Introduction

Recent earthquakes which hit Italy Between August and October 2016 (Fiorentino et al. 2017) demonstrated the high vulnerability of the Italian building stock. This vulnerability is evident for masonry and for reinforced concrete (RC) structures which were designed and built using old design criteria that heavily underestimated the seismic actions.

The use of FRP materials can be a valid solution for the retrofitting of existing RC buildings and bridges (Albanesi et al. 2008, 2009; Lavorato and Nuti 2010, 2011, 2015; Lavorato et al. 2010, 2015, 2017a; Marano et al. 2017). Many existing RC beams have insufficient shear reinforcement, due to design or construction defects or increased design load requirements. It is worth noting that infill panels can interact with the structural elements and influence their shear strength (Fiore et al. 2016).

The beam retrofitting with carbon fiber-reinforced polymer (C-FRP) sheets or strips is a valid solution to increase the shear strength. The retrofitting intervention with C-FRP is fast and the cost is modest. International and National Guidelines and Codes (CNR-DT 200 R1/2013 2013; Fib 2001; Italian Council of Public Works 2009) give design prescriptions for shear retrofitting of beams by C-FRP which are essentially based on exhaustive experimental data for simply supported beams only.

Key example tests from the literature have been conducted by Pellegrino and Modena (2000), Adhikary and Mutsuyoshi (2004), Carolin and Taljsten (2005), Zhang and Hsu (2005), Barros and Dias (2006), Guadagnini et al. (2006), Monti and Liotta (2007), Bousselham and Chaallal (2008) and Garcez et al. (2008).

In those cases, the new C-FRP shear reinforcements are placed, where moments are negligible and anchored in the compressed upper part of the section in absence of concrete cracking.

RC frames have beams in which the shear forces are combined with negative bending moments at supports with consequent concrete cracking on the upper part of the section (in tension), where the C-FRP anchorages are placed. As a consequence, specific tests are required to validate C-FRP anchorage behavior.

Few studies deal with this issue and new research efforts seem useful. In the scientific literature, Khalifa and Nanni (2000) tested nine continuous two-span beams with different C-FRP amounts and wrapping schemes highlighting that the U-wrap C-FRP reinforcement does not seem to reduce cracks, even if an overall increase of the shear strength is observed.

In the present paper, the behavior of existing RC beams reinforced for shear by C-FRP U strips placed in negative moment sections and anchored under the slab was investigated by experimental tests.

An existing RC building in Rome, dated around year 1930, had to be upgraded to withstand seismic actions and vertical loads according to the Italian Design Code (OPCM 2003; NTC 2008). Although for very extended buildings, as the case study presented herein, there could be spatial variability of the strong motion (Trifunac and Todorowska 1997) which should be taken into account by means of appropriate methods (Lavorato et al. 2017b), this was not taken into account in the retrofitting of this particular building. New RC shear walls and slabs had to be inserted and the application of C-FRP wrapping on existing columns and U-shape strips on beams was necessary for confinement and shear strength, after the construction of an additional slab which increased bending resistance and consequently shear demands.

Two beams were extracted (Fig. 1a, b) and retrofitted as those in the building: same additional slab, longitudinal upper reinforcement, and U-shaped C-FRP strips. After retrofitting, the beams were tested in the PRiSMa Laboratory (Proof Research and testing in Structures and Materials) at Roma Tre University.

Fig. 1
figure 1

Retrofitting of the RC building (a) and removal of the beams (b)

The beams were integrated with a new cantilever at one support to reproduce, in the lab, the negative moments and shear due to adequate vertical concentrated loads.

The original removed beams

Geometrical properties and steel reinforcement

The retrofitting intervention on the RC structure involved the construction of new RC walls with consequent removal of two existing beams, as depicted in Fig. 1. These beams, labelled as TM1 and TM2, were carried to the PRiSMa Lab of the Roma Tre University and retrofitted and tested there. The geometrical properties and the steel reinforcement configuration of the T-section beams TM1 and TM2 with smooth longitudinal rebars and stirrups are given in Table 1.

Table 1 Geometrical properties and steel reinforcement of beams TM1 and TM2 (mm)

Material properties

In the following sections, TM1 and TM2 indicate the original beams, while S-TM1 and S-TM2 indicate the beams after the retrofitting interventions. Concrete and steel rebar mechanical characteristics are given in Table 2. Concrete compressive strength is obtained by destructive test on cores extracted after the failure tests on S-TM1, and by SONREB test on the S-TM2 beam, correlated with core resistances on S-TM1. The characteristics of steel rebars (yield strength, maximum strength, and deformation under maximal load) are evaluated by destructive tests on six samples of smooth rebars removed from the beam TM1 after the failure tests, consisting in three stirrups (2ø8 and 1ø12) and three segments of ø24 rebars of the longitudinal reinforcement. These reinforcement characteristics can be considered valid for beam TM2 too, being the two beams very close in the building, and given that from direct observation of the specimens, the longitudinal reinforcement seems the same. More information about tests for the mechanical characterization of original beams and retrofitting intervention may be found in Imperatore et al. (2012a, b, 2013a, b), Forte et al. (2018) and Lavorato et al. (2016).

