Power Quality Improvements in a Novel 24-Pulse Line Commutated Converter HVDC Transmission System

  • Sabah Ramadhan Mohammed
  • Jiashen Teh
  • Mohamad KamarolEmail author
Conference paper
Part of the Lecture Notes in Electrical Engineering book series (LNEE, volume 547)

Abstract

The paper reports the investigation of the dynamic operation of novel 24-pulse HVDC transmission system for eliminating the 11th and 13th harmonic currents from spreading out to the AC system and improving power quality. The complete simulation of the 24-pulse HVDC system is performed using the MATLAB/Simulink. Simulation results show that the Total Harmonic Distortion (THD) of AC system in 12-pulse system is 8.51%. Whereas, the THD of AC system in 24-pulse system is 4.49%. The waveforms of AC current have improved without employing 11th and 13th tuned filters at AC systems.

Keywords

HVDC transmission 24-pulse HVDC converter Power quality 

References

  1. 1.
    Kim, C.-K., Sood, V.K., Jag, G.-S., Lim, S., Lee, S.: HVDC Transmission Power Conversion Applications in Power Systems. Wily, Singapore (2009)Google Scholar
  2. 2.
    Miyairi, S., Iida, S., Nakata, K., Masukawa, S.: New method for reducing harmonics involved in input and output of rectifier with interphase transformer. IEEE Trans. Ind. Appl. 1A-22(5), 790–797 (1986)Google Scholar
  3. 3.
    IEEE Standard 519.: IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems. IEEE Inc., New York (1992)Google Scholar
  4. 4.
    Abbas, A.M., Lehn, P.W.: PWM based VSC-HVDC systems-a review. In: Proceedings of IEEE International Conference. PES Conference, Calgary AB, Canada, 26–30 July, pp. 1–9 (2009)Google Scholar
  5. 5.
    Panchbhai A., Shab, H., Nizami, N.: Analog control of closed loop 24 pulse rectifier (Simulation and Hardware). In: IEEE Conference on Energy Conversion (CENCON), Johor Bohru, Malaysia, 19–20 October, pp. 277–282 (2015)Google Scholar
  6. 6.
    Gaonkar, A.D., Rane, R.G., Wagh, S.R., Singh, N.M.: Multi-winding phase-shifting transformer for 36-pulse rectifier: winding turns design and analysis. In: IEEE International Conference. North American Power Symposium (NAPS), Denver, Co, USA, 18–20 September (2016)Google Scholar

Copyright information

© Springer Nature Singapore Pte Ltd. 2019

Authors and Affiliations

  • Sabah Ramadhan Mohammed
    • 1
  • Jiashen Teh
    • 1
  • Mohamad Kamarol
    • 1
    Email author
  1. 1.School of Electrical and Electronic EngineeringUniversiti Sains MalaysiaNibong TebalMalaysia

Personalised recommendations