Abstract

In this investigation, the measurement thermal parameters and thermal comfort field survey were carried in six air-conditioned hospitals in Guangzhou. A total of 114 valid questionnaires were collected. Based on the data, there were strong linear regression relationships between PMV and MTSV and operative temperature. The neutral temperature was 24.39 °C from the linear regression of MTSV. The thermal comfort temperature which meets a satisfaction degree of 90% or 80% ranges from 22.83 to 25.94 °C, 21.74 to 27.03. In addition, the neutral operation temperature was 23.75 °C from the PMV model. The thermal comfort temperature which meets a satisfaction degree of 90% or 80% ranges from 22.00 to 25.50 °C, 20.77 to 26.73. Comparing the MTSV and PMV, the MTSV was lower than that of PMV. The preference Top was obtained by Probit regression analysis curve intersection point was 24.43 °C. By Actual Percentage Dissatisfaction obtains 90% or 80% of the medical staff acceptable comfort temperature upper limit of 24.71 °C, 25.53 °C.

Keywords

Medical staff Predicted Mean Vote (PMV) Neutral temperature 

Notes

Acknowledgements

This work is supported by the Opening Funds of State Key Laboratory of Building Safety and Built Environment and National Engineering Research Center of Building Technology, No.BSBE2018-03.

Ethical approval All procedures performed in studies involving human participants were in accordance with the ethical standards of the institutional and/or national research committee and with the 1964 Helsinki declaration and its later amendments or comparable ethical standards.

Informed consent Informed consent was obtained from all individual participants included in the study.

References

  1. 1.
    ASHRAE.: ANSI/ASHRAE Standard 55-2013: Thermal Environmental Conditions for Human Occupancy, Atlanta, GA (2013)Google Scholar
  2. 2.
    World Health Organization: Environmental Health in Rural and Urban Development and Housing Unit, Indoor Environment: Health Aspects of Air Quality, Thermal Environment, Light and Noise. World Health Organization, Geneva (1990)Google Scholar
  3. 3.
    Zhao, A.Z.: Hospital building indoor air quality status and energy saving solutions. Build. Thermal Ventilation 157–160 (2011)Google Scholar
  4. 4.
    Wang, Z.J.: Selection of Thermal Comfort Index in Field Study, pp. 39–42. HVAC, US (2004)Google Scholar
  5. 5.
    Sattayakorn, S., Ichinose, M., Sasaki, R.: Clarifying thermal comfort of healthcare occupants in tropical region: a case of indoor environment in Thai hospitals. Energy Build. 149, 45–57 (2017)CrossRefGoogle Scholar
  6. 6.
    Derksa, M.T.H., Mishraa, A.K.: Understanding thermal comfort perception of nurses in a hospital ward work environment. Build. Environ. 140, 119–127 (2018)CrossRefGoogle Scholar

Copyright information

© Springer Nature Singapore Pte Ltd. 2020

Authors and Affiliations

  1. 1.Department of Civil EngineeringGuangzhou UniversityGuangzhouChina

Personalised recommendations