Abstract
In this study, a solar ejector cooling system is theoretically analyzed to evaluate refrigerants and determine their performance characteristics and environment-friendly nature for a fixed ejector geometry under a set of standard operating conditions. The results show that the refrigerant R1234yf is the best choice for the cycle, and is an environment-friendly refrigerant with thermo-physical properties similar to that of R134a. Moreover, it has a high entrainment ratio and is cheap when compared to other refrigerants, nonflammable, and safe. The results indicate that the cooling cycle COP increases during the day hours as the generator temperature increases and reaches a maximum value of 0.59 at an optimum generator temperature of 86 \({^{\circ }}\)C in the middle of the day. The overall efficiency of the system varied in the range 38–45%. Furthermore, it was found that increasing the generator pressure by 40% reduced the COP by 58.5% and increased the critical backpressure by 27.3%.
Similar content being viewed by others
Abbreviations
- \({A}_{\mathrm{c} }\) :
-
Area of solar collector (m\(^{2}\))
- \({m}_{\mathrm{c} }\) :
-
Solar collector mass flow rate (kg h\(^{-1}\) m\(^{-2}\))
- \({m}_{\mathrm{p}}\) :
-
Primary mass flow rate (kg s\(^{-1}\))
- \({m}_{\mathrm{s}}\) :
-
Secondary mass flow rate (kg s\(^{-1}\))
- \(C_\mathrm{r}\) :
-
Compression ratio
- H:
-
Enthalpy (kJ kg\(^{-1}\))
- \({e}_{\mathrm{r}}\) :
-
Expansion ratio
- \({P}_{\mathrm{cri}}\) :
-
Critical condenser back pressure (kPa)
- \({P}_{\mathrm{e}}\) :
-
Evaporator pressure (kPa)
- \({A}_{3}\) :
-
Area of mixing chamber (m\(^{2}\))
- \({A}_{\mathrm{t}}\) :
-
Area of nozzle throat (m\(^{2}\))
- A :
-
Primary flow location at the inlet of the nozzle
- \({V}_\mathrm{s}\) :
-
Volume of storage tank (\(\hbox {m}^{3}\))
- G :
-
Total irradiance (\(\hbox {W m}^{-2}\))
- \(T_{\mathrm{g}}\) :
-
Temperature of generator (\({^{\circ }}\)C)
- \({T}_{\mathrm{c}}\) :
-
Temperature of condenser (\({^{\circ }}\)C)
- A_r:
-
Ejector area ratio
- \({C}_{\mathrm{p}}\) :
-
Specific heat (\(\hbox {kJ kg}^{-1} \hbox {K}^{-1}\))
- \({T}_{\mathrm{e}}\) :
-
Temperature of evaporator (\({^{\circ }}\)C)
- M :
-
Mach number
- R :
-
Gas constant (kJ kg\(^{-1}\) K\(^{-1}\))
- Q :
-
Heat transfer rate (kW)
- \({T}_{\mathrm{out~c}}\) :
-
Temperature at the exit of solar collector (\({^{\circ }}\)C)
- \({T}_\mathrm{out~storage}\) :
-
Temperature at the exit of storage tank (\({^{\circ }}\)C)
- \({T}_{\mathrm{a}}\) :
-
Temperature of the ambient air (\({^{\circ }}\)C)
- \({T}_{\mathrm{cri}}\) :
-
Critical temperature (\({^{\circ }}\)C)
- \({P}_{\mathrm{g}}\) :
-
Generator pressure (kPa)
- COP:
-
Coefficient of performance
- CFC:
-
Chlorofluorocarbon
- EES:
-
Engineering equation solver
- TRNSYS:
-
TRaNsient SYstem Simulation Program
- ODP:
-
Ozone depletion potential
- SECS:
-
Solar ejector cooling system
- GWP:
-
Global warming potential
- JUST:
-
Jordan University of Science and Technology
- 1-D:
-
One-dimensional
- G:
-
Generator
- E:
-
Evaporator
- C:
-
Condenser
- P:
-
Primary flow
- P1:
-
Primary nozzle exit
- \({p}_{\mathrm{y}}\) :
-
Primary flow at section y–y
- S:
-
Secondary flow
- M:
-
