037–2045
Dersin P, Levis AH (1984) Aggregate feasibility sets for large power networks. In: Proceedings of the 9th triennial world congress of IFAC, vol 4, Budapest, 2–6 July 1984, pp 2163–2168
Thorp JS, Seyler CE, Phadke AG (1998) Electromechanical wave propagation in large electric power systems. IEEE Trans Circ Syst I 45(6):614–622
Parashar M, Thorp JS, Seyler CE (2004) Continuum modeling of electromechanical dynamics in large-scale power systems. IEEE Trans Circ Syst I 51(9):1848–1858
Wang D, Wang X, Thorp JS (2006) Study on electromechanical wave continuum model for power systems in mechanics. In: Proceedings of the 2006 IEEE power engineering society general meeting, Montreal, 18–22 June 2006, 9 pp
Wang D, Wang X (2008) Analytical study on electromechanical wave propagation in a non-uniform continuum power system. In: Proceedings of the 3rd international conference on deregulation and restructuring and power technologies, Nanjing, 6–9 Apr 2008, pp 958–963
Logan JD (1988) Applied partial differential equations. Springer, New York
Kevorkian J (2000) Partial differential equations. Springer, New York
Haberman R (1988) Elementary applied partial differential equations: with Fourier series and boundary value problem, 3rd edn. Prentice-Hall, Englewood Ciffs
Thomas AJ, Mahajan SM (2009) Electromechanical wave analysis through transient magnetic modeling. IEEE Trans Power Deliv 24(4):2336–2343
Wang D, Wang X (2012) Electromechanical disturbance propagation and oscillation in power systems. In: Proceedings of the 2012 IEEE power and energy society general meeting, San Diego, 22–26 July 2012, 5 pp
Lesieutre BC, Scholtz E, Verghese GC (2002) A zero-reflection controller for electromechanical disturbances in power networks. In: Proceedings of the 2002 power system computation conference, Seville, 24–28 June 2002, pp 913–919
Lesieutre B, Scholtz E, Verghese G (2002) Impedance matching controllers to extinguish electromechanical waves in power networks. In: Proceedings of the 2002 international conference on control applications, vol 1, Glasgow, 18–20 Sept 2002, pp 25–30
Scholtz E (2004) Observer-based monitors and distributed wave controller for electromechanical disturbances in power systems. Ph.D Thesis, MIT, Cambridge
Samulesson O (1997) Power system damping-structural aspects of controlling active power. Ph.D. Thesis, Lund University, Lund
Nutaro J, Protopoopescu V (2012) A new model of frequency delay in power systems. IEEE Trans Circ Syst II 59(10):1–5
Zhang P, Thorp JS, Wang X et al (2012) The effect of electromechanical wave controller on inter-area modes. In: Proceedings of the 2012 IEEE power and energy society general meeting, San Diego, 22–26 July 2012, 8 pp
Ali M, Buisson J, Phulpin Y (2010) Improved control strategy to mitigate electromechanical wave propagation using PSS. In: Proceedings of the 15th IEEE mediterranean electrotechnical conference, Valletta, 26–28 Apr 2010, pp 35–40
Zheng G, Liu Y, Radman G (2012) Wide area frequency based generation trip event location estimation. In: Proceedings of the 2012 IEEE power engineering society general meeting, San Diego, 22–26 July 2012, 6 pp
Acknowledgments
This work is jointly supported by a discovery project of Australia Research Council (No. DP120101345), and National High Technology Research and Development Program of China (863 Program) (No. 2011AA05A105).
Author information
Authors and Affiliations
Corresponding author
Additional information
CrossCheck date: 23 April 2014
Rights and permissions
This article is published under license to BioMed Central Ltd. Open Access This article is distributed under the terms of the Creative Commons Attribution License which permits any use, distribution, and reproduction in any medium, provided the original author(s) and the source are credited.
About this article
Cite this article
XU, Y., WEN, F., LEDWICH, G. et al. Electromechanical wave in power systems: theory and applications. J. Mod. Power Syst. Clean Energy 2, 163–172 (2014). https://doi.org/10.1007/s40565-014-0054-2