Keywords

1 Introduction

Slab intrados deterioration and crumbling is one of the most frequent issues in Italian buildings built in the second half of the last century. The phenomenon is due to the presence of compression stresses that are normal to the joists direction in the slab clay hollow blocks. Compression stresses occur due to several reasons, among which thermal dilation, corrosion of the reinforcing bars, hogging moment due to plate effects, water infiltration, and so on, are the most significant. This scenario is frequent in the case of seismic events, with serious consequences for the building occupants.

Fiber-reinforced composite materials were recently introduced to the construction engineering community and were proven to be an effective solution for the strengthening and retrofitting of existing structures. Fiber-reinforced polymers (FRP) have been studied extensively over the last few decades and are largely employed to strengthen existing reinforced concrete (RC) structures (Bakis et al. 2002). However, due to the presence of organic resins, FRP composites present a number of drawbacks (e.g. lack of vapor permeability, low resistance at relatively high temperatures, and difficulties of application on wet substrates) and are poorly compatible with concrete and masonry substrates (de Felice et al. 2014). To overcome these issues, composite materials made by high-strength fibers embedded within inorganic matrices were proposed. Among them, those including high-strength open-mesh textiles with yarn spacing lower than or equal to 30 mm are referred to as fiber (or fabric) reinforced cementitious matrix (FRCM) or textile-reinforced mortar (TRM) composites (ACI 549.4R 2013; CNR-DT 215 2019). FRCM/TRM composites have been gaining increasing attention due to their effective compatibility with substrates, vapor permeability, partial reversibility, and resistance to relatively high temperatures (de Felice et al. 2014).

Recently, new types of inorganic-matrix strengthening materials, comprising a composite grid embedded within an inorganic-matrix and referred to as composite-reinforced mortar (CRM) materials, have been employed to strengthen the existing masonry structures (D’Antino et al. 2019). The grids used in CRMs are made by composite yarns in the warp direction and pultruded elements in the weft one. Usually, the composite yarns are twisted together and around the pultruded elements to realize a stable bi-directional grid (Fig. 1). The spacing between the yarns may vary and is higher than 30 mm. The cross-sectional area of the laminated and pultruded elements is often higher than that of textile-reinforced mortars’ fiber textile yarns (Carozzi et al. 2017; D’Antino et al. 2019).

Fig. 1
figure 1

Glass fiber grid (left); strengthening of a slab intrados with a glass CRM (right)

In this paper, a study on the efficiency of three glass composite grids designed as the reinforcement of CRM material, employed for preventing the intrados crumbling hazard, is presented and discussed. The grid contribution to the vertical load induced by the intrados failure (crumbling) was studied by 16 experimental punching tests on different types of specimens simulating horizontal slab, namely a timber slab and a pre-stressed RC slab lightened with hollow clay elements. The glass composite grid was fixed at the slab intrados using anchors. The effect of grid spacing, anchorage types, and grid discontinuity on the system load-bearing capacity is investigated. The glass grid studied appears to be an efficient solution to solve intrados crumbling hazards. Owing to the speed of the intervention, it is particularly attractive for applications in public buildings, such as educational buildings, since they cannot remain closed for long periods of time.

2 Mechanical Characterization of the Glass CRM

Three different geometries (layouts) of an impregnated glass fiber composite grid, namely grids with a mesh size of 40 × 40 mm, 40 × 80 mm, and 80 × 80 mm, are analyzed in this study.

Although the grids are all comprised of the same laminated yarns and pultruded elements, the different spacing entails for a different number of twists of the yarns, which in turn may affect the tensile properties of the grid. However, for the sake of brevity, only the mechanical characterization of the 40 × 40 mm grid is reported in this paper. The square grid is made up of rectangular GFRP pultruded weft yarns and two-wire GFRP warp strands (Fig. 1). The cross-sectional area of weft and warp yarns is 5.97 and 5.71 mm2, respectively.

To measure the grid tensile properties (i.e. tensile strength, elastic modulus, and ultimate strain) in warp and weft direction, tensile tests were performed on warp and weft single-yarn specimens, extracted from the grid, with a length of 700 mm. The tests were displacement-controlled using a servo-hydraulic testing machine equipped with a 100 kN load cell. To improve the specimen gripping by the machine, steel tabs were applied to the specimens ends. An extensometer with a gauge length of 50 mm was used to measure the specimen strain during the test.