Table 2 Material properties for beams TM1 and TM2

Interventions on the original beams

The intervention consisted in the addition of a cantilever and retrofitting as in the real frame structure building, i.e., for bending and shear. The cantilever was added at one end of the beams to apply negative moments by means of a mono-directional force actuator (“Additional RC cantilever”). Therefore, the two beams have a stress condition which is similar to the real building, with simultaneous presence of shear and negative moment at the support.

Then, the beams, TM1 and TM2, with the added cantilever, were retrofitted as in the real building, see Fig. 2, with the construction of an additional RC slab to improve the flexural strength (“Flexural strengthening”) and the application of C-FRP strips to enhance the shear strength (“Shear strengthening”).

Fig. 2
figure 2

Beam specimen with added cantilever (top), test load scheme (center) and internal forces (bottom); (mm)

The beam TM1 was tested twice. The first time the beam (labelled S-TM1-A) showed a fragile failure due to collapse of the compressed concrete at the support, and in the added upper slab. Subsequently, the same beam (labelled S-TM1-B) was tested again after adding a new cantilever on the undamaged opposite end with a proper reinforcement in bending for the new slab and the new cantilever and a proper distribution of the connectors between the new and the existing beam slab.

The second beam TM2 was retrofitted, taking into account the previous experience on beam TM1 and tested as S-TM2.

Additional RC cantilever

The cantilever lengths L2 are equal to 1.82 m for the beam S-TM1-A and 1.53 m for the beams S-TM1-B and S-TM2. These differences in the test geometry are due to practical needs for the construction of the cantilevers in the lab, as they were built in different dates. Other differences are in the steel arrangement to improve the reinforcement configuration on the base of the experience acquired during the test on the first beam S-TM1-A.

Concrete class C28/35 (characteristic value of cylinder concrete strength fck = 28 MPa) was used to build the cantilever of the beam S-TM1-A, while it was slightly smaller (average value of cubic concrete strength Rcm = 31.22 MPa) for the cantilevers of the beams S-TM1-B and S-TM2 (Table 3).

Table 3 Added RC cantilevers: concrete and reinforcement mechanical properties, section geometries

For the S-TM1-A beam, the reinforcement, that is built by a typical B450C steel rebar type (characteristic value of steel yield strength fyk = 450 MPa; see Italian Code NTC 2008), was arranged according to the following scheme:

  • longitudinal upper rebars: 4ø24 side-welded to the original 4ø24 upper rebars of TM1 beam;

  • longitudinal lower rebars: 2ø12 anchored chemically for a length of 250 mm, drilled in the original beam;

  • stirrups: ø12/150 mm in the web,

  • longitudinal bars 4ø12 and stirrups ø8/150 mm in the flange.

The reinforcement of the added cantilevers of S-TM1-B and S-TM2 changed in the inferior longitudinal bars and their connection to the existing beam:

  • longitudinal upper rebars: 4ø18 butt-welded to the upper reinforcement of the existing beams: 4ø24;

  • longitudinal lower rebars: 2ø18 butt-welded to the original lower reinforcement of the existing beam: 2ø24;

  • stirrups ø10/200 mm in the web;

  • longitudinal bars 4ø12 and stirrups ø10/200 mm in the cantilever flange.

The need of a different arrangement in the bottom cantilever reinforcement with respect to S-TM1-A arose after the test of S-TM1-A. In fact, there was failure of bottom concrete of the original TM1 beam which crashed, where cantilever bottom bars, compressed, ended at 250 mm from the support. It was, therefore, decided the butt-welding of the cantilever bottom reinforcement to the bottom reinforcement of the original beam, while larger diameter bars were used, ø18 instead of ø12, to reduce compression side failure probability. The steel reinforcement of the added cantilever was of the typical B450C type (characteristic value of steel yield strength fyk = 450 MPa).

The longitudinal ø18 bars and the ø24 rebars of the original beams are more or less equivalent in terms of strength, because the yielding strength of B450C steel type is higher with respect to the one of the original smooth rebars. On the other hand, the smaller diameter simplified the butt-welding connection.

Flexural strengthening

The flexural strengthening involves the addition of an RC slab with rectangular section 800 mm wide and 70 mm thick. This slab has been executed in two different ways (Figs. 3, 4). In fact, as already mentioned in the introduction, the original beam TM1 has been subjected to two interventions. The first time the cantilever has been added on one side, then the beam has been strengthened with an additional slab and carbon strips for shear (S-TM1-A), and finally tested to failure. After the removal of the damaged cantilever and slab, a new RC cantilever on the opposite undamaged end of the beam, a new RC slab, and new C-FRP strips have been added for shear resistance (S-TM1-B). A new test has been carried out to failure.

