Theoretical Evaluation of Energy Performance of a Vapour Compression Refrigeration System Using Sustainable Refrigerants

  • Sharmas Vali Shaik
  • T. P. Ashok Babu
Conference paper
  • 42 Downloads
Part of the Smart Innovation, Systems and Technologies book series (SIST, volume 169)

Abstract

The chief goal of this present investigation is to evaluate performance parameters of various sustainable refrigerants as R22 alternatives. In this investigation apart from R290, R134a and R22, twelve mixture refrigerants were developed at various composition. Results showed that energy efficiency ratio (EER) of mixture refrigerant MR40 (R290/R134a 95/5 in mass%) (4.546) stood greatest among twelve investigated alternatives and it was closer to the EER of R22 (4.602). Compressor discharge temperature of MR40 was lower than R22 by 16.020C. Volumetric refrigeration capacity of MR40 (3424 kJ/m3) was relatively lesser than R22 (3801 kJ/m3). Power spent per ton of refrigeration (PPTR) of MR40 (0.773 kW/TR) stood lowest among twelve investigated alternatives and it was fairly greater than R22 (0.764 kW/TR). Global warming potential (GWP100) of MR40 (68) was very low compared to R22 (1760). Overall, performance of MR40 was closer to R22, when compared with all the twelve investigated alternatives, and hence, it might be treated as a suitable replacement to refrigerant R22.

Keywords

Discharge temperature Energy efficiency ratio GWP R22 alternatives Volumetric refrigeration capacity 

References

  1. 1.
    Mohanraj, M., Jayaraj, S., Muraleedharan, C.: Environment friendly alternatives to halogenated refrigerants-a review. Int. J. Greenh. Gas Control. 3, 108–119 (2009)CrossRefGoogle Scholar
  2. 2.
    United Nations Environmental Programme: Montreal Protocol on Substances that Deplete the Ozone Layer, Final Act. United Nations, New York (1987)Google Scholar
  3. 3.
    Powell, R.L.: CFC phase out; have we met the challenge. J. Fluorine Chem. 114, 237–250 (2002)CrossRefGoogle Scholar
  4. 4.
    Devecioğlu, A.G., Oruça, V.: Characteristics of some new generation refrigerants with low GWP. Energy Proc. 75, 1452–1457 (2015)CrossRefGoogle Scholar
  5. 5.
    Chen, W.: A comparative study on the performance and environmental characteristics of R410A and R22 residential air conditioners. Appl. Therm. Eng. 28, 1–7 (2008)CrossRefGoogle Scholar
  6. 6.
    Arora, A., Kaushik, S.C.: Theoretical analysis of a vapour compression refrigeration system with R502, R404A and R507A. Int. J. Refrig. 31, 998–1005 (2008)CrossRefGoogle Scholar
  7. 7.
    Devotta, S., Padalkar, A.S., Mali, K.V.: Low GWP refrigerants as alternatives to HCFC-22 in room air conditioners. Sci. Technol. Built Env. 22, 1128–1135 (2016)CrossRefGoogle Scholar
  8. 8.
    Calm, J.M., Domanski, P.A.: R-22 replacement status. ASHRAE J. 46, 29–39 (2004)Google Scholar
  9. 9.
    Devotta, S., Padalkar, A.S., Sane, N.K.: Performance assessment of HCFC-22 window air conditioner retrofitted with R-407C. Appl. Therm. Eng. 25, 2937–2949 (2005)CrossRefGoogle Scholar
  10. 10.
    Oruc, V., Devecioglu, A.G.: Thermodynamic performance of air conditioners working with R417A and R424A as alternatives to R22. Int. J. Refrig. 55, 120–128 (2015)CrossRefGoogle Scholar
  11. 11.
    Oruc, V., Devecioglu, A.G., Berk, U., Vural, I.: Experimental comparison of the energy parameters of HFCs used as alternatives to HCFC-22 in split type air conditioners. Int. J. Refrig. 63, 125–132 (2016)CrossRefGoogle Scholar
  12. 12.
    ASHRAE Handbook Fundamentals: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, USA (2017)Google Scholar
  13. 13.
    Dalkilic, A.S., Wongwises, S.: A performance comparison of vapour-compression refrigeration system using various alternative refrigerants. Int. Commun. Heat Mass. 37, 1340–1349 (2010)CrossRefGoogle Scholar
  14. 14.
    Bolaji, B.O., Huan, Z.: Computational analysis of the performance of ozone-friendly R22 alternative refrigerants in vapour compression air-conditioning systems. Environ. Prot. Eng. 38, 41–52 (2012)Google Scholar
  15. 15.
    Bolaji, B.O., Huan, Z.: Performance investigation of some hydro-fluorocarbon refrigerants with low global warming as substitutes to R134a in refrigeration systems. J. Eng Thermophys. Rus. 23, 148–157 (2014)CrossRefGoogle Scholar
  16. 16.
    Lemmon, E.W., Huber, M.L., McLinden, M.O.: Reference fluids thermodynamic and transport properties-REFPROP 9.1. National Institute of Standards and Technology (NIST), Standard Reference Database 23, Gaithersburg, MD, Boulder, USA (2013)Google Scholar
  17. 17.
    Tian, Q., Cai, D., Ren, L., Tang, W., Xie, Y., He, G., Liu, F.: An experimental investigation of refrigerant mixture R32/R290 as drop-in replacement for HFC410A in household air conditioners. Int. J. Refrig. 57, 216–228 (2015)CrossRefGoogle Scholar

Copyright information

© Springer Nature Singapore Pte Ltd. 2020

Authors and Affiliations

  • Sharmas Vali Shaik
    • 1
  • T. P. Ashok Babu
    • 1
  1. 1.Department of Mechanical EngineeringNational Institute of Technology KarnatakaSurathkal, MangaloreIndia

Personalised recommendations