Abstract
Plasma ionization and heating, in the Frascati Tokamak, is obtained generating an emf along the plasma column, by switching the dc current flowing in the Tokamak transformer.30 kA flowing in the 60 mH transformer inductance must be commutated into a resistance to generate 40 kV across the transformer itself.
Studies and tests to solve this problem have been conducted, on different types of breakers, in cooperation between Tecnomasio Italiano Brown Boveri, Milan and Laboratori Gas Ionizzati, Frascati.
Satisfactory results have finally been obtained using a DLF commercial air blast breaker in a chopper type circuit.
A capacitor bank in parallel to the breaker is discharged immediately after the contacts separation and the arc in the switching element is estinguished at the first current zero. A saturable reactance in series with the breaker reduces the current decay rate to allow sufficient deionization time.
Access this chapter
Tax calculation will be finalised at checkout
Purchases are for personal use only
Preview
Unable to display preview. Download preview PDF.
Author information
Authors and Affiliations
Editor information
Editors and Affiliations
Rights and permissions
Copyright information
© 1976 Plenum Press, New York
About this chapter
Cite this chapter
Andreani, R., Lovisetto, L., Vittadini, G. (1976). Frascati Tokamak Transformer Switching System. In: Bostick, W.H., Nardi, V., Zucker, O.S.F. (eds) Energy Storage, Compression, and Switching. Springer, Boston, MA. https://doi.org/10.1007/978-1-4684-2214-6_53
Download citation
DOI: https://doi.org/10.1007/978-1-4684-2214-6_53
Publisher Name: Springer, Boston, MA
Print ISBN: 978-1-4684-2216-0
Online ISBN: 978-1-4684-2214-6
eBook Packages: Springer Book Archive