Mixing section m–m
- \(\Omega \) :
-
Entrainment ratio
- \(\eta _{\mathrm{o}}\) :
-
SECS overall efficiency
- \(\eta _{\mathrm{sc}}\) :
-
Efficiency for solar collector
- \({\gamma }\) :
-
Specific heat ratio
- \({\phi }_{\mathrm{m}}\) :
-
Coefficient of heat losses
References
Etier, I.; Al-Tarabsheh, A.; Ababneh, M.: Analysis of solar radiation in Jordan. Jordan J. Mech. Ind. Eng. 4(6), 733–738
Vidal, H.; Colle, S.; Pereira, G.D.S.: Modelling and hourly simulation of a solar ejector cooling system. Appl. Therm. Eng. 26(7), 663–672 (2006)
Keenan, J.H.: An investigation of ejector design by analysis and experiment. J. Appl. Mech. 17, 299 (1950)
Khalil, A.; Fatouh, M.; Elgendy, E.: Ejector design and theoretical study of R134a ejector refrigeration cycle. Int. J. Refrig. 34(7), 1684–1698 (2011)
Abdulateef, J.M.; Murad, N.M.; Alghoul, M.A.; Zaharim, A.; Sopian, K.: Economic analysis of combines solar assisted ejector absorption refrigeration system. In: Proceedings of the 5th International Conference on Energy and Development - Environment - Biomedicine 2011, pp. 157–161 (2011)
Pollerberg, C.; Ali, A.H.; Dötsch, C.: Experimental study on the performance of a solar driven steam jet ejector chiller. Energy Convers. Manag. 49, 3318–3325 (2008)
Al-Khalidy, N.: Performance of solar refrigerant ejector refrigerating machine. ASHRAE Trans. 103(1), 56–64 (1997)
Sokolov, M.; Hershgal, D.: Optimal coupling and feasibility of a solar-powered year-round ejector air conditioner. Sol. Energy 50(6), 507–516 (1993)
Pollerberg, C.; Heinzel, A.; Weidner, E.: Model of a solar driven steam jet ejector chiller and investigation of its dynamic operational behavior. Sol. Energy 83, 732–742 (2009)
Diaconu, B.M.: Energy analysis of a solar-assisted ejector cycle air conditioning system with low temperature thermal energy storage. Renew. Energy 37, 266–276 (2012)
Ma, X.; Zhang, W.; Omer, S.A.; Riffat, S.B.: Experimental investigation of a novel steam ejector refrigerator suitable for solar energy applications. Appl. Therm. Eng. 30(11), 1320–1325 (2010)
Tashtoush, B.; Alshare, A.; Al-Rifai, S.: Hourly dynamic simulation of solar ejector cooling system using TRNSYS for Jordanian climate. Energy Convers. Manag. 100, 288–299 (2015)
Cizungu, K.; Mani, A.; Groll, M.: Performance comparison of vapour jet refrigeration system with environment friendly working fluids. Appl. Therm. Eng. 21(5), 585–598 (2001)
Huang, B.J.; Chang, J.M.; Petrenko, V.A.; Zhuk, K.B.: A solar ejector cooling system using refrigerant R141b. Sol. Energy 64(4), 223–226 (1998)
Selvaraju, A.; Mani, A.: Analysis of an ejector with environment friendly refrigerants. Appl. Therm. Eng. 24(5), 827–838 (2004)
Nehdi, E.; Kairouani, L.; Elakhdar, M.: A solar ejector air-conditioning system using environment-friendly working fluids. Int. J. Energy Res. 32(13), 1194–1201 (2008)
Roman, R.; Hernandez, J.I.: Performance of ejector cooling systems using low ecological impact refrigerants. Int. J. Refrig. 34(7), 1707–1716 (2011)
Fong, K.F.; Lee, C.K.; Chow, T.T.: Improvement of solar-electric compression refrigeration system through ejector-assisted vapour compression chiller for space conditioning in subtropical climate. Energy Build. 43(12), 3383–3390 (2011)
