Examination of Variable Frequency Drive Transformer Copper Cooling Line Failures from Nuclear Power Plants

  • Andrew Ruminski
Technical Article---Peer-Reviewed
  • 79 Downloads

Abstract

The findings from a failure examination on copper cooling lines from nuclear power plant transformer cooling systems are discussed in this article. The failures occurred prior to regular service at two different nuclear power plants during installation and qualification testing. A failure examination including—light optical microscopy, scanning electron microscopy, metallography, and microhardness—was conducted on the fractured lines. The fractures predominately had fatigue striation morphologies, but were found to have initiated in areas exhibiting intergranular cracking, secondary cracking, and surface pitting. Additionally, evidence of phosphorus rich particles was found in the IG crack regions. The failures are hypothesized to be the result of outside diameter environmentally initiated cracking, assisted by residual stresses from brazing, and propagated by fatigue.

Keywords

Intergranular cracking Fatigue cracking Scanning electron microscope Metallography Microhardness Copper Failure analysis 

Notes

Acknowledgments

The author is grateful for the support of the following individuals who supported this investigation: J. Nelson, R. Rees, M. Fitz, R. Jacko, and D. Love.

References

  1. 1.
    M. Stevenson, M. Barkey, J. McDougall, Stresses in bent copper tubing: application to fatigue and stress-corrosion cracking failure mechanisms. J. Fail. Anal. Prev. 5, 25–29 (2005)CrossRefGoogle Scholar
  2. 2.
    H. Miyamoto, D. Saburi, H. Fujiwara, A microstructural aspect of intergranular stress corrosion cracking of semi-hard U-bend tubes of commercially pure copper in cooling systems. Eng. Fail. Anal. 26, 109–119 (2012)CrossRefGoogle Scholar
  3. 3.
    D. Duffner, Air conditioner failure investigation—intergranular cracking in a pure copper condense tube. J. Fail. Anal. Prev. 5, 79–85 (2005)CrossRefGoogle Scholar
  4. 4.
    J. McDougall, M. Stevenson, Stress corrosion cracking in copper refrigerant tubing. J. Fail. Anal. Prev. 5, 13–17 (2005)CrossRefGoogle Scholar
  5. 5.
    B. Kuzńicka, K. Junik, Intergranular stress corrosion cracking of copper—a case study. Corros. Sci. 49, 3905 (2007)CrossRefGoogle Scholar
  6. 6.
    Y. Yagodzinskyy, E. Malitckii, T. Saukkonem, H. Hänninen, Hydrogen-enhanced creep and cracking of oxygen-free phosphorus-doped copper. Scr. Mater. 67, 931–934 (2012)CrossRefGoogle Scholar
  7. 7.
    W. Liu, M. Bayerlein, H. Mughrabi, A. Day, P. Quested, Crystallographic features of intergranular crack initiation in fatigued copper polycrystals. Acta Metall. Mater. 40, 1763–1771 (1992)CrossRefGoogle Scholar
  8. 8.
    D. Thompson, D. Tracy, Influence of composition on the stress corrosion cracking of some copper-base alloys. Trans. Am. Inst. Mining Met. Eng. 185, 100–109 (1949)Google Scholar

Copyright information

© ASM International 2016

Authors and Affiliations

  1. 1.Westinghouse Electric Company - Materials Center of ExcellencePittsburghUSA

Personalised recommendations