Calculations show that to prevent the oscillatory instability of the flow in a PK-47 once-through boiler, it is necessary to install /12 mm orifice plates at the inlet of its bottom radiant section. Load-reduction tests on the boiler with such plates of a 200-MW power unit at constant turbine inlet pressure confirm the reliable operation of the unit in a load range of 80 – 200 MW.
Similar content being viewed by others
References
V. A. Lokshin, D. F. Peterson, and A. L. Schwarz (eds.), Standard Methods of Hydraulic Design for Power Boilers, Hemisphere, New York (1988).
L. M. Yanchuk, L. M. Kofman, A. V. Khudyak, and Yu. G. Obikhod, “Reliability of a gas-fired once-through boiler at low loads,” Élektr. Stantsii, No. 7 (1975).
Author information
Authors and Affiliations
Additional information
Translated from Élektricheskie Stantsii, No. 1, January 2013, pp. 49 – 54.
Rights and permissions
About this article
Cite this article
Belyakov, I.I., Breus, V.I. & Barannikov, A.B. Using thermal test data to determine the minimum load of a 200-MW power unit with a PK-47 boiler at the Zainsk power station. Power Technol Eng 47, 133–138 (2013). https://doi.org/10.1007/s10749-013-0410-9