Fig. 3
figure 3

Retrofitted beams: RC slab steel reinforcement. Beam S-TM1-A (top); beams S-TM1-B and S-TM2 (bottom) (mm)

Fig. 4
figure 4

Retrofitted beams: RC slab steel longitudinal reinforcement, connectors for retrofitted beams S-TM1-A (left), S-TM1-B and S-TM2 (right)

In beam S-TM1-A, the connection between the beam and the additional slab is simply straight vertical rebars ø12/200 mm, see Fig. 3, top and Fig. 4, left, limited to part of the zones of the additional longitudinal reinforcement. These latter consisted in 2 + 2 ø20, which was limited to the cantilever zone and to the final part of the slab opposite to the cantilever.

The additional slab reinforcement consisted of electro-welded mesh (ø8/200 × 200 mm) disposed along the entire RC slab between the lower (2 ø20) and the upper (2 ø20) longitudinal rebar layers.

S-TM1-B is obtained from the same beam TM1 after testing S-TM1-A, removing the slab, the cantilever, adding a cantilever on the opposite side and a new slab, with better reinforcement details. For the beam S-TM1-B, the new RC slab had two sets of connectors (ø12/125 mm) with butt-welded steel plate and U-shape rebars (as stirrups, ø12/125 mm) anchored chemically to connect the new RC slab to the existing one. The connectors, the slab main longitudinal reinforcement (6 ø16), and two layers of electro-welded net (ø6/200 × 200 mm, below and above the longitudinal reinforcement) are disposed along the whole length of the beam (Figs. 3, bottom, Fig. 4 right).

The concrete used for the S-TM1-A slab is a lightweight concrete with polypropylene fibers (40 × 12 × 0.2 mm) Leca® CLS 1800 with Rck = 45 MPa according to the commercial datasheet. The concrete is C28/35 type with characteristic cylindrical compressive strength equal to 28 MPa and steel B450C with characteristic yield strength equal to 450 Mpa. The RC slab concrete and steel mechanical characteristics have also been obtained experimentally by failure tests on standard cubic specimens (150 mm side) and steel reinforcement sample (4) if specimens were available. The full mechanical properties of concrete and reinforcement of the new RC slab are given in Table 4.

Table 4 Retrofitted beams S-TM1-A, S-TM1-B, and S-TM2: mechanical properties of concrete and reinforcement of the new RC slab

The RC slab for flexural reinforcement of S-TM1-A had been realized according to the following steps (Fig. 4, left):

  1. 1.

    Anchorage of two sets of connectors ø12/200 mm at the beam extrados in correspondence of each beam supports (points A and B, Fig. 2); these connectors were realized with simple rebar segments.

  2. 2.

    Placing of 2 ø20 longitudinal rebars in correspondence of each beam supports (points A and B, Fig. 2).

  3. 3.

    Placing of one layer of electro-welded net ø8/200 × 200 mm above the longitudinal rebars.

  4. 4.

    Placing of another 2ø20 longitudinal rebars in correspondence of each supports (points A and B, Fig. 2) on the electro-welded net.

  5. 5.

    Casting of lightweight concrete Leca CLS 1800® (http://www.leca.it).

The RC slabs for flexural reinforcement of S-TM1-B and S-TM2 were realized according to the following steps (Fig. 5):

Fig. 5
figure 5

Retrofitting of the beam specimens: a C-FRP strips for shear reinforcement and RC slab for flexural reinforcement; b intersection of the C-FRP strips at the beam intrados

  • Anchorage of two lines of connectors ø12/125 mm along the entire beam extrados; each connector free end has circular butt-welded plate ø30 with thickness equal to 5 mm.

  • Placing of one layer of electro-welded net ø6/200 × 200 mm along the entire slab.

  • Placing of 6ø16 longitudinal bars along the entire slab.

  • Placing of another layer of electro-welded net ø6/200 × 200 mm along the entire slab.

  • Chemical anchorage of stirrups (U-shaped rebars) ø12/125 mm along the entire beam extrados.

  • Casting of lightweight concrete class C28/35.

Shear strengthening

According to Italian Code (NTC 2008), the shear strength of the reinforced beam [VRd, Eq. (1)] is equal to the minimum value between strength of the compressed concrete strut (VRd,c) and the sum of the shear strength of the transversal steel reinforcement (VRd,s) and of the C-FRP reinforcement (VRd,f):

$$V_{\text{Rd}} = \hbox{min} \{ V_{\text{Rd,s}} + V_{\text{Rd,f}} ,V_{\text{Rd,c}} \} .$$
(1)

The compressed concrete strut contribution (VRd,c) and the transversal steel contribution (VRd,s) considering a concrete shear crack angle equal to 45°. They result 522 and 80–150 kN (depending on possible stirrups’ diameter; see "The original removed beams"), respectively.

