Introduction

Heat transfer improvement methods can be classified in one of two categories: active (e.g. application of external energy) and passive (e.g. modifications to the surface area, influence of the flow, or enhancement of fluid properties with various additives). This paper focuses on the last of above-mentioned passive methods: the introduction of nanoparticles that improve thermal properties of the base heat transfer fluid.

Prior to nanomaterials, attempts were made to create sustainable suspensions with microparticles. They did not reach expectations due to poor stability and tendency for clogging of channels, which noticeably increased pumping power [1, 2]. Using nanoparticles (solid particles with at least one dimension less than 100 nm) instead of microparticles seems to be a promising solution to rheological problems. Resulting suspensions are called nanofluids.

Nanofluids improve heat transfer coefficients in thermal systems. As a consequence of the tininess of the nanoparticles and their large specific surface area, a small volume fraction of particles leads to thermal improvement. Although viscosity increases when fluids are doped with nanoparticles, the negative effect is smaller than the possible enhancement of thermal conductivity [3].

The interest in nanofluids has grown substantially since their introduction by Choi and Eastman in 1995 [4]. They potentially overcome the greatest limitation of the base liquid (i.e. low thermal conductivity in comparison with solids) and thus allow for the development of high-performance heat transfer fluids [1, 2, 5, 6]. Most of the research on nanofluids focused on the heat transfer, pressure drop, and energy analysis [1, 2, 7,8,9,10,11,12,13,14,15]. These main performance parameters depend on broadly researched fundamental properties like thermal conductivity, viscosity, density, and specific heat capacity [3, 16,17,18,19,20,21,22,23]. Most recently, Estellé et al. [24] reviewed studies on surface tension and wetting behaviour of nanofluids which are key parameters for understanding heat transfer during boiling.

Many papers on graphene (GF) and graphene oxide (GO) nanoparticles have been published since it was first isolated in 2004, but only a fraction discusses graphene-based nanofluids [1, 7, 8, 21, 25,26,27,28,29]. In this group, only a few works contemplate graphene nanofluids as working fluids for thermosyphons and heat pipes [27,28,29]. Published results are case-depended and difficult to generalise because even small deviations in a synthesis method, duration of sonification, or the presence of surfactant change thermophysical properties and affect stability of the final suspension [30].

Two-phase closed thermosyphon (TPCT)

A two-phase closed thermosyphon is a sealed tube filled with properly selected working fluid. The device consists of three sections: evaporator section, adiabatic section, and condenser section (Fig. 1). Working fluid boils due to heat supplied to the evaporator from the external source. Vapour flows through the adiabatic section to the above-located condenser section where heat is released to the cooling medium. Condensed liquid returns to the evaporator section due to gravity.

Fig. 1
figure 1

Scheme of the two-phase closed thermosyphon

The main purpose of using nanofluids in thermosyphons is to lower overall thermal resistance of the device below what is possible with a pure working fluid. Few explanations for this effect can be found in the literature, e.g. enhanced thermal properties of nanofluids, nanoparticle interaction with the heater surface, and altered boiling process [1, 2, 31]. It was confirmed that nanofluids do not affect the thermal behaviour of the condenser [5, 6].

Several reviews on operation and application of thermosyphons employing nanofluids have been published in recent years [2, 7, 8, 10, 25, 26], but only a few investigations discussed graphene-based nanofluids [6, 27,28,29]. Azizi et al. [27] showed experimentally that a graphene nanofluid stabilised with a gum arabic increased thermal efficiency of thermosyphon of 10% compared with water. Amiri et al. [28] found that adding graphene nanoplatelets to water improved heat transfer efficiency. Thermal resistance was lowered with an increase in both power input and concentration. Enhancements of thermophysical properties of nanofluids were more significant for covalent nanofluids (the acid-functionalised nanoplatelet–water nanofluid) than for non-covalent ones (functionalised with sodium dodecyl benzene sulphonate SDBS). Kim and Bang [6] investigated the influence of graphene oxide nanofluids on heat pipe performance. Thermal resistance was lowered by about 25% compared with water. The results were better for a concentration of 0.01 vol% than for 0.03 vol%. The authors suggested that this was due to densely packed deposition which reduced permeability of the wick. No effect was registered in the condenser section. Nazari et al. [29] studied a pulsating heat pipe filled with graphene oxide nanofluid. Thermal resistance was decreased by up to 42% with the addition of GO, but an optimum of its concentration existed (0.25 g L−1). It was caused by the increase in dynamic viscosity which had a crucial impact on the operation of the pulsating heat pipe. The summary of previous research on heat pipes employing graphene-based nanofluids is presented in Table 1.

