1 Introduction

Chillers are among the most important cooling equipment that can generally be divided into two categories of compression and absorption chillers. Absorption chillers are classified in two types; water–lithium bromide cycle in which water is considered as a refrigerant and lithium bromide as an absorbent, and ammonia–water cycle whose refrigerant is ammonia and absorbent is water. Compression chillers use electrical energy while absorption chillers use thermal energy as an energy alternative to produce cooling. Absorption chillers have two main superiorities when they are compared with the compression chillers which are; the use of renewable energy as an input alternative such as solar energy, geothermal and heat lost from industrial processes, and their compatibility with the environment [1, 2]. Nowadays, environmental concerns about ozone depletion and global warming, on the one hand, and surplus energy consumption, rising fuel prices, etc., on the other hand, have made the absorption chillers more attractive to researchers. Absorption chillers are very suitable tools for reducing electric energy consumption and recovering waste heat from industrial plants [1,2,3,4]. Simulations are way very important tools for researchers to predict the performance of absorption chillers at the dynamic level with low cost. Coupling any renewable energy device to the chiller is easily performed without any cost.

Many papers have been so far published in the field of dynamic simulation of absorption refrigeration systems. Kohlenbach and Ziegler [5, 6] presented dynamic simulation of the water–lithium bromide absorption chiller based on external and internal steady-state enthalpy balances for each main component. Dynamic behavior of the model was described by mass storage terms in the absorber and generator, thermal heat storage terms in all vessels and a time-delay in the solution cycle. Many researchers conducted dynamic model of the absorption cycle by using the mass and energy conservation and momentum equations [7,8,9,10,11]. Investigation the behavior of the absorption cycle in dynamic mode by applying the step change in the cycle [5, 6, 8, 12, 13] and during start-up [7, 14, 15] have been already carried out. Dynamic simulation of ammonia–water heat pump [8, 16,17,18,19] was accomplished to predict the transient performance and design characteristics as well.

Some researchers have presented dynamic model for absorption chillers by using TRNSYS software and Simulink environment [10, 13, 15, 17, 19,20,21]. Altun and Kilic [20] developed a dynamic model for a 10 KW cooling capacity solar-assisted absorption cycle for different cities of Turkey by TRNSYS software. They conducted a parametric study to investigation the effect of various parameters such as solar collector type, area, storage tank volume, collector slope, boiler set point temperature, room thermostat set point temperature on system efficiency. Their results show that in terms of financial analysis, Izmir is the most suitable city for solar-based absorption cooling system applications with a payback period of 10.7 years. Utilization of the exhaust waste heat of the internal combustion engines for the cooling systems input energy has been done by Wang et al. [21]. They developed dynamic simulation for 3 different cascade waste heat recovery systems listed as an electric-cooling cogeneration system (ECCS), a double-effect absorption refrigeration system, and a double-stage organic Rankine cycle. Also, dynamic response and off-design performance of three aforementioned cases were analyzed and compared. They presented validated module library for building different dynamic models in Simulink and validated by basic thermodynamic cycles.

Arora and Kaushik [22] conducted an energy and exergy analysis of single-effect and double-effect water–lithium bromide absorption cycle in order to examine the effect of heat exchanger efficiency and component’s temperature on some parameters such as; performance coefficient, rate of exergy destruction, and rate of exergy loss. Their analysis relied on the first and second law of thermodynamics using the mass and energy balance for each component. The EES software was applied to solve governing equation. They found that the maximum COP occurs at high generator temperature, and its rise is tied by evaporator temperature and increase in heat exchanger’s efficiency as well. Sozen [23] studied the effect of heat exchanger on the aqua-ammonia absorption chiller’s performance. More to the point, he studied the thermodynamic performance of absorption cycle and the irreversibility of the thermal process for different modes. Parameters such as COP, ECOP, circulation ratio and non-dimensional exergy loss are calculated separately for each component. The concentration of ammonia vapor at the rectifier outlet was set to constant value of 0.999. Later on, Kaynakli and Kilic [24] scrutinized the effect of refrigerant and solution heat exchangers on cycle performance, efficiency ratio and operating temperature. And, the effect of operating temperature and efficiency of heat exchanger on the thermal loads of components, coefficients of performance were also investigated. Their results revealed that the solution heat exchanger could increase the COP value by 44% as well as raising the refrigerant heat exchanger performance by 2.8%. Karamangil et al. [25] studied the thermodynamic analysis of single-effect absorption cycles with different working fluid pairs. Moreover, the influence of operating temperature, refrigerant, solution and solution-refrigerant heat exchanger efficiency on system performance were investigated. They concluded that the solution heat exchanger causes significant increase in the absorption cycle COP and its percentage stands at 66%, and in case of solution-refrigerant and refrigerant heat exchanger, this percentage reaches at 14% and 6%, respectively.