The C-FRP reinforcement shear contribution (VRd,f) is calculated by Eq. (2). The required parameters are (see Fig. 6) the thickness (tf), the width (wf), the spacing (pf) of the C-FRP reinforcement, the fiber angle with respect to the beam longitudinal axis (β), the beam effective depth (d), the concrete shear crack angle with respect to the longitudinal beam axis (θ), the effective FRP design strength (ffed), and the partial factor for the resistance model (γRd), here assumed as 1:

$$V_{\text{Rd,f}} \, = \,1/\gamma_{\text{Rd}} \cdot 0.9 \cdot d \cdot f_{\text{fed}} \cdot 2 \cdot t_{\text{f}} \cdot (\cot \theta \, + \,\cot \beta ) \cdot w_{\text{f}} /p_{\text{f}} .$$
(2)
Fig. 6
figure 6

C-FRP shear reinforcement scheme for shear strength evaluation according Italian S.C.P.W guideline (images by Figures 3–8 in Italian Council of public works 2009)

The applied C-FRP shear reinforcement for each beam specimen is made of eight C-FRP U strips (Fig. 6, left) applied along the beam ends for a length of 140 cm starting from both the beam supports. Each U strip is composed by two sheets which cross at 45° on the intrados of the beam (Fig. 6, right). The C-FRP U strips are made of commercial product Carbostru® (https://www.interbau-srl.it) UDHM 400 (weight of 400 g/m2, tensile strength of 3000 MPa, elastic modulus of 390 GPa, and equivalent thickness tf= 0.225 mm according to the data from technical datasheet). The C-FRP strips have a width wf = 100 mm, the spacing of the strips is pf = 212 mm, and the strips distance is pf′ = 300 mm (Fig. 6).

The shear strengthening intervention is made according the “application type A of material and system certification” (CNR-DT 200 R1/2013 2013) and consists in:

  1. 1.

    Mechanical removal of the external grout for a length of 140 cm from the supports.

  2. 2.

    Leveling of the concrete surface.

  3. 3.

    Regularization of the surface by plaster.

  4. 4.

    Application of a thixotropic plaster (epoxy resin, Sikadur-30®, https://ita.sika.com/), having high strength and low shrinkage on the concrete surface.

  5. 5.

    Application of the C-FRP strips using the epoxy resin Carbostru® RS85 (https://www.interbau-srl.it).

The C-FRP strip properties have also been evaluated by qualification tests according to Italian the Code prescriptions called “coupon tests”. These consist in tests on C-FRP strips subjected to traction force parallel to the direction of the strips, to simulate the U strips shear behavior. The geometry and mechanical characteristics of the three tested specimens are given in Table 5.

Table 5 C-FRP coupon geometry and mechanical properties width (b), thickness (s), fiber area (Afib), composite area (Acom), failure force (F), maximum deformation (εmax), fiber stress (σr-fib), composite stress (σr-com), fiber elastic modulus (Efib), and composite elastic modulus (Ecom)

The effective design strength of FRP (ffed) is assumed equal to 541 Mpa, the concrete tensile strength (fctm) is equal to 2 MPa (a conservative value), and the concrete compressive strength is equal to 16.6 MPa. The concrete strut angle is equal to 45° according to Italian Code prescription and the safety coefficients γf,d, γc, and γR,d are assumed equal to 1. The resulting C-FRP reinforcement theoretical shear strength [VRd,f, Eq. (2)] results equal to 116 kN.

The two resulting shear strength values for the beam (VRd,s + VRd,f) considering the two possible stirrups’ arrangements (see “The original removed beams”) and so the two possible values of the stirrups’ shear contributions (VRd,s = 80–150) results equal to 196–266 kN. The large scatter for the stirrups’ shear contributions depends on the possible stirrup diameter. The stirrups’ rebar diameter is difficult to evaluate by non-destructive tests.

Tests: set up for loadings and applied load histories

Two set of tests are presented: the first one was carried out after the construction of the cantilever to evaluate the stiffness of the beam in the elastic field before retrofitting and the second one was performed until failure to check the ultimate behavior of the retrofitted beams. The latter was performed with special attention on the behavior of the C-FRP strip contribution to beam shear strength at support B, where the C-FRP reinforcement was anchored in a zone with negative bending moment. Some details about the tests are reported in Nuti et al. (2010, 2014).

The simply supported beam with cantilever is an isostatic load scheme, and therefore, internal forces, bending moment, and shear depend on the position and intensity of the external applied loads only, as shown in Fig. 2. Two loads have been applied: F1 on the beam span and F2 on the cantilever end. They are increased in steps to obtain at each loading step the desired values of shear and moment at support B.