The stress–strain curves resulting from the experimental tests are reported in Fig. 2 for weft and warp specimens. The curves showed a linear-elastic behavior up to the brittle specimen failure, which is associated with the glass fiber tensile strength. For some warp specimens, a load drop associated with the failure of a small portion of the twisted bundles was observed close to the peak load. This behavior is caused by the fiber twisting in warp specimens, which caused stress concentrations where the fibers deviate from linearity. The failure load Fmax and the corresponding maximum stress σmax obtained by each test, together with the elastic modulus E, are reported in Table 1.

Fig. 2
figure 2

Stress–strain curves for weft and warp single-yarn specimens

Table 1 Results of tensile tests on glass fiber weft and warp yarns

3 Experimental Program

A total of 16 tests were performed on two different specimens simulating horizontal slabs strengthened with the glass composite grid described in Sect. 2. Ten tests were conducted on specimens simulating a one-way timber slab, strengthened with the 40 × 80 mm or the 80 × 80 mm grid, whereas the remaining six tests were conducted on a pre-stressed RC slab including hollow clay elements, which was strengthened with either the 40 × 40 mm, the 40 × 80 mm, or the 80 × 80 mm grid.

Specific steel anchors were employed to fix the composite grid to the slab intrados. These steel anchors consist of one expandable anchor and a 50 mm diameter steel washer and were applied at a distance of 500 mm from one another. The role of the anchors in the specimen load bearing capacity was investigated by varying a number of parameters: (i) washer material (steel or PE); (ii) local strengthening of the anchor with the application of a single mesh of 40 × 40 mm composite grid below the steel washer (Fig. 3).

Fig. 3
figure 3

Anchorage type: anchor with PE washer (left) and anchor with steel washer strengthened using a single mesh of 40 × 40 mm composite grid

The tests were conducted in displacement control with a rate of 10 mm/min using a hydraulic jack with a capacity of 100 kN. To accommodate possible differential displacements or rotations of the slab, the hydraulic jack was equipped with a spherical joint. The vertical displacement of the slab and of the grid was measured with linear variable displacement transducers (LVDTs).

The timber slab was simulated by two laminate timber joists supported by rigid steel supports (Fig. 4). The cross-sectional area of the timber joists was 240 (height) × 120 (width) mm and the center-to-center distance between them was 600 mm. The composite grid was fixed to the joist intrados and the load was applied directly onto it by two contiguous timber footprints with areas of 400 × 400 mm (Fig. 4). Two separate load footprints were employed to simulate the contemporary crumbling of two separated hollow clay elements. In these tests, the hydraulic jack was connected to a steel distribution beam. The timber footprints were connected with spherical joints to the steel distribution beam (Fig. 4) and the load was transferred from the jack to the glass composite grid. Four LVDTs were used to measure the vertical displacement at each joist midspan and under the center-point of the footprints. To investigate the effect of grid discontinuity, four tests were conducted on specimens strengthened with two separate grids superimposed for 160 mm at midspan (Fig. 4). Furthermore, two tests were carried out to analyze the behavior of the different anchors on the grid bearing capacity.

Fig. 4
figure 4

Tests on strengthened timber slabs (dimensions in mm)

The pre-stressed RC slab with hollow clay elements was composed of four pre-stressed concrete joists with a center-to-center spacing of 480 mm fixed to a rectangular steel frame (Fig. 5). The joists supported hollow clay elements placed between the joists themselves. The load was applied to the glass grid with a single timber footprint of dimensions 240 × 350 mm through the space of the central hollow element, which was removed. The composite grid was fixed to the joist soffit with either eight steel anchors (specimens type a in Table 2) or four (specimens type b in Table 2) on each of the central joists, spaced at 500 mm (Fig. 6).

Fig. 5
figure 5

Cross-section of the pre-stressed RC joists and hollow clay elements

Table 2 Test results
Fig. 6
figure 6

Tests on strengthened pre-stressed RC slabs (dimensions in mm)

One linear variable displacement transducer was placed under the load footprint to measure the vertical displacement. The vertical deflection of the slab was not measured since it was negligible with regards to grid displacement. To investigate grid capacity, three tests were conducted with the weft yarns aligned with the joists’ longitudinal axis and three tests with the warp yarns aligned with the joists’ longitudinal axis.