Previous studies [16,17,18, 26] only concentrated on the dynamic response under a single working condition. They have not taken into account the issue that how long it takes for a system to reach a new steady-state condition when system conditions change. Also, researchers, Refs. [22,23,24,25], studied the effect of refrigerant and solution heat exchangers and heat exchanger’s efficiency on the performance of the absorption cycle in the steady state mode while dynamic mode still needs to be investigated. In our previous study, we investigated the effect of sub-cool liquid at condenser/absorber outlet and also, effect of ambient temperature on AC’s key parameters launch time [11]. The general structure and some of input data and initial values of the previous and current research are similar, but the subject that, investigated in this article is different. The main goal of this article is to comparison the start-up time of the key parameters of aqua-ammonia and water–lithium bromide absorption chiller under different heat exchanger configurations.

In this study, the thermodynamic analysis of the both NH3–H2O and H2O–LiBr absorption refrigeration cycle is performed by applying the mass and energy balance, continuity of solution species and momentum equations. The performance of NH3–H2O and H2O–LiBr absorption chillers is compared under different condition, which is not found in the literature. In fact, the aim of this study is to investigate and compare the start-up behavior of NH3–H2O and H2O–LiBr absorption chillers by lumped parameter model under three different cases including; (1) utilizing RHX with SHX in the cycle, (2) removing RHX from the cycle, just SHX plays role in the cycle and (3) removing SHX from the cycle, just RHX plays role in the cycle. Also, the effect of solution heat exchanger’s efficiency on the start-up time of the key parameters of the both ACs is studied and compared. Many researches employed polynomial functions approximation [13, 27,28,29] and EES software [9, 22] to extract the thermodynamic properties of H2O–LiBr solution, and some of them [7, 14, 16, 19, 30] benefited from empirical relations and equations of state to estimate the thermodynamic properties of NH3–H2O solution. In this paper, in order to minimize the deviations resulted from approximated equations, the Engineering Equation Solver (EES) software is used to obtain the thermodynamic properties of the working fluids, and MATLAB software is employed to solve differential equations by fourth order Rung-Kutta method. EES and MATLAB software are linked by an Excel file. To validate dynamic model, the results obtained from this work are compared with the results of the steady state.

2 Dynamic modeling of the system

2.1 Governing equation

Figure 1 shows the schematic of the ammonia–water and water–lithium bromide absorption refrigeration cycle with the refrigerant and solution heat exchangers. The main components of the absorption refrigeration cycle are as follows; evaporator, absorber, generator, condenser, pump, refrigerant and solution heat exchangers. The refrigerant and solution heat exchangers are two important devices in absorption refrigeration cycles. The solution heat exchanger heats the cool solution from the absorber on the way to the generator and cools down the solution returning from the generator to the absorber. Thus, the heat load decreases in the generator and the COP increases. In the refrigerant heat exchanger (condensate pre-cooler), which is in the refrigeration side of the cycle, the refrigerant leaving the condenser is cooled by the vapor coming from the evaporator, and the enthalpy of the liquid decreases. Since the cooling capacity increases, the COP value increases [24].

Fig. 1
figure 1

Schematic of absorption refrigeration cycle with both SHX and RHX (condensate pre-cooler) [31]

The following assumptions are made to simplify the simulation were clearly stated in the literature:

  • Concentration of ammonia vapor at the generator outlet is considered at its constant value of 0.9996 [31, 32].

  • Refrigerant leaves the generator at the state of saturated vapor [9,10,11, 27, 28, 31].

  • Refrigerant leaving the evaporator and condenser is at the state of saturated vapor and saturated liquid respectively [9,10,11, 27, 28, 31].

  • Fluid outlet temperature from each single component is equaled to inside temperature of its component [9,10,11, 27, 28].

  • The amount of work given to the pump is negligible [9,10,11].

  • There is no pressure loss in the pipes [9, 11].

In this study, each component of the absorption cycle is considered as a control volume. Mass, energy balance and momentum equations are used for dynamic analysis. As labeled in Fig. 1, \(M_{i}\)(t) corresponds to the mass within component i, and \(\dot{m}_{i}\)(t) indicates the mass flow rate between components. Subsequently, the overall mass balances for each component are formed by [9, 11]:

$$\frac{d}{dt}\left( {M_{C} } \right) = \dot{m}_{7} - \dot{m}_{8}$$
(1)
$$\frac{d}{dt}\left( {M_{E} } \right) = \dot{m}_{8} - \dot{m}_{10}$$
(2)
$$\frac{d}{dt}\left( {M_{A} } \right) = \dot{m}_{10} + \dot{m}_{6} - \dot{m}_{1}$$
(3)
$$\frac{d}{dt}\left( {M_{G} } \right) = \dot{m}_{1} - \dot{m}_{6} - \dot{m}_{7}$$
(4)
$$\dot{m}_{1} = \dot{m}_{2} = \dot{m}_{3}$$
(5)
$$\dot{m}_{4} = \dot{m}_{5} = \dot{m}_{6}$$
(6)
$$\dot{m}_{8} = \dot{m}_{9}$$
(7)