Table 1 A summary of previous research on heat pipe employing graphene-based nanofluids

As the results are scarce, it is necessary to study the effects that drive behaviour of graphene oxide-based nanofluids in thermosyphons.

Effects

In this work, we closely study three factors that influence operation of the TPCT: deposition of nanoparticles on the heat transfer surface, occurrence of geyser boiling, and the influence of surfactants.

Deposition of nanoparticles

During boiling, nanoparticles tend to form layers on the heated surface. The mechanism responsible for such deposition is probably a microlayer evaporation, as proposed by Kim et al. [32] and later experimentally confirmed by Kwark et al. [33]. The layer of liquid between the heated surface and the growing bubble evaporates quickly causing local increases in concentration and decreases in distance between nanoparticles. As a consequence, nanoparticles that were initially contained in a microlayer build a porous layer on the heated surface.

Distribution of particles depends on their hydrophilicity [16]. Initially, strongly hydrophobic nanoparticles are distributed uniformly in the droplet and evaporation takes place mostly at the vapour–liquid boundary. Liquid flows outward from the centre of the droplet to its edge carrying suspended nanoparticles. In result, nanoparticles get highly concentrated along the boundary, which phenomenon is called the coffee ring effect [34]. Moderately hydrophobic particles are distributed in loosely packed structures on the vapour–liquid interface. Inter-particle interactions deform interfaces and prevent particles from reaching the drop edges producing irregular and much rougher deposition layer than strongly hydrophobic particles [16].

Geyser boiling

Geyser boiling is a kind of instantaneous boiling where the working fluid gathered above a bubble is propelled to the condenser section [35, 36]. The problem of geyser boiling often remained unnoticed, and there were only a few mentions of it in the available literature [37,38,39,40]. There is only one study of geyser boiling occurring in thermosyphons filled with gold nanofluids [41], and no study on graphene oxide nanofluids.

Geyser boiling (or the geyser effect) in thermosyphons is schematically shown in Fig. 2. It consists of four phases: superheating of the working fluid in the evaporator (a), development and quick growth of the bubble (b), bubble expansion and propulsion of the fluid located above the bubble, even up to the top of condenser [5, 36] (c), and return of the displaced liquid (d). The cycle repeats itself.

Fig. 2
figure 2

Scheme of geyser boiling. Phases ad as follows: superheating of the working fluid in the evaporator (a), bubble development and its quick growth of the bubble (b), bubble expansion and propulsion of the fluid located above the bubble, even up to the top of condenser [5, 36] (c), and downfall return of the displaced liquid (d)

The amplitude and frequency of geyser boiling depend on working conditions, including heat load, working fluid, geometry of the device, its inclination angle, and filling ratio [37,38,39]. The phenomena occur at low pressures, for large filling ratios, or during start-ups and are classified as two-phase compound relaxation instability [40].

Influence of surfactants

Till now, in the literature, little attention was paid to the influence of surfactants on heat transfer of carbon-based nanofluids during boiling [28, 42]. Several hints can be found in more general papers on thermophysical properties of nanofluids themselves.

Shanbedi et al. [43] experimentally determined thermophysical properties of carbon nanotubes in the presence of three different surfactants: sodium dodecyl sulphate (SDS), cetyl trimethylammonium bromide (CTAB), and gum arabic (GA). They found that surface tension of nanofluids decreased with the rise in temperature and SDS concentration. Viscosity decreased with increasing concentration of surfactant and for higher temperatures under constant share rate. Density decreased with increasing temperature, and there were almost no effects caused by addition of a surfactant.

Huminic et al. [19] determined the influence of surfactant on properties of nanofluids based on FeC. The authors found that thermal conductivity of surfactant/water solution (water with 3 g L−1 CMCNa) was similar to pure water what suggests that the possible enhancement in thermal conductivity was due to the presence of nanoparticles. The situation was different when considering viscosity. The addition of surfactant into water increases its viscosity; thus, the viscosity of nanofluids was affected by both nanoparticles and the chemical additive. The authors showed that although the surface tension of surfactant solution was considerably lower than the one of water, the surface tension may change diversely when considering nanofluids. For small concentrations of FeC particles (0.1 mass % and 0.5 mass %), the surface tension was lower than the one of water. But when 1.0 mass % was employed, the surface tension exceeded the value for water.

