For many under-development countries, hybrid generation systems are the solution which could satisfy various requirements of power generation including availability, renewability and cost. The authors presented a procedure to evaluate the performance and economy of a hybrid system of wind, photovoltaic (PV) and Micro Gas Turbine (MGT) with the required battery capacity in a remote area in South Africa as a test case in [1] and suggest optimization to size of a hybrid system of all resources.

The optimization of the power plant can be considered in two groups of conventional and new generation methods [2]. The conventional methods include the trade-off approaches, iterative approaches, linear and mixed integer linear programming. The new generation approaches, on the other hand, integrate mathematical models with the computer programs in the heuristic manner to obtain a solution [3].

To find the optimum size of a hybrid system with solar PV and wind generators, a harmony search method is employed in [4]. In this order, several configurations are defined as “Harmony”. Sizes of solar PV generators and wind turbines, as well as estimated costs of the system, are specified in each harmony. Considering optimization targets, discrete search technique employed to find the solution.

In current study, Levelized Cost of Electricity (LCOE) [5] and load following of the generation system is considered as the target objects. The procedure is adopted in a rural area near Cape Town, South Africa and to apply direct optimization, solution domain of all scenarios using defined available sources is constructed. Various aspects of scenarios are investigated. Then, Pareto front technique is employed to obtain the optimum solution.

2 Theory and Methodologies

To define the solution domain, combinations of Capstone MGT30, MGT65 and MGT 200S with 0 to 4 wind turbine of 100 kW power are considered. The size of Solar PV in each configuration is obtained based on the assumption of providing at least 90% of the demand load in the worst month of each scenario. Therefore, 45 scenarios are extracted which are listed in Table 22.1.

Table 22.1 Available scenarios

Since there are a finite number of scenarios, the direct optimisation technique is employed to find the solution. In this method, techno-economic parameters of all scenarios are evaluated which make it possible to select the global optimal solution. Various parameters could be defined to show the performance, cost and availability of the system among which annual generation, Levelized Cost of Electricity (LCOE), load following deviation, nominal capacity, number of days with 1 hour shortage or blackout, and renewability of the hybrid generation system is considered to trim unpractical scenarios.

LCOE are selected as the objectives for the optimization process that means the desired hybrid power plant not only have to track the demand load profile but also provide the electricity in minimum LCOE. To quantify the load following behaviour, least square of the difference between monthly load demand and generation is considered as the deviation parameter.

Based on the objectives’ characteristics which are in contrary to each other the Pareto Front approach is applied to find the optimum. This method which is illustrated schematically in Fig. 22.1 generally employed when minimising one of the targets yields to increase of the other ones. Any of the scenarios which are places on the Pareto front could be selected as an optimum solution regarding the weight of each target for a project.

Fig. 22.1
figure 1

The Pareto front in a multi-objective optimisation domain

3 Results and Discussion

A rural area near Cape Town is considered as a case study in this article and extracted techno-economic parameters of all 45 scenarios are plotted in Fig. 22.2. It is obviously clear that some of the scenarios generate several times higher than the annual required load. Therefore, to achieve a better optimization domain, some of them are ignored by applying two following constraints:

Fig. 22.2
figure 2

Techno-economic parameters of all scenarios

  • Size: Annual generation of the system should be less than 2,500,000 kWh.

  • Availability: There should be no days with more than 1 h no generation situation.

  • Renewability: Utilization of renewable sources should be more than 20% of overall generation.

Although the values for these constrain are specified, other values or constraints may be added due to the condition of a project. The remaining scenarios are indicated in Table 22.2. All of the scenarios with no MGT are eliminated because of the availability constrains and the others eliminated by size and renewability ones. In remaining scenarios, some of them benefit from only two sources which means those do not include either any wind turbine or any solar PV. In Fig. 22.3 these two-source system are compared with the three-source systems in optimization targets domain which shows the effect of hybridization in improving both technical and economic aspects of the system.

Multi-objective optimization domain of the remaining 24 scenarios as well as the illustration of Pareto line is plotted in Fig. 22.4. Pareto front is passing through three following scenarios:

  1. 1-

    MGT 30 kW, WT 2 × 100 kW, PV 490 kW, Battery 1640 kWh

  2. 2-

    MGT 65 kW, WT 2 × 100 kW, PV 220 kW, Battery 1800 kWh

  3. 3-

    MGT 2 × 65 kW, WT 100 kW, PV 170 kW, Battery 1530 kWh

It could be seen that by increasing the size of the MGT, the load following behaviour of the system is improved but the LCOE is increased. Load following of these three optimum solutions is also plotted in Fig. 22.5 which shows more deviation in small MGT scenario.

Table 22.2 Remaining scenarios after applying size, availability and renewability constraints
Fig. 22.3
figure 3

Comparison between two-source and three-source systems

Fig. 22.4
figure 4

Multi-objective domain and Pareto front

Fig. 22.5
figure 5

Load following deviation of the selected scenarios

This Pareto front provides optimum solutions based on the selected targets as well as required data for decision makers. Having all optimum solution in hand, one may consider weights for each target and select the most appropriate one based on especial condition of the project.

4 Conclusion

Techno-economic parameters of all available solutions employing 30, 65 and 200 kW MGTs, as well as 0 to 4 sets of wind turbine in combination with appropriate solar PV, are evaluated. Applying size, availability and renewability constraints, some of the scenarios were eliminated. Among the remaining ones, load following behaviour and LCOE were considered as the target and the multi-objective Pareto front was obtained. It was shown that combining both three resources yields to enhancement of the overall techno-economic parameters of the system. The authors recommend that this procedure could be improved by employing a wider range of wind turbines. The criteria of suppling at least 90% of monthly loads to size the solar PV could also be investigated.