For aqua-ammonia absorption cycle, \(X_{i}\)(t) is the mass fraction of the ammonia in the component. Subsequently, we have the following absorbent mass balances in the absorber and generator [8, 11]:

$$\frac{d}{dt}\left( {X_{A} } \right) = \left( {\frac{1}{{M_{A} }}} \right)\left[ {\dot{m}_{10} X_{7} + \dot{m}_{6} X_{G} - \dot{m}_{1} X_{A} - X_{A} \left( {\dot{m}_{10} + \dot{m}_{6} - \dot{m}_{1} } \right)} \right]$$
(8)
$$\frac{d}{dt}\left( {X_{G} } \right) = \left( {\frac{1}{{M_{g} }}} \right)\left[ {\dot{m}_{1} X_{A} - \dot{m}_{6} X_{G} - \dot{m}_{7} X_{7} - X_{G} \left( {\dot{m}_{1} - \dot{m}_{6} - \dot{m}_{7} } \right)} \right]$$
(9)
$$X_{A} = X_{1} = X_{2} = X_{3}$$
(10)
$$X_{G} = X_{4} = X_{5} = X_{6}$$
(11)

For water–lithium bromide absorption cycle, \(Z_{i}\) stands for the concentration of H2O–LiBr solution in the absorber and generator. The concentration of solution at the generator and absorber outlet is indicated by \(xl_{i}\) [9].

$$\frac{d}{dt}\left( {Z_{A} } \right) = \left( {\frac{1}{{M_{A} }}} \right)\left[ {\dot{m}_{6} xl_{G} - \dot{m}_{1} xl_{A} - Z_{A} \left( {\dot{m}_{10} + \dot{m}_{6} - \dot{m}_{1} } \right)} \right]$$
(12)
$$\frac{d}{dt}\left( {Z_{G} } \right) = \left( {\frac{1}{{M_{g} }}} \right)\left[ {\dot{m}_{1} xl_{A} - \dot{m}_{6} xl_{G} - Z_{G} \left( {\dot{m}_{1} - \dot{m}_{6} - \dot{m}_{7} } \right)} \right]$$
(13)

The concentration of solution at the exit of generator and absorber in LiBr–H2O absorption chiller is a function of the quality and solution concentration of generator and absorber respectively. The concentrations of solution at the generator and absorber were not assumed to be equal to the corresponding concentration at the exit of those components. The relationship between concentration of solution at the exit of generator and absorber, quality and concentration of solution in components are followed by [9]:

$$z_{i} = x_{Li} \left( {1 - Qu_{i} } \right)$$
(14)

As the quality approaches to zero, the amount of Z will become equal to Xl. This effect is neglected in the NH3–H2O absorption chiller [9].

The momentum equations between the components are given by [8,9,10,11]:

$$\frac{d}{dt}\left( {\dot{m}_{7} } \right) = \left( {\frac{{A_{7} }}{{L_{7} }}} \right)\left[ {P_{G} - P_{C} } \right]$$
(15)
$$\frac{d}{dt}\left( {\dot{m}_{10} } \right) = \left( {\frac{{A_{10} }}{{L_{10} }}} \right)\left[ {P_{E} - P_{A} } \right]$$
(16)
$$\frac{1}{2}\xi_{1} \frac{1}{{\rho_{8} A_{V1}^{2} }}\dot{m}_{8} \left| {\dot{m}_{8} } \right| = P_{C} - P_{E}$$
(17)
$$\frac{1}{2}\xi_{2} \frac{1}{{\rho_{6} A_{V2}^{2} }}\dot{m}_{6} \left| {\dot{m}_{6} } \right| = P_{G} - P_{A}$$
(18)

where \(\xi_{i}\) is the expansion valve friction factor considered constant in this research [7,8,9,10,11]. \(L_{i}\), \(d_{i}\), and \(A_{i}\) are the length, diameter, and cross-sectional area of the pipe, respectively. \(\rho_{i}\) is the density and \(P_{i}\) is the pressure. The smallest cross sectional area of the expansion valve is indicated by \(A_{Vi}\) [11]. Also, it is assumed that the performance of pump in this cycle is evaluated by the polynomial expression obtained from the characteristic curves (Ref. [9]): Table 1, show the constant coefficients of the polynomial and the expansion valve friction factors.