Summary

In this paper, we study the performance of graphene oxide (GO) nanofluids in a thermosyphon. In the following sections, we analyse GO nanofluids behaviour with and without the addition of sodium dodecyl sulphate (SDS) and compare the results with two reference fluids: pure water and SDS water solution (without GO particles).

Firstly, we determined to what degree GO nanofluids affected the thermal resistance of the TPCT and how the presence of surfactant impacted its operation. Secondly, we studied the influence of boiling process on the medium-term stability of GO nanofluid and deterioration of GO nanoparticles. Finally, we analysed the occurrence and consequences of geyser boiling in the TCPT. The latter was possible thanks to especially located high-resolution pressure gauges that allowed us to register and record any occurrences of geyser boiling. The influence of boiling process on graphene oxide flakes was studied using SEM photography of particles that remained in the working fluid after the experiment.

Experimental

Experimental set-up and procedure

All experiments were carried out using a closed-loop two-phase thermosyphon (shown in Fig. 3) made of a 1800-mm copper pipe with an inner diameter of 20 mm and wall thickness of 1 mm, which was insulated with a 20-mm Armaflex shell. Evaporator and condenser sections (each 400 mm long) were wrapped with a coiled copper tube with an inner diameter of 4 mm.

Fig. 3
figure 3

Photograph of the experimental set-up

After evacuation, the thermosyphon was filled with 85 mL of working fluid. Water was used as heating and cooling medium. The inlet and the outlet temperatures were measured with Pt100 - elements with a working range from − 20 °C to + 150 °C and with an accuracy of ± 1/3 (0.3 + 0.005ϑ), where ϑ is the value of the determined temperature. At the highest analysed temperature (85 °C), the maximum uncertainty was equal to ± 0.24 K. Temperatures of the working fluid in the evaporator section were measured with a temperature sensor made according to the specification matching the thermodynamics and the geometry of thermosyphon. It consisted of six Pt100-elements positioned at different heights of the evaporator section (Fig. 3). Their accuracy in the range of temperatures from − 20 °C to +150 °C was ± (0.15 + 0.002ϑ). Thus, considering the highest temperature in the test rig (85 °C), the maximum uncertainty was ± 0.32 K.

Internal pressure was measured at three different positions along the pipe with a measurement range 0–400 Pa and at the top of the device with two different measurement ranges (0–104 and 0–105 Pa) to ensure high resolution of the data. All transmitters worked at a frequency of 1 kHz and an accuracy of ± 0.25%. Volume fluxes of heating and cooling water were measured with magneto-inductive Krohne Optiflux 5100C flow meters. The sample rate was 410 ms. Inlet temperatures of heating and cooling water cycles were provided by two LAUDA Eco RE 1050 GW thermostats with temperature constancy of ± 0.02 K. All the measured parameters were monitored and recorded with a ProfiSignal software.

Volume fluxes of heating and cooling cycles were kept constant at value 12 ± 0.055 l h−1. For each working fluid, two measurement series were conducted with inlet temperatures of cooling water of 15 °C and 25 °C. The temperature of the heating medium leaving the thermostat varied between 30 and 85 °C at 5 K steps. Despite the insulation, we registered heat losses between heat source and the thermosyphon. Thus the maximum inlet temperature of heating water obtained for 85 °C case was 80.56 ± 0.23 °C. Mean temperature of the inlet cooling water was 25.06 ± 0.14 °C for 25 °C case and 14.59 ± 0.12 °C for 15 °C series.

All conducted experiments followed a procedure established in ILK to ensure repeatability and comparability of results. The procedure started with a running-in period. After 30–60 min, inlet temperatures at the evaporator and the condenser, as well as evaporator and condenser volume fluxes, usually reached steady-state operation. From this moment, all measurements were recorded over a period of 60 min. Time averaged data were obtained by integration over the measurement period. Experiments were carried out at set condenser inlet temperature and varying evaporator inlet temperature (at 5 K increments). After experimental series with a given fluid, the thermosyphon was opened and the working fluid was carefully removed for analysis. The interior of the evaporator was inspected using an endoscopic SOMIKON HD camera in order to identify and evaluate the quality of porous layers deposited from nanoparticles. The inner surface of the entire thermosyphon was then carefully cleaned with lint-free flannel and by rinsing with acetone and distilled water. Afterwards, the surface got visually examined again using the camera. Remaining cleaning fluid was extracted by vacuuming. The device was then assumed ready for the next experimental series.

