Optimization of a liquid desiccant based dedicated outdoor air-chilled ceiling system serving multi-zone spaces

  • Research Article
  • Building Systems and Components
  • Published:
Building Simulation Aims and scope Submit manuscript

Abstract

A liquid desiccant based dedicated outdoor air-chilled ceiling (DOAS-CC) system is proposed to serve a multi-zone space. The outdoor airflow rate and the supply air humidity ratio are two crucial variables in such a system, which significantly influence indoor thermal comfort, indoor air quality and energy consumption. Two strategies are presented to optimize these two variables in the study. They are the demand-controlled ventilation (DCV) strategy and the supply air humidity ratio set-point reset strategy. To evaluate the performances of these two strategies, a basic control strategy, i.e., the strategy adopting constant ventilation flow rate and constant supply air humidity ratio, is selected as the benchmark. Performances of the two strategies in terms of indoor air temperature, relative humidity and CO2 concentration as well as energy consumption are analyzed using simulation tests. The results show that the supply air humidity ratio set-point reset strategy is effective for the indoor air humidity control. It can save about 19.4% of total energy consumption during the whole year. The DCV-based ventilation strategy can further reduce about 10.0% of energy consumption.

This is a preview of subscription content, log in via an institution to check access.

Access this article

Price excludes VAT (USA)
Tax calculation will be finalised during checkout.

Instant access to the full article PDF.

Similar content being viewed by others

References

  • ASHRAE (2001). ANSI/ASHRAE Standard 62.1-2001. Ventilation for Acceptable Indoor Quality. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers.

    Google Scholar 

  • ASHRAE (2007). ANSI/ASHRAE Standard 62.1-2007. Ventilation for Acceptable Indoor Quality. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

    Google Scholar 

  • Capozzoli A, Mazzei P, Minichiello F, Palma D (2006). Hybrid HVAC systems with chemical dehumidification for supermarket applications. Applied Thermal Engineering, 26: 795–805.

    Article  Google Scholar 

  • Chen XY, Li Z, Jiang Y, Qu KY (2006). Analytical solution of adiabatic heat and mass transfer process in packed-type liquid desiccant equipment and its application. Solar Energy, 80: 1509–1516.

    Article  Google Scholar 

  • Hao XL, Zhang GQ, Chen YM, Zou SH, Moschandreas DJ (2007). A combined system of chilled ceiling, displacement ventilation and desiccant dehumidification. Building and Environment, 42: 3298–3308.

    Article  Google Scholar 

  • Imanari T, Omori T, Bogaki K (1999). Thermal comfort and energy consumption of the radiant ceiling panel system: comparison with the conventional all-air system. Energy and Buildings, 30: 167–175.

    Article  Google Scholar 

  • Jeong JW, Mumma SA, Bahnfleth WP (2003). Energy conservation benefits of a dedicated outdoor air system with parallel sensible cooling by ceiling radiant panels. ASHRAE Transactions, 109(2): 627–636.

    Google Scholar 

  • Kittler R (1996). Mechanical dehumidification control strategies and psychrometrics. ASHRAE Transactions, 102(2): 613–617.

    Google Scholar 

  • Klein SA, Beckman WA, Mitchell JW, et al. (2006). TRNSYS, A Transient Simulation Program, User Manual version 16.1, Solar Energy Laboratory, University of Wisconsin, USA.

    Google Scholar 

  • Liang CH, Zhang LZ, Pei LX (2010). Independent air dehumidification with membrane based total heat recovery: modeling and experimental validation. International Journal of Refrigeration, 33: 398–408.

    Article  Google Scholar 

  • Lim JH, Jo JH, Kim YY, Yeo MS, Kim KW (2006). Application of the control methods for radiant floor cooling system in residential buildings. Building and Environment, 41: 60–73.

    Article  Google Scholar 

  • Liu XH, Li Z, Jiang Y, Lin BR (2006). Annual performance of liquid desiccant based independent humidity control HVAC system. Applied Thermal Engineering, 26: 1198–1207.

    Article  Google Scholar 

  • Matsuki N, Nakano Y, Miyanaga T, Yokoo N, Oka T (1999). Performance of radiant cooling system integrated with ice storage. Energy and Buildings, 30: 177–183.

    Article  Google Scholar 

  • Mumma SA (2002). Chilled ceilings in parallel with dedicated outdoor air systems: addressing the concerns of condensation, capacity and cost. ASHRAE Transactions, 108(2): 220–231.

    Google Scholar 

  • Mumma SA, Jeong J (2005). Direct digital temperature, humidity and condensate control for a dedicated outdoor air-ceiling radiant cooling panel system. ASHRAE Transactions, 111(1): 547–558.

    Google Scholar 

  • Niu JL, Zhang LZ, Zuo HG (2002). Energy savings potential of chilled-ceiling combined with desiccant cooling in hot and humid climates. Energy and Buildings, 34: 487–495.

    Article  Google Scholar 

  • Stetiu C (1999). Energy and peak power savings potential of radiant cooling systems in US commercial buildings. Energy and Buildings, 30: 127–138.

    Article  Google Scholar 

  • Sun ZW, Wang SW, Ma ZJ (2011). In-situ implementation and validation of a CO2-based adaptive demand-controlled ventilation strategy in a multi-zone office building. Building and Environment, 46: 124–133.

    Article  Google Scholar 

  • Wang SW (1999). Dynamic simulation of building VAV air-conditioning system and evaluation of EMCS on-line control strategies. Building and Environment, 34: 681–705.

    Article  Google Scholar 

  • Wang SW, Jin XQ (1998). CO2-based occupancy detection for on-line outdoor air flow control. Indoor and Built Environment, 7: 165–181.

    Article  Google Scholar 

  • Wilkins CK, Kosonen R (1992). Cool ceiling system: a European air-conditioning alternative. ASHRAE Journal, August: 41–45.

  • Zhang LZ (2008). Heat and mass transfer in plate-fin sinusoidal passages with vapor-permeable wall materials. International Journal of Heat and Mass Transfer, 51: 618–629.

    Article  Google Scholar 

Download references

Author information

Authors and Affiliations

Authors

Corresponding author

Correspondence to Fu Xiao.

Rights and permissions

Reprints and permissions

About this article

Cite this article

Ge, G., Xiao, F. & Wang, S. Optimization of a liquid desiccant based dedicated outdoor air-chilled ceiling system serving multi-zone spaces. Build. Simul. 5, 257–266 (2012). https://doi.org/10.1007/s12273-012-0087-2

Download citation

  • Received:

  • Revised:

  • Accepted:

  • Published:

  • Issue Date:

  • DOI: https://doi.org/10.1007/s12273-012-0087-2

Keywords

Navigation