$$P_{G} - P_{A} = a_{0} + a_{1} \dot{m}_{1} + a_{2} \dot{m}_{1}^{2}$$
(19)

Letting \(h_{i}\)(t) be the specific enthalpy, the energy balances for the components are given by [8,9,10,11]:

$$\frac{d}{dt}\left( {h_{C} } \right) = \left( {\frac{1}{{M_{C} }}} \right)\left[ {\dot{m}_{7} h_{7} - \dot{m}_{8} h_{8} - \dot{Q}_{C} - h_{C} \left( {\dot{m}_{7} - \dot{m}_{8} } \right)} \right]$$
(20)
$$\frac{d}{dt}\left( {h_{E} } \right) = \left( {\frac{1}{{M_{E} }}} \right)\left[ {\dot{m}_{8} h_{9} - \dot{m}_{10} h_{10} + \dot{Q}_{E} - h_{E} \left( {\dot{m}_{8} - \dot{m}_{10} } \right)} \right]$$
(21)
$$\frac{d}{dt}\left( {h_{A} } \right) = \left( {\frac{1}{{M_{A} }}} \right)\left[ {\dot{m}_{10} h_{10} + \dot{m}_{6} h_{6} - \dot{m}_{1} h_{1} - \dot{Q}_{A} - h_{A} \left( {\dot{m}_{10} + \dot{m}_{6} - \dot{m}_{1} } \right)} \right]$$
(22)
$$\frac{d}{dt}\left( {h_{G} } \right) = \left( {\frac{1}{{M_{G} }}} \right)\left[ { \dot{m}_{1} h_{3} - \dot{m}_{6} h_{4} - \dot{m}_{7} h_{7} + \dot{Q}_{G} - h_{G} \left( {\dot{m}_{1} - \dot{m}_{6} - \dot{m}_{7} } \right)} \right]$$
(23)
$$h_{5} = h_{6}$$
(24)
$$h_{8} = h_{9}$$
(25)
$$\dot{Q}_{E} = \dot{m}_{17} c_{p} \left( {T_{17} - T_{18} } \right) = UA_{E} \left[ {\frac{{\left( {T_{17} - T_{E} } \right) - \left( {T_{18} - T_{9} } \right)}}{{ln\left( {\frac{{\left( {T_{17} - T_{E} } \right)}}{{\left( {T_{18} - T_{9} } \right)}}} \right)}}} \right]$$
(26)
$$\dot{Q}_{C} = \dot{m}_{15} c_{p} \left( {T_{16} - T_{15} } \right) = UA_{C} \left[ {\frac{{\left( {T_{C} - T_{16} } \right) - \left( {T_{C} - T_{15} } \right)}}{{ln\left( {\frac{{\left( {T_{C} - T_{16} } \right)}}{{\left( {T_{C} - T_{15} } \right)}}} \right)}}} \right]$$
(27)
$$\dot{Q}_{A} = \dot{m}_{13} c_{p} \left( {T_{14} - T_{13} } \right) = UA_{A} \left[ {\frac{{\left( {T_{6} - T_{14} } \right) - \left( {T_{A} - T_{13} } \right)}}{{ln\left( {\frac{{\left( {T_{6} - T_{14} } \right)}}{{\left( {T_{A} - T_{13} } \right)}}} \right)}}} \right]$$
(28)
$$\dot{Q}_{G} = \dot{m}_{11} c_{p} \left( {T_{11} - T_{12} } \right) = UA_{G} \left[ {\frac{{\left( {T_{11} - T_{G} } \right) - \left( {T_{12} - T_{7} } \right)}}{{ln\left( {\frac{{\left( {T_{11} - T_{G} } \right)}}{{\left( {T_{12} - T_{7} } \right)}}} \right)}}} \right]$$
(29)

where \(UA_{i}\) is the conductance value for each component [9, 31].

$$COP = \frac{{\dot{Q}_{E} }}{{\dot{Q}_{G} }}$$
(30)

\(COP\) is the coefficient of performance of the both ammonia–water and water–lithium bromide absorption cycles [9, 31].

Table 1 Constant data are used in dynamic simulation [9]

3 Solution methods of the modeling

In many studies, the thermodynamic properties of solution were taken from some approximate relations causing the results to be somewhat inaccurate. On the other hand, the EES software is powerful and accurate software in field of thermodynamic issues. In this article to diminish the effect of approximate relations on the results, the Engineering Equation Solver (ESS) software is used to define the thermodynamic properties of ammonia–water and water–lithium bromide working fluids. Also, by making a link between MATLAB and EES software the set of differential equations are solved in MATLAB software. The fourth order Runge–Kutta method is employed in solving the differential equations system. Figure 2 shows the basic flowchart of the dynamic model of an absorption chiller.

