, Volume 14, Issue 3, pp 303–306 | Cite as

Premature Failure of Ductile Iron Pump Impeller in Cooling Tower System

  • Pankaj Sharma
Case History---Peer-Reviewed
  • 209 Downloads

Abstract

The root cause of corrosion of a pump impeller in a cooling water system is investigated. The impeller material was made of ductile cast iron. The pump failure was encountered after eight months of operation. A detailed visual examination, microstructure examination, and water analysis were carried out to ascertain the probable cause of failure. Finally, the obtained results infer that the solid-particle containing fluid flow was responsible for erosion–corrosion in the impeller failure.

Keywords

Erosion–corrosion Pump impeller Cast iron Ductile iron Failure 

References

  1. 1.
    Christian Brix Jacobsen, Book, The Centrifugal Pump, Structural and Fluid Mechanics, R&D, GrundfosGoogle Scholar
  2. 2.
  3. 3.
    R.J. Parrington, Cavitation Erosion of a Zirconium Pump Impeller in an Aqueous Hydrochloric Acid Service Environment, by IMR Test LabsGoogle Scholar
  4. 4.
    H.P. Bloch, Root Cause Analysis of Five Costly Pump Failures, Process Machinery Consulting, Montgomery, TXGoogle Scholar
  5. 5.
    R. Celin, F. Tehovnik, F. Vodopivec, B. Zuzek, Impeller-Blade Failure Analysis. Mater. Technol. 47(2), 253–258 (2013)Google Scholar
  6. 6.
    A. Saha, H. Roy, A.K. Shukla, Investigation into the Probable Cause of Failure of Economiser Tube of a Thermal Power Plant. J. Fail. Anal. Prev. 10, 187–190 (2010)CrossRefGoogle Scholar
  7. 7.
    ASTM Standard A536 - 84(2009), Standard Specification for Ductile Iron Castings Google Scholar
  8. 8.
    S. Tandon, M. Gao, R. Mcnealy, Erosion–Corrosion Failure of A Carbon Steel Pipe Elbow, Paper No. 09479Google Scholar
  9. 9.
    D.I. Lee, H.C. Lim, Erosion–corrosion damages of water-pump impeller. Int. J. Auto. Technol. 10, 629–634 (2009)CrossRefGoogle Scholar
  10. 10.
    S. Ariely, A. Khentov, Erosion corrosion of pump impeller of cyclic cooling water system. Eng. Fail. Anal. 13, 925–932 (2006)CrossRefGoogle Scholar

Copyright information

© ASM International 2014

Authors and Affiliations

  1. 1.Research & DevelopmentBuckmanMemphisUSA

Personalised recommendations