The span load F1 is placed at a distance L1 from support B (see Fig. 7) between 2.5 H and 3 H (H is the beam section height, Table 1), which determine shear failure without arch mechanism. F2 is applied at the cantilever end, i.e., at L2 (see Fig. 7).

Fig. 7
figure 7

Retrofitted beams in test apparatus: a retrofitted beams in the test apparatus; b potentiometers and strain gauges on the C-FRP strips

Experimental setup for loading and measurements

The test apparatus reproduces the load scheme in Fig. 2. The beam specimens were placed on two steel frames (supports A and B). The load F1 is applied on the beam span by a 1000 kN hydraulic jack (300 mm maximum stroke) controlled by an external load cell (1000 kN maximum load, TEDEA-HUNTLEIGH). The load F2 is applied on the cantilever end by a 250 kN MTS hydraulic actuator (250 mm maximum stroke) controlled by an internal load cell and the Labview® (http://www.ni.com/it-it/shop/labview.html) software for the application of load or displacement histories. The acquisition system consisted of:

  • National Instruments DAQ station SCXI 1001 with DAQ moduli SCXI 1314/1520.

  • National Instruments DAQ board 6281 (18 bit).

  • LabView acquisition program.

The beam deflections and the C-FRP strains acquisition system consisted of:

  • 24 potentiometers Penny–Giles on the two beam sides (10 with stroke ± 25.0 mm and 14 with stroke ± 50.0 mm); 12 potentiometers for the beam vertical displacements along the span at 0.2–0.4–0.6 L (load F1 application point)—0.8 L from the simple support without cantilever and along the cantilever at 0.5 L2—L2 (load F2 application point) (Fig. 7); four potentiometers for the beam support vertical displacements; and eight potentiometers for the beam shear deformations (diagonal direction) beside the C-FRP strips

  • 18 strain gauges (10 mm grid) placed at 45° on the C-FRP strips f4, f3, f2, and f1 (Fig. 7) near support B (six for strip and three for each side).

Load steps for elastic tests before retrofitting

The loading in the elastic test had the aim of not overtaking 80% of shear resistance of the beams, as given in Table 6. The loading steps are given in Fig. 8. The corresponding moment and shear are given in Table 7. Note that in the final step, the internal shear force is 71 kN, about 80% of the theoretical strength. The corresponding bending moment is well below the bending resistance.

Table 6 Theoretical bending and shear strength of the beams before retrofitting (assuming 8 mm for stirrups’ diameter)
Fig. 8
figure 8

Elastic test load history: F1 (blue solid line) and F2 (red solid line) are the forces applied on the beam according to the load scheme displayed in Fig. 7

Table 7 Loading steps for the external forces F1 and F2 (F1hyp: desired applied; F1ef: effectively applied load) and corresponding internal forces (shear T, bending moment M) at beam support B and C in the elastic tests before retrofitting

Load steps for failure tests on the retrofitted beams

The bending moment strength (M), based on the geometry and reinforcement characteristics, in the span and at support B (MuC, MuB) and the design goal shear resistance (Vu) at the left of support B are given in Table 8.

Table 8 Theoretical bending resistance at mid-span and bending and shear resistance at left of support B after retrofitting

Loading steps differ among the two elastic tests before retrofitting and tests to failure after retrofitting, because the geometry of the loads was different. Small difference in the geometries of beam S-TM1-A and the couple S-TM1-B, S-TM2, existed as well, therefore, the loading steps were slightly different.

The goal of the failure test for each beam is the evaluation of the bending and shear strength on the left side of beam support B.

The geometry of the failure tests on S-TM1-A and on the S-TM1-B and S-TM2 beams are given in Figs. 9 and 10, respectively.

Fig. 9
figure 9

S-TM1-A failure test scheme after retrofitting

Fig. 10
figure 10

S-TM1-B and S-TM2 failure test scheme after retrofitting

Load steps applied on the S-TM1-A during the failure test are given in Table 9. The load steps are interrupted below the values F2 = 140 kN and F1 = 254 kN, required to give the intended shear and bending moment on the left of the support B (shear 215 kN and bending moment 457 kN m), as the beam failed in bending for various inadequate detailing discussed in test results ("Experimental results").

Table 9 S-TM1-A loading steps and corresponding internal forces in the elastic tests before retrofitting

The last load steps were N. 11 with F1 = 180 kN and F2 = 100 kN and N. 12 with F1 = 201 and F2 = 118 kN. One can see that in steps N. 12A and 12B, we could increase F1, but not F2 due to bending failure of the support.

Load steps applied on the S-TM1-B and S-TM2 during the failure test are practically coincident and are given in Table 10.

Table 10 S-TM2 loading steps and corresponding internal forces in the elastic tests before retrofitting

Experimental results

The experimental results about the elastic and failure tests described in §4 are discussed in terms of: (1) behavior (deflections) of the non-retrofitted beams during the elastic tests and (2) behavior (deflections and C-FRP reinforcement deformations) of the retrofitted beams during the failure tests.

