Influence Analysis of the Grounding Grid of Communication Tower Base on Lightning Signal

  • Jin Yang
  • Zhiyu Li
Conference paper
Part of the Lecture Notes in Electrical Engineering book series (LNEE, volume 482)

Abstract

Communication tower is often close to machine room. When the lighting strikes the communication tower, it raises electrical potential of grounding grid and transient ground potential raise could damage weak electrical equipment in machine room. In order to solve this problem, in this paper, a response calculation model under the condition of the lightning transient was established, which was based on the construction drawing of a communication tower and machine room grounding grid in Bao-Lan PDL (Passenger Dedicated Line). This model analyzed potential changes under the conditions of various factors when the lightning current injected grounding grid, including two grounding grid is equipotent connected or not, different distances and soil resistivity between two grounding grid, etc. Computational results show that transient ground potential of the machine room can reduce by 70% when the distance of two grounding grid increased from 5 to 20 m, and transient ground potential can be 10 times higher when two grounding grid is equipotent connected. Finally, the propose suggestions related to requirements engineering based on these analysis.

Keywords

Communication tower Lightning Grounding grid Machine room 

References

  1. 1.
    Ruan W, Ma J, Liu J et al (2002) Performance of HVDC ground electrode in various soil structures. In: Proceedings of IEEE 2002 international conference on power system technology, vol 2. EEE, New York, pp 962–968Google Scholar
  2. 2.
    Zhang L, Yuan J (2000) Numerical calculation of substation grounding grid with unequal potential model. In: Proceedings of the Chinese society for electrical engineering, vol 20, issue (1), pp 1–3 (in Chinese)Google Scholar
  3. 3.
    Du Z, Wang J, Liu X (2007) Analysis of the performance of the grounding UHVDC ring. High Voltage Eng 32(12):146–149 (in Chinese)Google Scholar
  4. 4.
    Ge W, Ruan B (1990) Recursion formula of the electric field of the ground point source in the vertical multi-layer dielectric. J Guilin Coll Metall Geol 10(2):173–181 (in Chinese)Google Scholar
  5. 5.
    Ge W (1994) Analysis of point source electric field in layered medium and its application. Chin J Geophys 37(II):534–541 (in Chinese)Google Scholar
  6. 6.
    Dawalibi FP, Ma J, Southey RD (1994) Behaviour of grounding systems in multilayer soils: a parametric analysis. IEEE Trans Power Deliv 9(1):334–342CrossRefGoogle Scholar
  7. 7.
    Guo W, Wen X, Tan J (2013) Calculation method of grounding parameters of grounding grids using fast multipole method. Power Syst Technol 37(3):753–758 (in Chinese)Google Scholar
  8. 8.
    Liu Y, Zitnik M, Thottappillil R (2001) An improved transmission-line model of grounding system. IEEE Trans Electromagn Compat 43(3):348–355CrossRefGoogle Scholar

Copyright information

© Springer Nature Singapore Pte Ltd. 2018

Authors and Affiliations

  1. 1.Beijing National Railway Research & Design Institute of Signal & Communication Co., Ltd.BeijingChina

Personalised recommendations