Fig. 2
figure 2

Basic flow chart of the dynamic model of an absorption chiller

In this article, each component of the absorption cycle is considered as a control volume and a trial and error process are created for them. The initial values like mass, enthalpy and concentration of main components, the constant values such as temperature and mass flow rate of external water circuit, conductance values and solution heat exchanger’s efficiency are given to MATLAB software as input data. Table 2 shows the input values are used in the dynamic model. These values are read by EES software. By using initial values and a hypothetical parameter like pressure, a trial and error process for each component were created in EES software. The pressure variable is considered as a trial and error parameter. Creating a trial and error process was carried out by having initial values such as enthalpy and concentration of the solution at the exit of the generator and hypothetical pressure. Then, generator variables such as temperature, quality and so on, will be obtained. After that, by having these parameters calculate the generator specific volume and will be compared with specific volume that calculating by initial mass. This process is repeated until the convergence criterion is satisfied. Then, the correct values of temperature, pressure and quality of main components are obtained. After that, thermodynamic properties of all points of the cycle and the heat transfer rate of main components are possible to be obtained at each iteration by performing thermodynamic analysis. The output data such as pressure, mass flow rate at points 1–6–8, the enthalpy of all points of the cycle, concentration of the solution at points 1–6 and heat transfer rate of 4 main components are continuously read in MATLAB software to solve differential equations and the new initial values are obtained. This process is continued until the result reached steady state conditions. Tables 3 and 4 show the initial values used in the dynamic model of aqua-ammonia and water–lithium bromide absorption chillers respectively. To validate dynamic model and determined the initial values, the Herold et al. [31] steady state condition results were used.

Table 2 Typical set of input data for the absorption cycle [31]
Table 3 Typical set of initial values for the H2O–LiBr absorption cycle
Table 4 Typical set of initial values for the NH3–H2O absorption cycle

4 Validation and verification of the dynamic modeling

To validate the dynamic code, the results extracted from numerical simulation of both aqua-ammonia and Water-Lithium bromide absorption cycles are compared with steady state results obtained by Herold et al. [31]. Results obtained from the present dynamic analysis, steady state data [31] and also relative error values are reported in Table 5 and 6. As shown in these Tables, the dynamic results have good agreement with their peers. In fact, maximum relative error in aqua-ammonia absorption chiller generated by the \({\dot{\text{m}}}_{1}\) stands at 3.93% while it reaches to 9.2% for \({\dot{\text{m}}}_{6}\) in the case of water–lithium bromide absorption chiller.

Table 5 The dynamic simulation result compared to steady state one [31] for H2O–LiBr absorption chiller
Table 6 The dynamic simulation result compared to steady state one [31] for NH3–H2O absorption chiller

5 Dynamic simulation results

5.1 Comparison the start-up time of NH3–H2O and H2O–LiBr AC’s key parameters under different working conditions

In this paper, transient behavior of main parameters of aqua-ammonia and water–lithium bromide absorption chillers like COP and heat transfer rate of the main components under three different cases are compared:

  1. 1.

    Utilizing RHX with SHX in the cycle (both, case A).

  2. 2.

    Removing RHX from the cycle, just SHX plays role in the cycle (Just SHX, case B).

  3. 3.

    Removing SHX from the cycle, just RHX plays role in the cycle (Just RHX, case C).

To be precise, the time that an absorption chiller needs to reach the designed working condition is called start-up. During this time, energy is consumed in the system while efficient refrigeration is not available. So, it’s too important to consider the influencing parameters on this period of time in order to reduce the energy consumption. Figure 3a, b show the variation of generator’s heat transfer rate for both ammonia–water and water–lithium bromide absorption cycles versus time in three cases mentioned above. The result shows that removing the solution heat exchanger from the cycle (case C) causes 28% and 14% increase in \(Q_{G}\) of NH3–H2O and H2O–LiBr ACs respectively, happening due to lack of heat transfer from point 4 to 3. Besides, it is found that generator start-up time at aqua-ammonia and water–lithium bromide absorption cycles increases in terms of time by 90 and 250 s respectively. To be precise, the percentage of this increase for NH3–H2O AC is about 47.36%, and stands at 22.72% in the case of H2O–LiBr. Figure 3a, b show that utilizing or removing refrigerant heat exchanger in both absorption cycles does affect neither \({\text{Q}}_{\text{G}}\) nor its dynamic response.