The latter test results are discussed to evaluate the real C-FRP contribution to the shear strength of the retrofitted beam in term of: the ratio between the theoretical and the experimental beam shear strength and the additional contribution of the C-FRP shear reinforcement to the total beam shear strength, the so-called C-FRP efficiency.

Preliminary elastic tests on the no retrofitted beams with the added cantilever

The obtained beam deflections under the maximum loads during the elastic tests on S-TM1 and S-TM2 beams are given in Fig. 11. The comparison between the two beams deflections showed that beam S-TM1 had larger mid-span and cantilever displacements.

Fig. 11
figure 11

Deflections along the beams S-TM1 and S-TM2 under the loads F1 = 79–80 kN and F2 = 27 kN during the elastic tests

Displacements under F1 at point C in Fig. 11 are from 35% (S-MT1) to 25% (S-MT2) larger than those calculated with the gross section without considering the cracking state before the test.

Failure test on beam S-TM1-A failure happened in a premature manner at a shear TBsx = 174 kN with a negative moment of 245 kN m. We remember that the goal shear was 215 kN and bending moment of 457 kN m.

The experimental behavior of the specimen S-TM1-A enhanced the ineffectiveness at failure of the new concrete slab due to the absence of efficient connectors and abrupt interruption of longitudinal reinforcement. The additional slab lifted from the beam near support B at a load F1 = 150 kN, as the connector added for the slab had no anchoring device at the end and loosed vertical connection with concrete.

Beam deflections

The behavior of the beam compared to that before retrofitting can be seen in Fig. 12 in terms of beam deflections. As already explained, the geometry of failure tests has light differences with respect to the elastic one. Therefore, displacement comparison is not straightforward. The span of the retrofitted beam is larger, while the cantilever is shorter. Therefore, larger span and smaller cantilever displacements were expected.

Fig. 12
figure 12

Deflections of the beam S-TM1-A for loads F1 = 73–75 kN and F2 = 27 kN before retrofitting (TM1pre) and after retrofitting (TM1post)

Figure 13 shows the results of the failure test carried on on retrofitted beam S-TM1-A. Passing to larger forces, the deflection direction and the beam stiffness changed abruptly when the load F1 was equal to about 180 kN and F2 about 100 kN. The corresponding shear force was 152 kN and the bending moment was 200 kN m. At the following step with F1 = 200 kN and F2 = 118 kN, corresponding to a shear force of 173 kN and a moment of 254 kN m, there was total failure. Failure happened in a brittle manner due to flexure at support B with concrete crushing and detachment of C-FRP reinforcement.

Fig. 13
figure 13

Retrofitted beam S-TM1-A experimental results of the failure test: load F1 vs span deflection curves at 0.2, 0.4, 0.6 and 0.8 L

This should have been foreseen as the section is strongly reinforced in tension with few compressed steel badly anchored (See Fig. 3) .

C-FRP deformations

The shear at support B (TB) VS deformation of C-FRP of the strips f2, f3, and f4 at their top, middle, and bottom points is shown in Fig. 14. The beam design shear strength (215 kN) was, by far, not obtained. The contribution of C-FRP strips was well below the expected design one (116 kN). However, the deformations of the C-FRP strips were modest due to the detachment of the concrete base due to the ejection of concrete cover at the anchorage of the strips nearest to support due to bending failure of the beam with concrete crushing (Fig. 15). For that reason, the C-FRP shear reinforcement could not develop its contribution.

Fig. 14
figure 14

Retrofitted beam S-TM1-A experimental results of the failure test: shear at support B vs deformation for the C-FRP strips f2, f3, f4 measured by strain gauges at the top, middle and bottom positions on each beam side

Fig. 15
figure 15

Retrofitted beam S-TM1-A damage after the failure test; a damage at support B with negative moment; b detail of lateral ejection of concrete due to the interruption of the lower steel reinforcement

Failure mechanism

Failure was evident as various fragile mechanism arose. The additional slab detached, lifting upward from the original beam, near support B, as the connectors were not adequately anchored at their top. The longitudinal new slab rebars were interrupted all together in the slab causing, at the interruption section, the rupture of the slab in tension, while the slab lifted from the original beam (see Fig. 15). Flexural reinforcement was not effective near the support B. The new cantilever had bottom reinforcement anchored in the old beam with a short superposition. This detail caused the total inefficiency of bottom reinforcement which rendered the section sensible to brittle failure and caused rupture by crushing of compressed concrete at support B with buckling of the longitudinal rebars and detachment of the C-FRP reinforcement (Zhou et al. 2014, 2015). For that reason, the shear retrofitting was not effective.

The beam damage developed seriously near support B, starting from a shear (TB) of 141 kN and a moment (MB) of 208 kN m (F1 = 160 kN and F2 = 100 kN), and included:

  • evident vertical cracks on the original beam flange;

  • detachment and lifting of the new RC slab (max lifting = 6 cm);

  • concrete crushing along the beam sides at the support B near the connection with the cantilever with primer (on which C-FRP strips are applied) damage.