Working fluids

The thermosyphon was filled with two kinds of nanofluids based on graphene oxide (GO). GO flakes were prepared at ITME, Warsaw, Poland by means of a modified Hummers method [44] that is schematically presented in Fig. 4.

Fig. 4
figure 4

Production route of graphene oxide nanofluids

Source graphite material was oxidised chemically through a treatment with a solution of 95% sulphuric acid (proportion of graphite to acid 10 g per 1 L), sodium nitrate (mass ratio to graphite 2:3), and potassium permanganate (mass ratio to graphite 6:1) in the temperature of 50 °C. After oxidation, slurry was diluted in deionised water and H2O2 was added. Hydrogen peroxide acts like an inhibitor for the second stage of an oxidation [45]. This stage of a process is caused by Mn2O7 MnO3+ in diluted acid. The violence of the oxidation process leads to flakes damages. Presence of hydrogen peroxide lowers the oxidation state of manganese, allowing to form Mn2+ ions and manganese sulphate which is well soluble in water.

In the next step, the solution was cleaned in a microfiltration device. The resulting solution of concentrated graphene oxide (GO) was diluted to ensure a concentration of 0.1 g L−1. Half of the nanofluid was enhanced with 0.01 g L−1 of sodium dodecyl sulphate (SDS), and both samples were mixed for 4 h. Part of the samples were used in the thermosyphon, and the remaining ones were further stored for observation. After 4 months of visual monitoring, no optical signs of sedimentation were noticed. There was no difference in external appearance in any of the stored samples. Particles in the samples used in the thermosyphon exhibited sedimentation which is described in detail in “Surface of the evaporator and SEM photographs of particles” section and presented in Fig. 8.

In order to obtain reliable data, all experiments followed the measurement procedure explained in “Experimental set-up and procedure” section. As distilled water was the base fluid in all cases, DI water was also considered as a base line. Additionally, a solution of sodium dodecyl sulphate (SDS) was tested to obtain the reference data for the SDS stabilised nanofluid. The SDS solution contained the same amount of SDS as the graphene oxide nanofluid with SDS. This approach allowed for the separation of effects triggered by nanoparticles and by surfactant. All tested working fluids are presented in Table 2.

Table 2 Fluids used as working fluid in the thermosyphon

Results and discussion

Time averaged data

All results presented in this section are estimated as mean values from experiments lasting one hour. One of the crucial indicators of the heat transfer efficiency of a thermosyphon is its thermal resistance, shown in Fig. 5. It is defined according to [5] as:

$$R_{\text{th}} = \frac{{\bar{t}_{\text{e}} - \bar{t}_{\text{c}} }}{{\bar{Q}_{\text{c}} }},$$
(1)

where \(\bar{t}_{\text{e}}\) and \(\bar{t}_{\text{c}}\) are the mean temperatures of evaporator and condenser, respectively; \(\bar{Q}_{\text{c}}\) is the heat released in the condenser section. The error analysis is based on Gaussian law of error propagation. The maximum values of uncertainty are 0.08 W K−1 for tci = 25 °C series and 0.24 W m−1 K−1 for tci = 15 °C series.

Fig. 5
figure 5

a Thermal resistance of all working fluids in dependency on heat realised in the condenser for condenser temperature of 25 °C. b Thermal resistance of all working fluids in dependency on heat realised in the condenser for condenser temperature of 15 °C. Circles indicate the same inlet temperature of heating medium.

Thermal resistance of the device decreases with the increase in the heat flux and achieves almost a constant value of 0.078 ± 0.003 W K−1 for inlet temperatures of heating medium higher than 55 °C (in case of tci = 25 °C series) and 50 °C (tci = 15 °C series) for all tested fluids. Considerable reduction in thermal resistance caused by nanofluid is visible only at low evaporator temperatures. In this temperature range, the use of nanofluids yields to both lower the thermal resistance of the device and increase the amount of transferred heat.