Fig. 3
figure 3

a Variation the generator heat transfer rate of the NH3–H2O AC versus time in 3 different cases. b Variation the generator heat transfer rate of the H2O–LiBr AC versus time in 3 different cases

As seen in Fig. 3a, at the beginning of the simulation, \({\text{Q}}_{\text{G}}\) of NH3–H2O absorption cycle in case C initially increased and after about 15 s decreased. Decrease in the weak solution enthalpy of the generator inlet (lack of heat transfer from point 4–3) and fall in the generator temperature resulted in initially raise in \({\text{Q}}_{\text{G}}\). As the time passed by 15 s, the ammonia vapor enthalpy at the absorber inlet is increased by refrigerant heat exchanger, leading to an increase in the absorber temperature as well as weak solution at the generator inlet, and this would itself reduce the \({\text{Q}}_{\text{G}}\) of the NH3–H2O AC. Reducing the \({\text{Q}}_{\text{G}}\) results in reduction in the ammonia vapor generated in the generator, and consequently reduces the cooling capacity and the enthalpy of the solution at point 3 about 80 s. The \({\text{Q}}_{\text{G}}\) increases at 80 s and then reaches to steady state condition, shown in Fig. 3a, due to decrease in the enthalpy of the solution at point 3. Figure 3b shows that \({\text{Q}}_{\text{G}}\) of the water–lithium bromide AC does not change in 3 cases until 250 s. After that, cases A and B reach steady state condition. However, in case C, \({\text{Q}}_{\text{G}}\) increases after 250 s and reaches steady state condition by 1100 s. This increase has been brought about because of removing the solution heat exchanger from the cycle (lack of heat transfer from point 4 to 3) and reducing the solution enthalpy at point 3.

Variation of NH3–H2O AC condenser heat transfer rate versus time for 3 cases is illustrated in Fig. 4a. At the beginning the simulation, temperature and heat transfer rate of the condenser increases due to the high temperature of the ammonia vapor entering the condenser (temperature difference between condenser chamber and point 9) in all three cases. According to the Fig. 4a, \({\text{Q}}_{\text{c}}\) in case of C decreases after 40 s, and after 100 s it increases and then reaches steady state condition. The reduction of \({\text{Q}}_{\text{c}}\) after 40 s is due to the reduction of the ammonia vapor enthalpy at the generator outlet (removing SHX). On the other hand, the refrigerant heat exchanger with regard to liquid enthalpy reduction at the condenser outlet increases the enthalpy of the refrigerant vapor at the absorber inlet and the weak solution enthalpy at the generator inlet as well. Also, increase in enthalpy at point 9 causes an increase in \({\text{Q}}_{\text{c}}\) after 100 s.

Fig. 4
figure 4

a Variation of the condenser heat transfer rate of the NH3–H2O AC versus time in 3 different cases. b Variation of the condenser heat transfer rate of the H2O–LiBr AC versus time in 3 different cases

As seen in Fig. 4a, removing SHX from the cycle (case C) causes a reduction in NH3–H2O AC’s \({\text{Q}}_{\text{c}}\) and increases the start-up time from 180 to 210 s. In case C, \({\text{Q}}_{\text{c}}\) of the NH3–H2O AC increases by 14.28% and has no effect on H2O–LiBr AC’s which is illustrated in Fig. 4a, b. Also, removing RHX from the cycle (case B) has marginal effect on the dynamic response of \({\text{Q}}_{\text{c}}\) in both absorption cycles. The result shows that the \({\text{Q}}_{\text{c}}\) of NH3–H2O AC has been highly affected by removing SHX while its effect on H2O–LiBr AC has been minor.

Variation of evaporator heat transfer rate of NH3–H2O and H2O–LiBr AC versus time for 3 cases are illustrated in Fig. 5a, b respectively. According to these figures, the use of refrigerant heat exchanger with solution heat exchanger (case A) has significantly increased \(Q_{e}\) up to 10% in an aqua-ammonia absorption cycle however it has marginal impact on water–lithium bromide cycle. Moreover, increase in \({\text{Q}}_{\text{e}}\) happens due to reduction of refrigerant enthalpy inside the evaporator and consequently temperature difference reduction between evaporator chamber and chilled water circulation in evaporator. Figure 5a shows that \({\text{Q}}_{\text{e}}\) of NH3–H2O AC reaches steady state condition near to 200 s in when just SHX is used, and this value stands at 155 s in case of RHX. In fact, employment of SHX accompanied with RHX (case A) means increasing the start-up time of \({\text{Q}}_{\text{e}}\) of the NH3–H2O AC by 22.5%, not having effect on the dynamic response of the H2O–LiBr AC evaporator heat transfer rate. The result shows that the evaporator component of NH3–H2O AC has been highly affected by utilizing RHX while it has marginal impact on H2O–LiBr AC.