4 Results and Discussion

The results of the experimental tests are reported in Table 2. Specimens were named according to the notation Q_XY_Z_d_A_n, where Q (equal to T = “timber” or C = “pre-stressed RC”) indicates the slab type, X and Y are the grid spacing (in cm) in weft an warp direction, respectively, Z is the number of grid layer applied (2 in the case of discontinuous grids), d (equal to a = weft direction aligned with the slab joist or b = warp direction aligned with the slab joist) indicates the grid orientation, A (equal to S = “standard”, W = “PE washer”, or R = “steel washer”) indicates the anchor type, and n is the specimen number.

Table 2 reports the maximum load, bearing capacity (i.e. the maximum applied load divided by the area of a single footprint), and the associated vertical displacement. Figure 7 shows the load–displacement curves for timber slabs strengthened with grids with 40 × 80 mm and 80 × 80 mm mesh. All the specimens show an initial approximately linear behavior, which ends with a marked load drop associated with the shear failure of one of the weft or warp yarns close to one of the anchors (Fig. 8). After this load drop, with increasing displacement, the applied load further increased in some cases and remained approximately constant in others due to stress redistribution in the grid bundles.

Fig. 7
figure 7

Load–displacement curves of timber slabs strengthened with a single continuous grid and two discontinuous grids

Fig. 8
figure 8

Typical grid shear failure at anchor positions

Specimens strengthened with discontinuous grids showed similar load bearing capacity, although a decrease of the maximum load was observed for some specimens (see Table 2). Also in these tests, the stress redistribution in the grids allowed for an increase in the applied displacement maintaining or even increasing the applied load. This behavior is particularly important in the case of seismic events because it may prevent the sudden collapse of the slab intrados.

All specimens eventually failed due to grid shear rupture close to the anchors due to stress concentrations at the grid warp–weft joints. To decrease the stress concentration at the joints, a single 40 × 40 mm grid mesh was inserted under the steel washer (Fig. 3). In addition, the steel washer was substituted with a PE washer to investigate the effect of washer stiffness on the response obtained. Figure 9 shows the load responses of timber slabs strengthened with a single continuous grid with 80 × 80 mm mesh with different anchorages (i.e. different washers and the addition of the strengthening single grid mesh). The results show that the different anchorages proposed did not significantly affect the specimen bearing capacity.

Fig. 9
figure 9

Load–displacement curves for timber slabs with different anchors

The results of the tests conducted on pre-stressed RC slabs are reported in Fig. 10. Specimens strengthened with the 40 × 40 mm grid showed a higher bearing capacity for specimens with warp laminated yarns oriented orthogonally to the slab joist direction with respect to specimens with weft pultruded elements oriented orthogonally to the slab joist direction. As observed for timber slabs, pre-stressed RC slabs strengthened with 40 × 80 mm and 80 × 80 mm grids provided similar results (Fig. 10).

Fig. 10
figure 10

Load–displacement curves for pre-stressed RC slabs

5 Conclusions

This paper described the results of 16 experimental punching tests on different specimens simulating horizontal slabs, namely timber and pre-stressed RC slabs, strengthened with a glass fiber-reinforced polymer (FRP) grid designed as the reinforcement of a composite-reinforced mortar (CRM). The tests were designed to obtain information on the efficiency of a glass FRP grid in preventing and contrasting the occurrence of slab intrados failure and crumbling. The parameters investigated were the grid spacing, anchorage types, and grid discontinuity. The results obtained showed that a shear failure of a grid bundle close to one anchor always occurred. However, this bundle failure did not determine the specimen failure, because the stress redistribution in the grid allowed for maintaining and in some cases increasing the applied load. All grid spacings (40 × 40 mm, 40 × 80 mm, and 80 × 80 mm) demonstrated similar behavior. The different anchors studied (i.e. steel anchors with steel and PE washer and with the addition of a single mesh grid strengthening below the washer) did not significantly affect the behavior observed. Finally, the grid discontinuity did not significantly affect the load-bearing capacity.

The results obtained showed that the glass grid studied is an efficient solution to solve intrados crumbling hazards and, due to the speed of the intervention, is particularly attractive for applications in public buildings, such as educational buildings, which cannot remain closed for long period.