The difference between red crosses and red squares indicating the same working fluid (GO nanofluid without SDS, 25 °C case) suggests that the results exhibited transient-like characteristics what is in agreement with other studies [33, 46]. The first measurements conducted after filling the device with nanofluid (red cross, GO, 25 °C case) showed thermal resistance approx. 20% lower than in the case of water. Thermal resistance decreased by about 60% compared to water when experiments were repeated after completing the whole first series of measurements (red squares, GO, 25 °C case). At the beginning of each part of experiments, nanoparticles were evenly dispersed, but during boiling they deteriorated and formed layers on the inner surface of the evaporator. Certain amount of time was required to see the effect because boiling heat transfer improvement was caused mainly by a GO coating on the surface.

Inspection with an endoscopic camera indicated that the inner surface of the evaporator was coated with a GO layer (see Fig. 8 right). Such deposition of nanoparticles influences surface roughness in three ways depending on the size of nanoparticles and initial roughness of surface [31]:

  • nanoparticles size is smaller than the surface roughness—nanoparticles fill the surface cavities and reduce therewith the surface roughness,

  • nanoparticles size is smaller than the characteristic length scale of surface roughness, but the difference is not that significant (e.g. nanoparticle size 47 nm and characteristic length scale of roughness 0.524 mm)—the number of active nucleation sites is multiplied by splitting single cavities into several nucleation sites,

  • size of nanoparticles or its agglomerates is greater than cavities—surface roughness and number of nucleation sites may change diversely.

By these effects, the wettability of the surface alters [31, 47]. Moreover, the density of the nucleation sites stimulating phase change may increase [5], which in turn further accelerates boiling process. A next effect—increasing the evaporator surface available for the boiling process by depositing nanoparticles—is ruled out as cause of an increased heat transfer. The reason is that the surface increase by deposited nanoparticles is tiny compared with the uncoated evaporator surface. However, with the experimental technique employed here it was not possible to examine these effects en detail.

In the case of porous layer deposition, the interplay of wettability and porosity is called wickability [13]. Deposited nanolayers influence chemistry and structure of the base surface and modify the force balance at the triple line. All mentioned factors have a crucial impact on characteristics of the heat transfer process during boiling [13, 31, 48, 49]. No effect was found in the condenser section what agrees with previous studies [5, 42].

Reduction of GO occurs at approx. 50–60 °C; thus, it takes place during boiling. Although reduced graphene oxide (rGO) is hydrophobic, it can still absorb water into its structure after some period of time [50] leading to capillary wicking. This observation agrees with measurements of graphene oxide–water nanofluids conducted by Kamatchi et al. [17], before and after boiling on both smooth and rough surfaces. The study confirmed dual wettability of rGO caused by activation of the carboxyl groups on the flake surface. Contact angle decreased with time for all tested cases. In result, permeability increased, creating proper conditions for capillary wicking [50, 51].

Graphene oxide has high thermal conductivity (up to 3500–5300 W m−1 K−1 [52, 53]) and surface area (736 m2g−1 [54] or even up to 2630 m2 g−1 [53]). Particles deposited on the heating surface form a thermal bridge between the wall and working fluid. It worked well for low heat loads where the thermal conductivity played a more important role than for high temperatures. Here, a well-developed boiling process was the main mechanism of heat transport.

The amount of heat transferred by the thermosyphon changed for various working fluids, even if all other working conditions remain the same. Figure 6 presents the degree of an enhancement obtained for a given fluid QcNF compared to the base value determined for water Qc, ref:

$$\Delta q_{\text{c}} = 100 \% \left( {\frac{{Q_{{{\text{c}},{\text{nf}}}} }}{{Q_{{{\text{c}},{\text{ref}}}} }} - 1} \right) .$$
(2)
Fig. 6
figure 6

a Increase in heat transferred by different working fluids compared to water in dependency of evaporator inlet temperature (upper: 25 °C case). b. Increase in heat transferred by different working fluids compared to water in dependency of evaporator inlet temperature (15 °C case)

Enhancement was achieved only for an inlet temperature of the heating medium below 50 °C for both series. The highest improvement was obtained for pure GO nanofluid. GO + SDS nanofluid presented a slight progression compared to the SDS solution for the low values of tei. Both fluids showed values lower than those for water; however, the trend was not as stable as for GO series. The real inlet temperature of heating water (tei) was almost constant for all the fluids; thus, the differences in results were not caused by additional variations in external conditions.