Fig. 5
figure 5

a Variation of the evaporator heat transfer rate of the NH3–H2O AC versus time in 3 different cases. b Variation of the evaporator heat transfer rate of the H2O–LiBr AC versus time in 3 different cases

Figure 6a, b show the variation of coefficient of performance (COP) versus time for both absorption chillers in different cases. The result represents that utilizing the RHX (case A) causes slight improvement in the COP of the NH3–H2O and H2O–LiBr AC by 11.16% and 1.8% respectively. Also, solution heat exchanger utilization with refrigerant heat exchanger increases the NH3–H2O absorption chiller’s COP by 28.53%, and this value for H2O–LiBr stands at only 16.38%. Removing SHX from the cycle (case C) makes the start-up time of the ammonia–water AC’s COP experience an increase from 150 s to 170 s, and this value is accordingly counted for water–lithium bromide AC’s COP from 850 s to 1550 s. According to Fig. 6a, the NH3–H2O absorption chiller’s COP corresponding with (case C) decreases after 80 s and reaches steady state condition at 170 s, happening because of increase in generator thermal load at 80 s. Figure 6b shows the coefficient of performance of the water–lithium bromide AC does not change through three cases up until 250 s. After that, the COP for cases A and B meets steady state condition. However, the COP decreases after 250 s and reaches steady state condition near to 1250 s in case C. Fall in the COP happens owing to raise in generator heat transfer rate after 250 s.

Fig. 6
figure 6

a Variation of the COP of the NH3–H2O AC versus time in 3 different cases. b Variation of the COP of the H2O–LiBr AC versus time in 3 different cases

The result shows that the influence of utilizing the RHX is only imposed on the evaporator thermal load and the COP, and does not affect the dynamic response of the different parameters of the both absorption chillers. In this regard, the NH3–H2O absorption cycle has been highly affected in comparison with the H2O–LiBr AC. The importance of using SHX for both absorption cycles is much greater than the RHX. According to the result, the start-up time of various parameters of water–lithium bromide absorption chiller is highly affected in comparison with the ammonia–water absorption cycle. Then, removing the SHX from the cycle leads to increase in start-up time of the coefficient of performance of the NH3–H2O AC by 11.76%, and this value is counted as 45.16% in which case the H2O–LiBr absorption chiller is used.

5.2 Comparison the effect of solution heat exchanger’s efficiency on the start-up time of the key parameters of both ACs

As already mentioned, heat exchanger’s components play a very important role in the absorption cycles. Also, the heat exchanger’s efficiency has significant impact in the absorption cycle. In this section, the effect of solution heat exchanger’s efficiency on start-up time of the key parameters of the both AC is discussed and compared. Figure 7a, b indicate the variation of coefficient of performance (COP) versus time for both absorption chillers in different SHX efficiencies. It can be concluded from these figures that increase in SHX efficiency results in COP enhancement for both absorption cycles and this happens owning to reduction in the generator heat transfer rate. In addition, it is revealed that in which case the efficiency of solution heat exchanger goes up from 0.55 to 0.8, COP of the NH3–H2O absorption cycle increases from 0.388 to 0.451, which means 13.92% enhancement. And in case of H2O–LiBr AC, COP ranges from 0.6909 to 0.764 and accordingly brings 9.7% profit. Also, the start-up time of the COP related to NH3–H2O AC increases 9.6%, and this value stands at 46.42% in case H2O–LiBr AC is used. According to Fig. 7a, COP of the NH3–H2O absorption chiller corresponding with 0.55 SHX efficiency decreases after 100 s and then reaches steady state condition, happening due to reduction in generator heat transfer rate at a certain time. By increasing the SHX efficiency (decrease in generator heat transfer rate), intensity of this reduction decreases and at a certain SHX efficiency (ɛ = 0.8), COP increases. Figure 7a, b reported that in H2O–LiBr AC, SHX efficiency enhancement has slightly influenced the COP by 9.7% but has applied a valuable increase in the COP start-up time around 11 min. In contrast, SHX efficiency enhancement in NH3–H2O AC, has a minor impact on COP start-up time (near to 15 s) while remarkably influences the COP by 14%.

Fig. 7
figure 7

a Variation of the COP of the NH3–H2O AC versus time at different SHX efficiency. b Variation of the COP of the H2O–LiBr AC versus time at different SHX efficiency

6 Discussion

Nowadays, due to the unceasing increase in electric energy consumption, the rising cost of fuel and destructive effects of the HCFC refrigerant on the ozone layer and the global warming problem, absorption chillers are more considered. The time required an absorption chiller achieves its design condition is called Start-up time and during this time, energy is used however the effective refrigeration wouldn’t be achieved. Also, dynamic analysis can be used to reduce the startup time and increase system performance in addition to strategic control purposes. Optimizing the absorption cycle during transient operations, such as start up or shut down is of interests. In this article, in order to mitigate the effect of approximate relations on the outcomes, the thermodynamic properties of NH3–H2O and H2O–LiBr solutions are extracted from the EES software. By making a link between MATLAB and EES software, a set of differential equations is solved in MATLAB software. This study deals with a lumped-parameters dynamic simulation of aqua-ammonia and water–lithium bromide absorption chillers under three different conditions including, (1) utilizing RHX within SHX in the cycle, (2) removing RHX from the cycle, just SHX plays the role in the cycle and (3) removing SHX from the cycle, just RHX plays the role in the cycle. The effect of employing refrigerant and solution heat exchangers and solution heat exchanger’s efficiency on the start-up time of the key parameters of both ACs studied and compared.