Finally, wide diagonal shear cracks appeared along the original beam flange. The collapse occurred when the shear TB was 181.47 kN and the moment MB was 232.79 kN m (F1 = 219.4 kN, F2 = 111.92 kN), as displayed in Fig. 15. These actions values were smaller than the design ones, in particular the shear of about 10–20%. The segment of the beam from the support A to the section of the applied load F1 presented no significant damage at beam failure. This permitted to reuse of the beam TM1 with a new cantilever starting from A.

Failure test on beam S-TM1-B and S-TM2

Beam deflections

The two beams S-TM1-B and S-TM2 showed greater strengths than the design ones (Fig. 16). They had similar initial stiffness and yielding deformations. They also showed significant deformation capacity, as demonstration of the good retrofitting detailing now adopted, validating the final design solution.

Fig. 16
figure 16

Retrofitted beams S-TM1-B and S-TM2 experimental results of the failure test: load F1 vs span deflection curves at 0.2, 0.4, 0.6 and 0.8 L

Beam S-TM1-B, already tested as S-TM1-A, showed plateau strength only (450 kN) without initial peak value (500 kN) like in S-TM2. This was probably due to the damage cumulated in S-TM1-A beam failure test. The total displacement was, however, large in both, with values of about 15–20 mm at 0.4 and 0.6 L.

Beam S-TM2 had a peak strength at the displacement of 7.5 mm at 0.4 and 0.6 L, after a couple of mm the force reduced to about 400 kN. This value remained constant to failure with 33–43 mm of displacement.

The beam collapse resulted plastic as a good design has to guarantee.

C-FRP deformations

The C-FRP deformations are given in Figs. 17 and 18 for each strip (f2–f3–f4) on the two beam sides, as a function of internal shear force.

Fig. 17
figure 17

Retrofitted beam S-TM1-B without retrofitting construction defects: shear at support B vs deformation curves for the C-FRP strips f2, f3, f4 by strain gauges at the top, middle and bottom positions on each beam

Fig. 18
figure 18

Retrofitted beam S-TM2 without retrofitting construction defects: experimental results of the failure test; shear at support (TB) B vs deformation curves for the C-FRP strips f2, f3, f4 by strain gauges at the top, middle and bottom positions on beam sides 1 and 2

The maximum experimental C-FRP deformations were in range of 1.0‰ (in one point 1.5‰, strip 4) for S-TM1-B (Fig. 17) and in the same range 1.0‰—(but maximum of 2.0‰ but in strip 2) for S-TM2 (Fig. 18). These values were significantly smaller than the one assumed during the C-FRP reinforcement design (5‰).

Failure of the C-FRP reinforcement was due to debonding of the strips starting from a shear value of 375–400 kN for S-TM1-B and S-TM2 beam, respectively. These shear values were greater than the retrofitting objective; therefore, the intervention proved to be effective. In fact, strips had a maximum strain of 1‰, sufficient to develop the additional shear contribution required.

The plain anchorage of the strips guaranteed the design shear strength even if it was applied, at least partially, on the cracked concrete zone.

This is an important conclusion as C-FRP plain anchorages are simpler to realize in situ, but international and national guidelines and code about C-FRP reinforcement, in case of complex load scheme (different from simple supported beam) do not give detailed information about how to calculate and realize C-FRP anchorages on cracked concrete.

In beam S-TM1-B, the greatest deformation had been measured at the middle level of the strip. Differently, the S-TM2 top and middle strip deformation were similar at the beginning, but then the middle deformations were smaller that the top ones. Top and middle deformations were again very similar at the end of the test. In both beams, the goal internal shear force was overtaken.

The final failure of shear reinforcement happened for debonding, probably due to strong compression deformations in concrete, together with tension in the strip. The simple evaluation of local strain in the strip does not allow to draw comprehensive conclusions concerning effectiveness. However, if we assume that a crack passes through strips 2 and 3, we may evaluate the contribution of the strips 2 and 3 with the measured maximum deformation ε = 0.001, each strip of two layers, the vertical C-FRP strip contribution in S-TM1-B is V = 115 kN. This is enough to guarantee the needed shear resistance.

Failure mechanism

The shear strengths of the two beam specimens S-TM1-B and S-TM2 were greater than the design one; therefore, it was proved that the retrofitting of the beam with C-FRP shear reinforcement was the exact solution. In fact, the collapse of beam occurred when the shear TB and bending moment MB at the support B were 384.86 kN and 396.00 kN m (F1 = 450 kN and F2 = 165 kN) or 416.49 kN and 396.00 kN m (F1 = 500 kN, F2 = 165 kN) for the beam S-TM1-B and S-TM2, respectively.

