Skip to main content
Log in

High Impedance Restricted Earth Fault Relay Settings: Impact of using Auxiliary Current Transformers at Neutral End for Ratio Matching

  • Original Contribution
  • Published:
Journal of The Institution of Engineers (India): Series B Aims and scope Submit manuscript

Abstract

This paper describes the impact on settings for high impedance Restricted Earth Fault Relays (REF) while using auxiliary CTs at neutral end to compensate for the mismatch between phase and neutral ratios for the power transformers. The idea of using auxiliary CTs is in itself not a new concept to compensate for the mismatch of current transformer ratios. However the derivation of REF settings is not easy and straightforward while using auxiliary CTs using conventional procedures. This paper uses detailed work sheets including varied parameters for phase and neutral CTs and derivation of REF settings therefrom. The necessity arises for use of auxiliary CTs while having to use an existing neutral CT of a different ratio from the phase CTs. In such a case there are two procedures for derivation of high impedance REF settings. One is to directly connect the REF relay across the phase and neutral CTs with a suitable REF setting. This procedure has already been described in an accompanying article (ref 10). But the current paper describes a different procedure of using auxiliary CTs at neutral end for compensating for the ratio mismatch between phase and neutral CTs and derive the REF settings suitably as described. It is claimed that this procedure with use of auxiliary CTs with detailed work sheets with detailed parameters for the CTs has not so far been used (Ref 1–23) in REF applications.

This is a preview of subscription content, log in via an institution to check access.

Access this article

Price excludes VAT (USA)
Tax calculation will be finalised during checkout.

Instant access to the full article PDF.

Fig. 1
Fig. 2
Fig. 3

Similar content being viewed by others

Abbreviations

CTR1:

CT Turns ratio on the phase side

CTR3:

CT Turns ratio of the neutral CT

IG:

Ground Current (considered as reference)

Isec1:

Secondary current phase side = IG/CTR1

Isec2:

Secondary current through auxiliary CT 

= Say (Isec21 + j Isec22)—Derived

Isec3:

Secondary current on neutral side = IG/CTR3

Xm3:

Excitation impedance, neutral CTs

Ie3:

Excitation amps, neutral CT secondary

Ie1:

Excitation amps (total) of phase side CTs

Xm1:

Excitation impedance of all phase CTs in parallel

RCT1:

Secondary resistance of CTs at phase end

Isec1:

Secondary current through phase CTs in parallel

RL1:

Total lead resistance from CTs to relay at phase end

RL:

Relay location

Rstab:

Stabilising resistor value (indicated as R in Fig. 1)

RCT2, CTR2 RL2, Ie2, Xm2:

similar parameters of the aux CT side

I1′, I2′:

Circulating currents described w.r.t Fig. 1

(I1′–I2′):

Relay current

References

  1. Alsthom Network Protection and Automation Guide (Protective Relays Measurement and Control), May 2011 edn. Micom 30 series, REF Protection application guide, Issue B1, Alsthom

  2. A comparison between high impedance and low impedance REF Transformer protection by Casper Labuschagne and Izak Vander Merwe, pp. 1–9. Eskom Enterprises and Schweitzer Engg (2005–2007)

  3. D. Robertson (ed.), Power System Protection Reference Manual, Reyrolle Protection, Chapter 6 (Orient Press)

  4. Performance of REF Protection scheme in the presence of CT remanence, ed. by K.J.A. Jallil, A.H.A. Bakae, W.N. Wan Mahadi, Hanif—Power Energy Conference, 2008 IEEE Second International

  5. Application Notes for KCGG High Impedance Protection by Alsthom T&D Protection and Control Ltd., Publication R6142B

  6. Application Guide for High Stability Circulating Current Relay, Alsthom Publication Ref R6136D

  7. Application Notes for High Impedance REF Protection, Section 2.3, Micom application guide NO. P64X/EN-AP/A32

  8. High impedance differential relaying. GE Power Management Document No: GE 3184 9. SIPROTEC Differential Protection Manual, 7UT612, V4.0, C53000, G1176-C148–1, Siemens

  9. SIPROTEC Differential Protection manual, 7UT612, V4.0 C53000, G1176-C148- 1, Siemens

  10. Practical Considerations For High Impedance Restricted Earth Fault Relay Settings. Journal of the Institution of Engineers (India), Series B, 12 July 2014.

  11. Interposing Current Transformers – Alsthom Application Guides ref Nos: GJ0104010, GJ0104020, GJ0104030

  12. . CSH30 Interposing Current Transformer ( Instruction Bulletin) Schneider Electric . Doc. No. 63230 -216-252A1-051-2007

  13. Interposing CT by CHK Power Quality

  14. . The essentials of CTs in power Circuits (theory and practice) by Edward – Dec 3rd, 2018 – Electrical Portal ( EEP) – Premium Membership

  15. . Auxiliary Current or Voltage Transformers (Indoor) , ABB product Bulletin

  16. Auxiliary Current Transformers for differential relay RADSS by ABB

  17. . Use of auxiliary CTs by Powell, document No. 01–01–4TB-066, Nov3, 1995.

  18. A new REF Protection , 2007 Canadian IEEE conference on Electrical and Computer Engg 2007, pp 276–279 by J. Tan. D Thelomier and H. Ivei.

  19. K. J. A. Jalil, A. H. A.. Baker, W. N. W. Mahadi and M. Salleh, “ Performance of REF Protection in the Presence of CT remenance, 2008 IEEE 2nd International Power and Energy conference, 2008 , pp 549 – 552

  20. A New Method of Transformer REF Protection, KRSTIVOJEVIC JP and DJVRIC, IEEEXplore – Advances in Electrical and Computer Engg, Vol 14, No3, 2014

  21. M. Davarpanah, M. Sanye Pasand, R. Iranami, Performance enhancement of transformer REF relay. IEEE Trans. Power Deliv. 28(1), 467–474 (2013)

    Article  Google Scholar 

  22. . IEEE guide for protective relay applications to power transformers, C37.91–2000

  23. . High impedance REF protection technical guidance notes, SIEMENS 2002

Download references

Acknowledgements

The authors are thankful to the Ministry of Electricity and Water Authority (KINGDOM OF BAHRAIN) for their encouragement and support during the preparation of this manuscript for publication.

Funding

No external source of funding was used.

Author information

Authors and Affiliations

Authors

Corresponding author

Correspondence to Subramanian Vanchier Payyalore.

Ethics declarations

Conflict of interest

The authors declare that they have no conflict of interest.

Additional information

Publisher's Note

Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Rights and permissions

Reprints and permissions

About this article

Check for updates. Verify currency and authenticity via CrossMark

Cite this article

Payyalore, S.V., Palanisamy, S. High Impedance Restricted Earth Fault Relay Settings: Impact of using Auxiliary Current Transformers at Neutral End for Ratio Matching. J. Inst. Eng. India Ser. B 103, 469–475 (2022). https://doi.org/10.1007/s40031-021-00638-x

Download citation

  • Received:

  • Accepted:

  • Published:

  • Issue Date:

  • DOI: https://doi.org/10.1007/s40031-021-00638-x

Keywords

Navigation