The boiling curves are shown in Fig. 7. They denote heat supplied to the evaporator in dependence of the overheating at the evaporator wall. Overheating is the difference between temperature of the evaporator wall and the boiling temperature at a given pressure. GO nanofluid affected the boiling regimes occurring in the device. For small heat loads, boiling curves were shifted to the left, which means that more heat was removed from the surface at the same temperature or that the surface temperature was lower. When the overheating exceeded the values of 10 K (for tci = 25 °C) or 13 K (tci = 15 °C), there were no noticeable differences in data for different working fluids. GO + SDS nanofluid behaved similar to water. Exept an inlet temperature of the heating medium equal to 50 °C and 55 °C and cooling medium of 15 °C, where two parallel states of boiling were obtained. The device switched between these two states without any pattern, which was not seen in any other experimental series. It was probably caused by reduction of GO which may happen at given temperatures.

Fig. 7
figure 7

a Boiling curves for inlet temperature in condenser of 25 °C. b Boiling curves for inlet temperature in condenser of 15 °C

Surface of the evaporator and SEM photographs of particles

Deposited GO/rGO particles are exposed as a black porous layer in Fig. 8 (right). A photograph taken inside the thermosyphon with an endoscopy camera shows a porous layer found approx. 200 mm from the bottom of the device. Energy-dispersive spectrometer (EDS) analysis carried out by Kim et al. [55] confirmed that layers formed during the boiling of nanofluids are indeed made of nanoparticle material.

Fig. 8
figure 8

Samples before and after use (left picture). First two are GO (0.1 g L−1) nanofluid without SDS; the second ones are with SDS addition (0.01 g L−1). Porous layer formed on inner surface of the evaporator after GO nanofluid boiling (right picture)

Figure 8 (left) presents fluids taken out from the device after finishing all the experiments compared to the fresh ones. The change of colour, as well as agglomerated particles that were not stuck to the wall, is easily noticeable. The sheet shape of graphene oxide was destroyed, as presented in Fig. 9. Figure 9a shows SEM photographs of diluted and dried fresh material, while Fig. 9b–d presents nanoparticles removed from the device after experiments. Shapes and sizes of the structures became very irregular. They were either similar to a sponge or few connected sheets like graphene paper or other chaotic texture. Crystals visible in Fig. 9d are the SDS that attached to the flakes of graphene oxide. It inhibited strong interaction between particles and evaporator wall which resulted in worse thermal capacity of the device employing GO-SDS than pure GO nanofluid.

Fig. 9
figure 9

SEM pictures of GO particles: a fresh sheets, bc GO structures after experiments, d GO-SDS after experiments

Time-dependent data

Although no significant differences in averaged thermal capabilities of the device are reported for high temperatures in the evaporator, time-dependent behaviour in this region highly depended on the employed working fluid (Fig. 10). Water and graphene oxide nanofluid behaved in similar ways, and phase transition occurred through geyser boiling for high heat loads. In general, the amplitude and frequency of the events depended on both temperatures, in the evaporator and in the condenser. An increase in temperature difference between evaporator and condenser resulted in shorter and less intensive geysers.

Fig. 10
figure 10

a Time-dependent pressure data at p3 for water, SDS solution, and GO + SDS nanofluid (tci = 25 °C, tei = 80 °C). b Time-dependent pressure data at p3 for water, SDS solution, and GO + SDS nanofluid (tci = 15 °C, tei = 65 °C)

Employment of SDS solution prolonged periods of boiling between geysers at lower temperatures and completely prevented sudden events at the highest heat fluxes (see tci = 25 °C, tei = 85 °C case, Fig. 10 upper middle plot). SDS, which is an anionic surfactant, reduces surface tension. According to the visualisation reported by Wang et al. [56], two mechanisms during boiling of surfactant may happen: bubble bursting and a strong jet flow phenomena. The first one prevents formation of large bubbles expelling further towards the condenser due to lower surface tension. The second deals with the traces of small bubbles ejected from the main bubble that appeared on the heater surface. After splitting, the main bubble decreases and dry-out spots are eliminated. When at least two unstable bubbles appear in a short distance from each other, the bubbles merge. After coalescence, surfactant molecules transfer to the connection point. Due to significant decrease in surface tension at this point, the merged bubble expands rapidly, which results in an explosion at the point with the lowest surface tension. Both mechanisms lead to smaller dry-out spots, more intense disturbance, and, as a result, improved heat transfer. Due to reduced surface tension, less energy is required to create the bubble and activation of nucleation sites in a clustered mode is promoted. It engenders higher bubbles departure frequency (affected also by cavity–cavity interaction, microlayer evaporation, and coalescence of bubbles), a more vigorous boiling process, and smaller bubble diameters [56, 57].

