Study on attached ventilation based on inclined walls

  • Research Article
  • Published:
Building Simulation Aims and scope Submit manuscript

Abstract

In practical engineering, inclined building walls are often presented due to their functional and aesthetic needs. A reasonable air distribution design is essential for creating a satisfactory indoor environment in such buildings. In the present study, inclined walls with a variable inclination angle β were used as the research object to explore a novel air supply mode. Visualization experiments and numerical simulations were conducted to investigate the induced airflow, such as the airflow pattern, the airflow characteristics (maximum jet velocity decay and jet spreading rate) and the ventilation effect (vertical air temperature difference, draft rate, air diffusion performance index). The results show that the “air lake” phenomena occurred over the floor, which resembles the displacement ventilation to some extent. The proposed air supply mode has a good ventilation effect and could be applied to building spaces with inclined walls. The current study can be used as a reference for ventilation design in buildings with inclined walls.

This is a preview of subscription content, log in via an institution to check access.

Access this article

Price excludes VAT (USA)
Tax calculation will be finalised during checkout.

Instant access to the full article PDF.

Similar content being viewed by others

References

  • Aganovic A, Steffensen M, Cao G (2019). CFD study of the air distribution and occupant draught sensation in a patient ward equipped with protected zone ventilation. Building and Environment, 162: 106279.

    Google Scholar 

  • Ahn H, Rim D, Lo LJ (2018). Ventilation and energy performance of partitioned indoor spaces under mixing and displacement ventilation. Building Simulation, 11: 561–574.

    Google Scholar 

  • Al Assaad D, Ghali K, Ghaddar N (2019). Effect of flow disturbance induced by walking on the performance of personalized ventilation coupled with mixing ventilation. Building and Environment, 160: 106217.

    Google Scholar 

  • Alsaad H, Voelker C (2020). Qualitative evaluation of the flow supplied by personalized ventilation using schlieren imaging and thermography. Building and Environment, 167: 106450.

    Google Scholar 

  • ASHRAE (2017a). ANSI/ASHRAE Standard 55: Thermal Environmental Conditions for Human Occupancy. Atlanta, GA, USA: American Society of Heating, Refrigerating, and Air-conditioning Engineers.

    Google Scholar 

  • ASHRAE (2017b). ASHRAE Handbook: Fundamentals. Chapter 20, Space Air Diffusion. Atlanta, GA, USA: American Society of Heating, Refrigerating, and Air-conditioning Engineers.

    Google Scholar 

  • Awbi HB (2003). Ventilation of Buildings, 2nd edn. London: Taylor and Francis.

    Google Scholar 

  • Bauman FS, Dally A (2003). Underfloor air distribution (UFAD) design guide. American Society for Electroplated Plastics

  • Beltaos S, Rajaratnam N (1973). Plane turbulent impinging jets. Journal of Hydraulic Research, 11: 29–59.

    Google Scholar 

  • Boyle R (1899). Natural and Artificial Methods of Ventilation. London: Robert Boyle & Son.

    Google Scholar 

  • Cao G, Sirén K, Kilpeläinen S (2014). Modelling and experimental study of performance of the protected occupied zone ventilation. Energy and Buildings, 68: 515–531.

    Google Scholar 

  • Cao G, Nielsen PV, Jensen RL, Heiselberg P, Liu L, Heikkinen J (2015). Protected zone ventilation and reduced personal exposure to airborne cross-infection. Indoor Air, 25: 307–319.

    Google Scholar 

  • Chen Q (1995). Comparison of different k-ε models for indoor air flow computations. Numerical Heat Transfer, Part B: Fundamentals, 28: 353–369.

    Google Scholar 

  • Chen HJ, Moshfegh B, Cehlin M (2013). Investigation on the flow and thermal behavior of impinging jet ventilation systems in an office with different heat loads. Building and Environment, 59: 127–144.

    Google Scholar 

  • Chludzińska M (2019). The effect of front pattern perforation shape on thermal sensations of occupants in personalized ventilation systems. Building and Environment, 151: 140–147.

    Google Scholar 

  • Coanda H (1936). Device for deflecting a stream of elastic fluid projected into an elastic fluid. United States Patent 2052869.

  • Haghshenaskashani S, Sajadi B (2018). Evaluation of thermal comfort, IAQ and energy consumption in an impinging jet ventilation (IJV) system with/without ceiling exhaust. Journal of Building Engineering, 18: 142–153.

    Google Scholar 

  • Karimipanah T, Awbi HB (2002). Theoretical and experimental investigation of impinging jet ventilation and comparison with wall displacement ventilation. Building and Environment, 37: 1329–1342.

    Google Scholar 

  • Li Y, Leung GM, Tang JW, Yang X, Chao CYH, et al. (2007). Role of ventilation in airborne transmission of infectious agents in the built environment? a multidisciplinary systematic review. Indoor Air, 17: 2–18.

    Google Scholar 

  • Li AG, Qiu SH, Wang GD (2008). Vertical wall attached airflow and air lake mode ventilation system. China patent, ZL 200810017349.0, 2008. (in Chinese)

  • Li AG, Yin HG, Wang GD (2012). Experimental investigation of air distribution in the occupied zones of an air curtain ventilated enclosure. International Journal of Ventilation, 11: 171–182.

    Google Scholar 

  • Li A (2019). Extended Coanda Effect and attachment ventilation. Indoor and Built Environment, 28: 437–442.