The obtained shear values were greater than the design one of 206 kN and about two times the experimental shear strength of the specimen S-TM1-A (181 kN) with retrofitting defects. The beam part between simple supports without cantilever, where the F1 force was applied did not presented significant damage. The failure of the retrofitted beams was characterized (Figs. 19, 20) by:

Fig. 19
figure 19

Retrofitted beam S-TM1-B without retrofitting construction defects damage after the failure test: a debonding of C-FRP strips; b concrete diagonal crack and buckling of the longitudinal rebars near the support with negative moments

Fig. 20
figure 20

Retrofitted beam S-TM2 without retrofitting construction defects: damage after the failure test a debonding of C-FRP strips; b concrete principal diagonal crack

  • debonding of C-FRP strips (Figs. 19a, 20a);

  • diagonal concrete cracks, passing through the two beam sides, which extend from the application point of the load F1 to the support B (Figs. 19b, 20b);

  • buckling of the original rebars between the stirrups (Fig. 19b), for S-TM1-B only.

The damage sequence for the beams consisted in:

  • one diagonal concrete crack from the original beam slab, in the section, where F1 was applied, to the C-FRP strip f4 and debonding phenomena on f4 strip when the shear TB was equal to about 251 kN and 210 kN for S-TM1-B and S-TM2, respectively (F1 = 300kN and F2 = 100kN for S-TM1-B, F1 = 250 kN and F2 = 85 kN for S-TM2). Some vertical cracks were evident on the slab near the support B in case of S-TM2;

  • new diagonal concrete cracks on the two sides of the original beam slab and web and large C-FRP local deformations when the shear in section B was equal to about 305 kN for each beam;

  • diagonal cracks widening and evident debonding of the C-FRP strip at the top section near the support B when the shear was equal to about 373 kN.

Conclusions

Two beams (TM1 and TM2) extracted from an existing RC building located in Rome and dated around 1930 have been retrofitted in bending by adding an RC slab and reinforced in shear with C-FRP strips, using the same provisions adopted in the real building. The retrofitted beams have been tested until failure to investigate the shear strength of C-FRP-reinforced concrete when submitted to a stress state typical of a beam of a frame structure, in the presence of negative bending and shear. After the realization of the cantilever, to create negative bending and shear at one end of the span, the retrofitting intervention consisted of two subsequent solutions. The beam TM1 had been first retrofitted as S-TM1-A specimen, but retrofitting provisions revealed unsatisfactory, due to premature fragile bending failure. A second retrofitting detailing was than applied to beam TM2, named S-TM2 beam specimen, and to a new intervention on TM1 on the opposite site, named S-TM1-B specimen. This second retrofitting detailing proved to be effective and was adopted.

The main conclusion of this study from the experimental evidence is that the shear strengthening of RC beams by externally bonded C-FRP sheets can be effective in providing additional shear resistance to existing members also for the analyzed loading scheme. The negative bending at the end of the cantilever, with the adopted provisions, does not render ineffective the shear reinforcement by U strips of C-FRP. When shear and negative bending develop simultaneously, shear cracks start from the beam extrados, supporting the FRP debonding if it is not adequately anchored. However, the simple C-FRP anchorages used for the retrofitted beams are resulted sufficient to guarantee the necessary shear strength improvement. In the first test on the beam S-TM1-A, debonding happened but for the crushing of compressed concrete at support B and not for cracking of the concrete in the tension zone of the section, where the C-FRP anchorages are applied. This failure could be easily avoided with a proper design of the compressed reinforcement. Each section of the retrofitted beam should show a ductile behavior until failure after the retrofitting intervention as crushing of compressed concrete and rebar buckling can produce debonding of the C-FRP shear reinforcement. This should be a serious concern in concrete frame retrofitting, and becomes even of larger consequences if C-FRP U strips are adopted.

S-TM1-A had some further inadequate detailing which reduced both the overall and the local ductility, related to flexural behavior or anchoring of connection between the new slab and the old beam. In the case at hand, the presence of not well-engineered solutions reduced the foreseen shear resistance to at least 50%.

The second interventions tested in lab with the realization of the specimen S-TM1-B and S-TM2, with the simple modification of some construction and retrofitting detailing, avoided brittle flexural failure and the detachment of the new slab assuring the target shear and bending strength. These beams showed more than doubled experimental shear resistances with respect to the one of the S-TM1-A beam. It was showed that, even in the presence of negative bending, the use of U C-FRP strips, without any particular anchorage provision, can solve possible needs of retrofitting. It seems obvious that the only real proof is a test like the one here presented.

Finally, this paper provides original experimental results, because the tested beams, removed from an existing building, give an effective evaluation of the strengthening intervention as in real-framed structures, where the shear forces are combined with negative moments at supports. The obtained experimental results significantly improve the database of full-size beams, available from literature, with flexural strengthening and shear FRP reinforcements.