Unexpectedly, graphene oxide nanofluid stabilised with the same concentration of SDS did not follow the behaviour of the surfactant solution. Geyser boiling appeared again with similar amplitude and slightly lower frequency than for water. From Fig. 9d, we suspect that the surfactant was no longer present in the fluid (or its concentration was significantly reduced) due to possibility of SDS attachment to the surface of graphene flakes. As any other thermophysical property, surface tension of nanofluids depends on nanoparticle content (concentration) and additional surfactant content. It is known from experimental determination of surface tension of GO nanofluids that surface tension is lowered [10, 24]. Most recently, Cabaleiro et al. [21] showed that the addition of graphene oxide particles with concentration between 0.0005 and 0.1 vol% without surfactant causes the decrease in surface tension with a maximum reduction of about 3%. Based on these findings, an influence of nanoparticle and surfactant content of the working fluid on the surface tension and therewith on the boiling process can be expected. Thus, SDS attachment to the flakes reduced its influence on the surface tension of fluid and consequently on the boiling process. This shows that the chemistry of the particle plays an important role in preventing geyser boiling.

Geyser boiling may influence the process of nanolayer deposition. Because the boiling process is volatile and intermittent, it is not clear whether the microlayer evaporation takes place in the pool. However, centrifugal splashing of fluid caused by the geyser event produced similar results when the narrow fluid film dries out on the wall. We found traces of the nanoparticles about 200 mm to 400 mm above the bottom of the evaporator (working fluid at rest reached about 270 mm). The location suggests that both mechanisms actively contribute to formation of the layer.

Conclusions

An experimental study on thermosyphon employing graphene oxide (0.1 g L−1) nanofluids with and without the addition of surfactant (sodium dodecyl sulphate, SDS) is conducted. Results are compared with a baseline data obtained for distilled water and SDS water solution. The main findings are as follows:

  • GO nanofluids improved heat transfer capabilities of the thermosyphon, but the effect was noticeable only at low temperatures of the evaporator section. Exchanging a traditional working fluid (like water) with a water-based nanofluid leaded to a shift of the working point. This took place even if inlet temperatures and the volume fluxes in heating/cooling coils were kept unchanged.

  • For high heat loads, the difference between thermal performances of analysed fluids was negligible, regardless of the presence of nanoparticles.

  • The nanofluid did not influence heat transfer in the condenser. The positive influence of the nanofluid on heat transfer was limited to the evaporator section.

  • Heat transfer improvement was caused by the deposited layer on the inner surface of the evaporator. The layer affects not only the roughness but also the surface energy, wettability, and surface tension at the evaporator wall.

  • Although there were almost no differences in transport heat capabilities for the high heat fluxes, the time-dependent behaviour of tested fluids was substantially different. For water and graphene oxide nanofluid, the main boiling regime for high temperatures of the evaporator was geyser boiling. The phenomenon was inhibited by the SDS because the surfactant reduced surface tension. It prevented the formation of large bubbles expelling working fluid towards the condenser.

  • The surface chemistry of GO nanoparticles played a key role in avoiding geyser boiling. Even though the graphene oxide nanofluid was stabilised with SDS, it did not prevent geyser boiling because most of the SDS was attached to the surface of the GO flakes. In result, there was not enough surfactant in the solution to suppress geyser formation.

  • The amplitude and the frequency of geysers depended on temperatures in the evaporator and condenser sections. Increases in temperature difference between evaporator and condenser led to shorter and less intensive geysers.

  • Geyser boiling did not affect overall thermal resistance of the device for high heat load region.

  • Non-dimensional representation of the boiling curves which would be based on similarity numbers relevant for the effects observed in the thermosyphon does not exist. This is at least partly due to the fact that boiling regimes are changing when increasing the provided amount of heat at the evaporator.