    Google Scholar 

  • Li A, Hou Y, Yang J (2019). Attached ventilation based on a curved surface wall. Building Simulation, 12: 505–515.

    Google Scholar 

  • Lin Z, Chow TT, Tsang CF, Fong KF, Chan LS (2009). Stratum ventilation—A potential solution to elevated indoor temperatures. Building and Environment, 44: 2256–2269.

    Google Scholar 

  • Lin Z, Yao T, Chow TT, Fong KF, Chan LS (2011). Performance evaluation and design guidelines for stratum ventilation. Building and Environment, 46: 2267–2279.

    Google Scholar 

  • Makhoul A, Ghali K, Ghaddar N (2013). Desk fans for the control of the convection flow around occupants using ceiling mounted personalized ventilation. Building and Environment, 59: 336–348.

    Google Scholar 

  • Meng X, Wang Y, Liu T, Xing X, Cao Y, Zhao J (2016). Influence of radiation on predictive accuracy in numerical simulations of the thermal environment in industrial buildings with buoyancy-driven natural ventilation. Applied Thermal Engineering, 96: 473–480.

    Google Scholar 

  • Miller P (1977). Room air diffusion systems design techniques. The air diffusion performance index. ASHRAE Journal, 19(4): 37–40.

    Google Scholar 

  • Seppänen O (2008). Ventilation strategies for good indoor air quality and energy efficiency. 6: 297–306.

    Google Scholar 

  • Sundell J, Levin H, Nazaroff WW, Cain WS, Fisk WJ, et al. (2011). Ventilation rates and health: multidisciplinary review of the scientific literature. Indoor Air, 21: 191–204.

    Google Scholar 

  • Taheri M, Schuss M, Fail A, Mahdavi A (2016). A performance assessment of an office space with displacement, personal, and natural ventilation systems. Building Simulation, 9: 89–100.

    Google Scholar 

  • Tian L, Lin Z, Wang Q (2011). Experimental investigation of thermal and ventilation performances of stratum ventilation. Building and Environment, 46: 1309–1320.

    Google Scholar 

  • Yang C, Li A, Gao X, Ren T (2020). Interaction of the thermal plumes generated from two heat sources of equal strength in a naturally ventilated space. Journal of Wind Engineering and Industrial Aerodynamics, 198: 104085.

    Google Scholar 

  • Ye X, Kang Y, Zuo B, Zhong K (2017). Study of factors affecting warm air spreading distance in impinging jet ventilation rooms using multiple regression analysis. Building and Environment, 120: 1–12.

    Google Scholar 

  • Yin H (2012). Study on design procedures of air distribution by air curtain ventilation with a linear slot diffuser. PhD Thesis, Xi’an University of Architecture and Technology, China. (in Chinese)

    Google Scholar 

  • Yin H-G, Li A-G (2012). Airflow characteristics by air curtain jets in full-scale room. Journal of Central South University, 19: 675–681.

    Google Scholar 

  • Yin H, Li A (2016). Study of attached air curtain ventilation within a full-scale enclosure: comparison of four turbulence models. Indoor and Built Environment, 25: 962–975.

    Google Scholar 

  • Yin H, Li A, Liu Z, Sun Y, Chen T (2016). Experimental study on airflow characteristics of a square column attached ventilation mode. Building and Environment, 109: 112–120.

    Google Scholar 

  • Yin H, Wu R, Chen T, Sun Y, Li A (2017). Study on ventilation effectiveness of circular column attached displacement ventilation mode. Procedia Engineering, 205: 3511–3518.

    Google Scholar 

  • Yuan X, Chen Q, Glicksman LR (1998). A critical review of displacement ventilation. ASHRAE Transactions, 104(1): 78–90.

    Google Scholar 

  • Zhai ZJ, Metzger ID (2019). Insights on critical parameters and conditions for personalized ventilation. Sustainable Cities and Society, 48: 101584.

    Google Scholar 

  • Zhang WD (2002). Prediction and visualizing validation of downward directed vertical wall jets and air lake phenomena. Master Thesis, Xi’an university of Architecture and Technology, China. (in Chinese)

    Google Scholar 

  • Zhuang R, Li X, Tu J (2014). CFD study of the effects of furniture layout on indoor air quality under typical office ventilation schemes. Building Simulation, 7: 263–275.

    Google Scholar 

  • Zukowski M (2007). A new formula for determining a minimum recommended value of inlet air velocity from uFAD system to prevent occupants from draught risk. Building and Environment, 42: 171–179.

    Google Scholar 

  • Zuo B, Zhong K, Kang Y (2015). An experimental study on particle resuspension in a room with impinging jet ventilation. Building and Environment, 89: 48–58.

    Google Scholar 

Download references

Acknowledgements

This paper was supported by the National Natural Science Foundation of China (No. 50778145, No. 51478377).

Author information

Authors and Affiliations

Authors

Corresponding author

Correspondence to Angui Li.

Rights and permissions

Reprints and permissions

About this article

Check for updates. Verify currency and authenticity via CrossMark

Cite this article

Hou, Y., Li, A., Yang, J. et al. Study on attached ventilation based on inclined walls. Build. Simul. 14, 667–679 (2021). https://doi.org/10.1007/s12273-020-0662-x

Download citation

  • Received:

  • Revised:

  • Accepted:

  • Published:

  • Issue Date:

  • DOI: https://doi.org/10.1007/s12273-020-0662-x

Keywords

Navigation