Abstract
This study aimed to evaluate the pressure difference distribution across the escape stair in a 24-story stairwell. A large eddy simulation (LES) method was used to model the pressure in a stairwell model with a set of simulation parameters using FDS (Fire Dynamic Simulator) software. Two configurations of fans involved single injection, and multiple fan injection is observed. A Single-injection fan is located on the highest point of the stair. The double injection system consists of two fans and is separated at 45 m at each other. When the fire alarm is activated, the pressurization fan automatically runs and delivered outdoor air to the stairwell. It is commonly acknowledged that the pressure would start to built-up in the stairwell before the occupants entering the stair by open the door. Besides, when the pressure is significantly high, the door is unable to be open from outside by occupants as a consequence. In order to overcome this issue, a pressure relief damper was then installed on the top of the stair. The numerical study shows possible pressure difference in the stairwell is about 50 and 95 Pa. However, a multi injection system has the advantages of proper pressure distribution along the stairwell. Performance-based design by using numerical computation is a valuable tool to predict the engineering system and presents a better understanding of how the system would perform in design.
Access this chapter
Tax calculation will be finalised at checkout
Purchases are for personal use only
Similar content being viewed by others
References
Tamura GT, Wilson AG (1964) Air leakage measurements on two occupied houses. ASHRAE Trans 70:110–119
Thomas PH (1970) Movement of smoke in horizontal corridors against an airflow. Inst Fire Eng Q 30(77):45–53
Hansen ND, Stevenson FB, Valkist M et al (2018) Movement of smoke in horizontal corridors against an airflow. Inst Fire Eng Q 30(77):45–53
Jensen L (2003) Stairwell flow pressurization—a new method. J Fire Prot Eng 13(4):251–274
Klote JH (2004) Tenability and open doors in pressurized stairwells. ASHRAE Trans 110(7):613–637
Chen YL, Shicheng DW (2010) Application analysis of wind speed method in mechanical smoke control volume flow rate calculation. Fire Sci Technol 29(11):958–961
Acknowledgements
The authors would like to thank the financial support provided by the Ministry of Research, Technology, and Higher Education of the Republic of Indonesia through Penelitian Terapan Unggulan Perguruan Tinggi (PTUPT) 2019–2020 funding scheme managed by the Directorate for Research and Public Services (DRPM) Universitas Indonesia.
Author information
Authors and Affiliations
Corresponding author
Editor information
Editors and Affiliations
Rights and permissions
Copyright information
© 2022 The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd.
About this paper
Cite this paper
Alianto, B., Nasruddin, Nugroho, Y.S. (2022). Numerical Study on the Effect of Single and Multi-injection Pressurized Fan in Enclosed Stairwell of High-Rise Building. In: Yola, L., Nangkula, U., Ayegbusi, O.G., Awang, M. (eds) Sustainable Architecture and Building Environment . Lecture Notes in Civil Engineering, vol 161. Springer, Singapore. https://doi.org/10.1007/978-981-16-2329-5_12
Download citation
DOI: https://doi.org/10.1007/978-981-16-2329-5_12
Published:
Publisher Name: Springer, Singapore
Print ISBN: 978-981-16-2328-8
Online ISBN: 978-981-16-2329-5
eBook Packages: EngineeringEngineering (R0)