Many researches have been carried out through steady state condition to analyze the absorption chiller’s performance. The results in literature show that employing SHX in absorption chillers and increasing the effectiveness of the SHX has caused generator heat load decrement in addition to an increase in COP [22, 23, 33]. Also, employing SHX in ACs grows up the COP more than 44% while this value for RHX stands at only 2.8% [22, 33]. Based on researchers’ findings, the absorption chillers performance is highly affected by SHX in comparison with RHX [22, 23, 33]. Our dynamic simulation outcomes represent that utilizing the RHX causes slight improvement in COP value of both NH3–H2O and H2O–LiBr ACs by 11.16% and 1.8%, respectively. Also, the use of SHX increases the COP of NH3–H2O absorption chiller by 28.53%, and this value for H2O–LiBr stands at only 16.38%. Removing solution heat exchanger from the cycle increases the start-up time of COP of the NH3–H2O and H2O–LiBr ACs by 11.76% and 45.16% respectively. According to the results, by increasing the SHX efficiency from 0.55 to 0.8, the COP of the NH3–H2O and H2O–LiBr ACs increases by 13.92% and 9.7%, respectively. Furthermore, the start-up time of the COP related to NH3–H2O AC increases 9.6%, and this value stands at 46.42% in case of H2O–LiBr AC. In case of H2O–LiBr AC, increase in SHX efficiency has slightly affected the COP by 9.7%, but it significantly increases the COP start-up time near to 11 min. On the contrary, SHX efficiency enhancement in NH3–H2O AC has minor effect on COP start-up time near to 15 s, having highly affected the COP by 14%.

Our dynamic results represent that the start-up time of the COP of water–lithium bromide absorption chiller is highly affected in comparison with ammonia–water absorption cycle, by removing SHX or increasing the SHX efficiency. Also, by utilizing the RHX does not affect the dynamic response of the key parameters of the both absorption chillers. The importance of using SHX for both absorption cycles is much greater than the RHX.

7 Conclusion

Simulations are way very important tools for researchers to predict the performance of absorption chillers at the dynamic level with low cost. Also, dynamic analysis can be used to reduce the startup time and increase system performance in addition to strategic control purposes. The aim of this study was to evaluate and compare the dynamic performance of aqua-ammonia and water–lithium bromide absorption chillers under three different conditions including, (1) utilizing RHX within SHX in the cycle, (2) removing RHX from the cycle, just SHX plays the role in the cycle and (3) removing SHX from the cycle, just RHX plays the role in the cycle. In addition, the impact of solution heat exchanger’s efficiency on the start-up time of the key parameters of both ACs was studied. In order to minimize the deviations resulted from approximated equations, the Engineering Equation Solver (EES) software was used to obtain the thermodynamic properties of aqua-ammonia and water–lithium bromide working fluids, and MATLAB software was employed to solve differential equations. To validate the dynamic model, the results extracted from numerical simulations of both aqua-ammonia and water–lithium bromide absorption cycles were compared with steady state results, and relative errors were also reported. The following results were obtained from the dynamic analysis of the cases mentioned above:

  1. 1.

    Removing SHX increases the start-up time of \(Q_{g}\) of the NH3–H2O and H2O–LiBr ACs by 47.36% and 22.72% respectively.

  2. 2.

    Removing SHX increases the start-up time of \(Q_{c}\) of the NH3–H2O AC by 14.28% while it has no effect on H2O–LiBr AC.

  3. 3.

    Removing SHX increases the start-up time of COP of the NH3–H2O and H2O–LiBr ACs by 11.76% and 45.16% respectively.

  4. 4.

    In case of H2O–LiBr AC, increase in SHX efficiency has slightly affected the COP by 9.7%, but it significantly increases the COP start-up time near to 11 min. On the contrary, SHX efficiency enhancement in NH3–H2O AC has minor effect on COP start-up time near to 15 s, having highly affected the COP by 14%.

  5. 5.

    Key parameters of H2O–LiBr AC in terms of start-up and NH3–H2O AC in terms of quantity are highly affected by removing SHX and increasing the SHX efficiency respectively.

Dynamic simulation of triple-stage absorption chiller by HYSYS software, analysis and economic optimization of triple-stage absorption chillers, and new controller design to reduce the absorption chiller energy consumption are suggested as a future research.