Alexis, G.K.; Karayiannis, E.K.: A solar ejector cooling system using refrigerant R134a in the Athens area. Renew. Energy 30(9), 1457–1469 (2005)
Sun, D.W.; Eames, I.W.: Performance characteristics of HCFC-123 ejector refrigeration cycles. Int. J. Energy Res. 20(10), 871–885 (1996)
Steven, B.J.; Claudio, Z.; Alberto, C.: The fluorinated olefin R-1234ze(z) as a high-temperature heat pumping refrigerant. Int. J. Refrig. 32, 1412–22 (2009)
Kasaeian, A. B.; Daviran, S.: Performance analysis of solar combined ejector-vapor compression cycle using environmental friendly refrigerants. IIUM Eng. J. 14(1) (2013)
Li, H.; Cao, F.; Bu, X.; Wang, L.; Wang, X.: Performance characteristics of R1234yf ejector-expansion refrigeration cycle. Appl. Energy 121, 96–103 (2014)
Chen, J.; Havtun, H.; Palm, B.: Screening of working fluids for the ejector refrigeration system. Int. J. Refrig. 47, 1–14 (2014)
Sun, D.-W.: Comparative study of the performance of an ejector refrigeration cycle operating with various refrigerants. Energy Convers. Manag. 40, 873–84 (1999)
Allouche, Y.; Varga, S.; Bouden, C.; Oliveira, A.: Dynamic simulation of an integrated solar-driven ejector based air conditioning system with PCM cold storage. Appl. Energy 190, 600–611 (2017)
Carrillo, J.; Flor, F.; Lissén, J.: Thermodynamic comparison of ejector cooling cycles. Ejector characterisation by means of entrainment ratio and compression efficiency. Int. J. Refrig. 74, 371–384 (2017)
Megdouli, K.; Tashtoush, B.M.; Nahdi, E.; Elakhdar, M.; Kairouani, L.; Mhimid, A.: Thermodynamic analysis of a novel ejector-cascade refrigeration cycles for freezing process applications and air-conditioning. Int. J. Refrig. 70, 108–118 (2016)
Chen, W.; Shi, Ch; Zhang, S.; Chen, H.; Chong, D.; Yan, J.: Theoretical analysis of ejector refrigeration system performance under overall modes. Appl. Energy 185, 2074–2084 (2017)
Fang, Y.; Croquer, S.; Poncet, S.; Aidoun, Z.; Bartosiewicz, Y.: Drop-in replacement in a R134 ejector refrigeration cycle by HFO refrigerants. Int. J. Refrig. 77, 87–98 (2017)
Yataganbaba, A.; Kilicarslan, A.; Kurtbas, I.: Exergy analysis of R1234yf and R1234ze as R134a replacements in a two evaporator vapour compression refrigeration system. Int. J. Refrig. 60, 26–37 (2015)
Tashtoush, B.; Alshare, A.; Al-Rifai, S.: Performance study of ejector cooling cycle at critical mode under superheated primary flow. Energy Convers. Manag. 94, 300–310 (2015)
Huang, B.; Chang, J.; Wang, C.; Petrenko, V.: A 1D analysis of ejector performance. Int. J. Refrig. 22, 354–364 (1999)
Calm, J.M.; Hourahan, G.C.: Refrigerant data summary. Eng. Syst. 18(11), 74–88 (2001)
Acknowledgements
This work was supported by the Scientific Research Support Fund in Jordan (Grant No. ENE/02/02/2012).
Author information
Authors and Affiliations
Corresponding author
Rights and permissions
About this article
Cite this article
Tashtoush, B., Bani Younes, M. Comparative Thermodynamic Study of Refrigerants to Select the Best Environment-Friendly Refrigerant for Use in a Solar Ejector Cooling System. Arab J Sci Eng 44, 1165–1184 (2019). https://doi.org/10.1007/s13369-018-3427-4
Received:
Accepted:
Published:
Issue Date: