Abstract
The increasing capacity of nuclear units in power grid poses threat to system stability and security. Load disturbance may cause overspeed of the units and trigger the overspeed protection controller (OPC). Repeating actions of valves have a strong impact on the security of the equipment and may result in a collapse of the power system. Based on the analysis of frequency regulation, mathematic models for nuclear units in the grid are established in this paper to simulate the dynamic process when load disturbance occurs. The critical action of the OPC is proposed as the constraint of safe operation for the units. The relationship between different styles of frequency regulation and the allowable capacity of the nuclear units in the grid is discussed. This research can help to estimate the capacity limitation of nuclear units in the grid.
Similar content being viewed by others
References
Dai Y P, Zhao P, Chang S P. Primary frequency control characteristic of a grid. In: Proceedings of the 3rd IEEE Conference on Industrial Electronics and Applications, Singapore, 2008, 1493–1497
Younkins T D, Johnson L H. Steam turbine overspeed control and behaviour during system disturbances. IEEE Transactions on Power Apparatus and Systems, 1981, PAS-100(5): 2504–2511
Kundur P, Lee D C, Bayne J P, Dandeno P L. Impact of turbine generator overspeed controls on unit performance under system disturbance conditions. IEEE Transactions on Power Apparatus and Systems, 1985, PAS-104(6): 1262–1269
Gao L, Dai Y P. Impact of overspeed protection control on stability for islanded power system. International Journal of Emerging Electric Power Systems, 2009, 10(6): 1–9
Yu D R, Guo Y F, Xu J Y. The primary frequency regulation stability of parallel turbo-generators. Proceedings of the CSEE, 2000, 20(9): 59–63
Zhang Z Y, Cai Y J. Automatic Control of Turbomachinery. Xi’an: Xi’an Jiaotong University Press, 1993
Guo Y F, Xu Z Q, Yu D R, Zhao T. The design of secondary frequency regulation loop considering regulation dead band. Proceedings of the CSEE, 2004, 24(10): 77–81
Author information
Authors and Affiliations
Corresponding author
Rights and permissions
About this article
Cite this article
Dai, Y., Jiang, P., Gao, L. et al. Capacity limitation of nuclear units in grid based on analysis of frequency regulation. Front. Energy 6, 148–154 (2012). https://doi.org/10.1007/s11708-012-0174-1
Received: